HomeMy WebLinkAboutInspection Report 2/28/2008
I nspection Report
GILBERT MECHANICAL CONTRACTORS, INC.
4451 w. 76th St. - Minneapolis, MN 55435
Office phone 952-835-3810 Fax 952-835-4765
Inspection # 2589
Inspection Date: 02/28/2007
Billing Information:
Name: Kwik Trip
Address: PO Box 2107
Address: 1626 Oak Street
City, State, Zip: LaCrosse, WI 54602
Job Information:
Kwik Trip #423
14160 Wilds Path NW
Prior Lake, MN 55372
-- -
- - ---- - --- --- --~--- -~----- - ~ ------ -- - ---~---- - - --- - -
1. GENERAL
Yes
N/A
No'
a. Is the building occupied? x I
b. Is occupancy same as previous inspection? X I
c. Are all the systems in service? x
d. Are all fire protection systems same as last inspection? X I
e. Is hazard completely sprinkled? X
f. Are all new additions and building changes properly protected? X
g. Is all stock or storage properly below sprinkler piping? X
h. Was property free of fire since last inspection? (Explain any fire on Page 2) X
I. In areas protected by wet system, does the building appear to be properly heated in all areas, including blind attics X
and perimeter areas and are all exterior openings protected against entrance of cold air? x
2. CONTROL VALVES (See Section 16)
a. Are all sprinkler system main control valves open?
b. Are all other valves in proper position?
c. Are all control valves in ood condition and sealed or supervised?
3. WATER SUPPLIES (See Section 17)
a. Was a water flow test made and results satisfactory?
4. TANKS. PUMPS. FIRE DEPARTMENT CONNECTIONS
a. Are fire pumps, gravity tanks, reservoirs and pressure tanks in good condition and properly maintained?
b. Are fire department connections in satisfactory condition, couplings free, caps in place and check valves tight?
5. WET SYSTEMS (See Section 13)
N/A
No'
a. Are cold weather valves open or closed as necessary? X
b. Have antifreeze systems been tested and left in satisfactory condition? x
c. Are alarm valves, water flow indicators and retards in satisfactory condition? X
6. DRY SYSTEMS (See Section 14)
Yes
N/A
No.
a. Is dry valve in service and in good condition? X
b. Is air pressure and priming water level normal? X
c. Is air compressor in good condition? X
d. Were low points drained during fall and winter inspection? X
e. Are Quick Opening Devices in service? X
f. Has piping been checked for stoppage within past 10 years? X
g. Has piping been checked for proper pitch within past 5 years? X
h. Have dry check valves been trip tested satisfactorily as required? X
I. Are dry valves adequately protected from freezing? X
j. Valve house and heater condition satisfactory? x
7. SPECIAL SYSTEMS (See Section 18)
Yes
N/A
No'
a. Were valve systems tested as required? X
b. Were all heat responsive systems tested and results satisfactory? X
c. Were supervisory features tested and results satisfactory? X
8 ALARMS
Yes
N/A
No'
a. Water motor and gong test satisfactory? X
b. Electric alarm test satisfactory? X
c. Supervisory alarm service test satisfactory? X
9. SPRINKLERS - PIPING
a. Are all sprinklers in good condition, not obstructed, and free of corrosion or loading?
b. Are all sprinklers less than 50 years old?
c. Are extra sprinklers readily available?
d. Is condition of piping, drain valves, check valves, hangers, pressure gauges, open sprinklers, strainers satisfactory?
e. Are all sprinklers of proper temperature rating?
f. Are portable fire extinguishers in good condition?
g. Is hand hose on sprinkler systems satisfactory?
Yes
N/A
No'
*Explain "No" answers on Page 2
GILBERT MECHANICAL CONTRACTORS, INC.
4451 w. 76th St. - Minneapolis, MN 55435
Date: 02/28/2007
Inspection # 2589
Inspector: Dean Kaminski
10. Date Dry System Piping last checked for stoppage:
11. Date Dry System Piping last checked for proper pitch:
12. Date Dry Pipe Valve last trip tested:
13. Wet Systems: 1 Make and Model?
14. Dry Systems: 2 Make and Model?
15. Special Systems: Type?
Make and Model?
