HomeMy WebLinkAboutReport of Inspection 3/25/2007 Report of Inspection/Test Semi-Annual Dry,Wet March 20, 2007 Property Owner/Agent Prior Lake Fire Station #1 16776 Fish Point Road SE Prior Lake, MN ~ AUTOMATIC SPRINKLER co. 10351 Jamestown 81. NE - Blaine, MN 55449 Tel (763) 784-8902 Fax (763) 784-5787 Conducted by: Joel Hirsch Inspection Ref: 9518 System Off 11.00 Monitoring Company Operator Alarm Panel/Code MetroAlarm X System On 1 :00 Inspector - Signature ~~ 3/25/07 11:11 am I state that the information on this form is correct at the time and place of my inspection, and that all equipment tested at this time was left in operational condition upon comoletion of this insoection exceot as noted. Owner - Printed Bob Hutchins Owner - Signature Date 3/25/07 11:11 am Except as noted, the building is occupied with the same occupancy classification and hazard of contents as last inspection. Also, the system has remained in service without modification and been free of actuation of devices or alarms. Gauges on wet pipe system in good condition and showing normal water supply pressure? Alarm devices free from physical damage? Hydraulic nameplate, if provided, securely attached to riser and legible? Valve switches indicate movement? Visible and accessible? Couplings and swivels not damaged and rotate smoothly? Plugs or caps in place and undamaged? Gaskets in place and in good condition? Identification sign(s) in place? Check valve is not leaking? Automatic drain valve in place and operating properly? Interior free of obstructions (if caps are not in place) ? Valve over its full are not in In good condition? Free of mechanical damage and not leaking? No external corrosion? Properly aligned? No external loads ? Visible pipe hangers and seismic braces not damaged or loose? Was an obstruction conducted and the flushed? Yes Yes Yes Yes Yes Yes Yes Sprinkler wrench with spare sprinklers? Proper number and type of spare sprinklers? Free of corrosion? Free of obstructions to spray patterns? Free of foreign materials including paint? Free of physical damage? Are all sprinklers in service dated 1920 or later? Print Date: 4/4/2007 (All "NO" answers are to be fully explained) Copywrite 2002-5 Life Safety Inspector, OnSite Software, Inc. Page 1 of 3 Report of Inspection/Test Semi-Annual Dry,Wet March 20, 2007 Property: Prior Lake Fire Station #1 Owner: l}~.~,jl~.,~'~!.."'UTOMA1K SPRINKLER CO. Inspection Ref: 9518 Yes Fast Response sprinklers in service for less than 20 years? If "no" test sample now and every 10 years. Standard sprinklers less than 50 years old? If no test sample now and every 10 years. If sprinklers have been replaced, were they proper replacements? Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating for which show no of Yes NA NA Yes NA NA Yes Yes Yes Enclosures around dry-pipe, preaction or deluge valves maintaining a of 400 F? Gauges on dry, preaction and deluge systems in good condition and showing normal air and water pressure? Free from physical damage? Trim valves in appropriate (open or closed) position? No leakage from intermediate chamber? Interior of dry pipe, preaction and deluge valves passed internal inspection (required every 5th year if resetable without opening)? Priming water level correct? Low air pressure signal passed test? Quick opening devices passed test? Automatic air maintenance devices on dry pipe and preaction systems passed test? Dry pipe systems being maintained in dry condition? Interior of dry pipe, preaction and deluge valves cleaned? Yes Yes Yes Yes Outlet Pressure (psi) Alarms Waterflow Results System Connection devices comparable Flowed Size Static Resid Static Actuate pass test to prior test Main Main drain 2 103 72 82 NA NA Yes Test valve 1 wet Inspector's test 1/2 Yes Yes Yes system .!!:! -0 -0 t/) <ll >.~ <ll <ll .... <ll r::: t/) t/) E~ Description o > Type .!:! Secured <ll :::: t/) r::: 'u ~C; en Co t/) t/) .~ ... ! .g > 0 t1l <ll <ll W t) en >< en.c t) w ::l <l: .....I Control Valve Chart/lnsp/Maint OS&Y 4" Supervised Yes Yes Yes Yes Yes Control Valve Chart/lnsp/Maint Butterfly 4" Supervised Yes Yes Yes Yes NA Control Valve Chart/lnsp/Maint Butterball 2" Supervised Yes Yes Yes Yes NA Print Date: 4/412007 (AII"NO" answers are to be fully explained.) Copywrite 2002-5 Life Safety Inspector, OnSite Software, Inc. Page 2 of 3 Report of Inspection/Test Semi-Annual Dry,Wet March 20, 2007 Property: Prior Lake Fire Station #1 Owner: ~~AUTOMAnc SPRINKLER CO. Inspection Ref: 9518 Dry Valve Size: 2" Year: 1992 Q.O.D. No QOD Year: Make Model Serial no. Make Model Serial no. Star A 042992 Time water Time to Trip Water Air Trip point reached test Alarm thru test pipe Pressure Pressure air pressure outlet Operated No Q.O.D. sec 82 psi 37 psi 1 psi sec Yes Comparable to previous tests? NA