Report of Inspection/Test
Semi-Annual Dry,Wet
March 20, 2007
Property Owner/Agent
Prior Lake Fire Station #1
16776 Fish Point Road SE
Prior Lake, MN
~ AUTOMATIC SPRINKLER co.
10351 Jamestown 81. NE - Blaine, MN 55449
Tel (763) 784-8902 Fax (763) 784-5787
Conducted by: Joel Hirsch
Inspection Ref: 9518
System Off 11.00 Monitoring Company Operator Alarm Panel/Code
MetroAlarm X
System On 1 :00
Inspector - Signature
~~
3/25/07
11:11 am
I state that the information on this form is correct at the
time and place of my inspection, and that all equipment
tested at this time was left in operational condition upon
comoletion of this insoection exceot as noted.
Owner - Printed
Bob Hutchins
Owner - Signature
Date
3/25/07
11:11 am
Except as noted, the building is occupied with the same
occupancy classification and hazard of contents as last
inspection. Also, the system has remained in service
without modification and been free of actuation of devices
or alarms.
Gauges on wet pipe system in good condition and showing normal water supply pressure?
Alarm devices free from physical damage?
Hydraulic nameplate, if provided, securely attached to riser and legible?
Valve switches indicate movement?
Visible and accessible?
Couplings and swivels not damaged and rotate smoothly?
Plugs or caps in place and undamaged?
Gaskets in place and in good condition?
Identification sign(s) in place?
Check valve is not leaking?
Automatic drain valve in place and operating properly?
Interior free of obstructions (if caps are not in place) ?
Valve over its full are not in
In good condition?
Free of mechanical damage and not leaking?
No external corrosion?
Properly aligned?
No external loads ?
Visible pipe hangers and seismic braces not damaged or loose?
Was an obstruction conducted and the flushed?
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Sprinkler wrench with spare sprinklers?
Proper number and type of spare sprinklers?
Free of corrosion?
Free of obstructions to spray patterns?
Free of foreign materials including paint?
Free of physical damage?
Are all sprinklers in service dated 1920 or later?
Print Date: 4/4/2007
(All "NO" answers are to be fully explained)
Copywrite 2002-5 Life Safety Inspector, OnSite Software, Inc.
Page 1 of 3
Report of Inspection/Test
Semi-Annual Dry,Wet
March 20, 2007
Property: Prior Lake Fire Station #1
Owner:
l}~.~,jl~.,~'~!.."'UTOMA1K SPRINKLER CO.
Inspection Ref: 9518
Yes
Fast Response sprinklers in service for less than 20 years? If "no" test sample now and every
10 years.
Standard sprinklers less than 50 years old? If no test sample now and every 10 years.
If sprinklers have been replaced, were they proper replacements?
Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating
for which show no of
Yes
NA
NA
Yes
NA
NA
Yes
Yes
Yes
Enclosures around dry-pipe, preaction or deluge valves maintaining a of 400 F?
Gauges on dry, preaction and deluge systems in good condition and showing normal air and
water pressure?
Free from physical damage?
Trim valves in appropriate (open or closed) position?
No leakage from intermediate chamber?
Interior of dry pipe, preaction and deluge valves passed internal inspection (required every 5th
year if resetable without opening)?
Priming water level correct?
Low air pressure signal passed test?
Quick opening devices passed test?
Automatic air maintenance devices on dry pipe and preaction systems passed test?
Dry pipe systems being maintained in dry condition?
Interior of dry pipe, preaction and deluge valves cleaned?
Yes
Yes
Yes
Yes
Outlet Pressure (psi) Alarms Waterflow Results
System Connection devices comparable
Flowed Size Static Resid Static Actuate pass test to prior test
Main Main drain 2 103 72 82 NA NA Yes
Test valve 1 wet Inspector's test 1/2 Yes Yes Yes
system
.!!:! -0 -0
t/) <ll >.~ <ll <ll
.... <ll r::: t/) t/) E~
Description o > Type .!:! Secured <ll :::: t/) r::: 'u
~C; en Co t/) t/) .~ ... ! .g
> 0 t1l <ll <ll
W t) en >< en.c
t) w ::l
<l: .....I
Control Valve Chart/lnsp/Maint OS&Y 4" Supervised Yes Yes Yes Yes Yes
Control Valve Chart/lnsp/Maint Butterfly 4" Supervised Yes Yes Yes Yes NA
Control Valve Chart/lnsp/Maint Butterball 2" Supervised Yes Yes Yes Yes NA
Print Date: 4/412007
(AII"NO" answers are to be fully explained.)
Copywrite 2002-5 Life Safety Inspector, OnSite Software, Inc.
Page 2 of 3
Report of Inspection/Test
Semi-Annual Dry,Wet
March 20, 2007
Property: Prior Lake Fire Station #1
Owner:
~~AUTOMAnc SPRINKLER CO.
Inspection Ref: 9518
Dry Valve Size: 2" Year: 1992 Q.O.D. No QOD Year:
Make Model Serial no. Make Model Serial no.
Star A 042992
Time water
Time to Trip Water Air Trip point reached test Alarm
thru test pipe Pressure Pressure air pressure outlet Operated
No Q.O.D. sec 82 psi 37 psi 1 psi sec Yes
Comparable to previous tests? NA