4" - 40 Second Retard
(1) 4" Tyco DPV-1 (1) 3" Tyco DPV-1
16. CONTROL VALVES Open Secured Closed Signs Condition
Number Type Yes No Yes No Yes No Yes No
City Connection Control Valve 2 BFV x x x x
Dry System 2 BFV x x x x
Sectional Control Valves
System Control Valves 1 BFV x x x x
17. WATER FLOW TEST
Water Pressure?
85
CITY PSI
TANK PSI
FIRE PUMP PSI
Water Flow Test? (If none made, Why?)
Size Pressure Flow Pressure Size Pressure Flow Pressure
Test Pipe Located Test Pipe Before Pressure After Test Pipe Located Test Pipe Before Pressure After
Storaqe Room 2" 85 70 85
18. HEAT RESPONSIVE DEVICES: Type ofTest?
Valve # A B C D E F Valve # A B C D E F
Valve # A B C D E F Valve # A B C D E F
Valve # A B C D E F Valve # A B C D E F
Valve # A B C D E F Valve # A B C D E F
Auxiliary Equipment? Number? Type? Location? Test Results?
19. EXPLANATION OF ANY "NO" ANSWERS:
20. RECENT CHANGES IN BUILDING OCCUPANCY OR FIRE PROTECTION EQUIPMENT:
21. ADJUSTMENT OR CORRECTIONS MADE:
22. DESIRABLE IMPROVEMENTS:
GILBERT Mechanical Contractors, Inc. DATE: 02/28/2007
4451 W. 76th St. - Minneapolis, MN 55435 INSPECTION # 2589
INSPECTOR: Dean Kaminski
----- - -- --~----- - -- - --- --~--- - -~~--- ---- - ---~----- -
DRY PIPE VALVE TRIP TEST REPORT
- -- --------~---~ --- - -- ---~--- ------- -------- --- --------- - -- -~- --
Kwik Trip #423
14160 Wilds Path NW
Prior Lake, MN 55372
NOTE: BEFORE ANY DRY PIPE VALVE IS TRIP TESTED, THE WATER SUPPLY LINE TO IT SHOULD BE THOROUGHLY FLUSHED. THE TWO INCH
DRAIN BELOW THE VALVE SHOULD BE OPENED WIDE AND WATER AT FULL PRESSURE SHOULD BE DISCHARGED LONG ENOUGH TO CLEAR
PIPE OF ANY ACCUMULATION OF SCALE OR FOREIGN MATERIAL. IF THERE IS A HYDRANT ON THE SUPPLY LINE, THIS HYDRANT SHOULD BE
FLUSHED BEFORE THE TWO INCH IS OPENED. THE DRIP VALVE ON THE DRY PIPE VALVE SHOULD BE CHECKED BEFORE TRIPPING THE DRY
PIPE VALVE, TO SEE THAT IT IS IN OPERATING CONDITION.
DRY PIPE VALVES SYSTEM #1 SYSTEM #2 SYSTEM #3 SYSTEM #4
Valve Serial Number
Manufacturer Tyco Tyco
Valve Model Number DPV-1 DPV-1
Valve Size 4" 3"
Controlling Number Sprinklers (approximately) 100 40
Date Last Trip Test
Date Last Operated
Pressure Before Test: Air 34 34
Water 85 85
Size And Location Of Test Valve
Was Gate Valve Below Dry Valve Open Wide No No
at Test? (If not, how many turns) 4 Turns 4 Turns
Air Pressure 14 14
Water Trip At: Water Pressure 85 85
Time 60 10
If System Flooded, List Time Water Reached
Test Openings No No
PERFORMANCE SYSTEM #1 SYSTEM #2 SYSTEM #3 SYSTEM #4
Valve Condition Interior Of Body
Moving Parts
GOOD Rubber Facing
Seats
Reset? Good Good
Did Alarms Operate At Trip Test? Yes Yes
All Low Point Drains Blown Out? Yes Yes
Water Control Valve Left Open And Sealed? Yes Yes
Alarm Control Valve Left Open And Sealed? Yes Yes
QUICK OPENING DEVICES SYSTEM #1 SYSTEM #2 SYSTEM #3 SYSTEM #4
Device Serial Number
Manufacturer
Type And Model
Air Pressure In Upper Chamber
Quick Opening Device Tripped At
Performance
Quick Opening Device Left In Service And
Control Valve Open And Sealed
Conferred With
Date