AGREEMENT AND REPORT OF INSPECTION
#INSPECTION "Z.. \ t l 7 ~
REPORT TO
STREET
SHEET 1 of 2, Use separate sheet for each building inspected
MINNESOTA LICENSE NO. COO5
- '1
~~e..
, bC{ C):":;'
BUILDING OR LOCATION
INSPECTOR
DATE
CITY & STATE
Owner hires Viking Automatic Sprinkler Company to conduct an inspection of the fire suppression system at the above location or building, and
prepare a written report of that inspection for an agreed upon fee. As part of this agreement, owner agrees to terms and conditions on rear of form and
will complete the Owner's Section of this document.
Owner's Section (fo be answered by Owner or Occupant) 1\ .
A. Explain any occupancy hazard chanRes since the previous inspection: ;' Ii (')
I
f\/~I\.e.J
,
B, Describe fire protection modifications made since last inspection:
"
A / 'Fjf\,p ,
/ -
J
(' ~ /4l /;; c!J
C. Describe any fires since last inspection:
D, When was the system piping last checked for stoppaRe, corrosion or forei;w !!!3tetiaI? , j
E, ''''hen was th.e dry.. -Po iping system last checked for proper Pitch?~. . LV.. a L--
F. Are dry v~v.~ ad~quatelY p otjted from freezinR? , 1 . , ~. ,\') ~ .
Si~ature' it -' '0 A'i. h.~ Title Pit, /1 ~-( 51 d C,d-Date
Inspector's Section (All responses reference current inspection) N/A = NOT APPLICABLE
1 General
a. Is the building occupied? ~es 0 No
b. Are all systems in service? )lQ'es 0 No
c, Does there appear to be a minimum of 18 in, (457 rom) clearance between the top of the storaRe and the sprinkler deflectors? X Yes 0 No
d, Does the valve hose on the sprinkler system(s) appear to be satisfactory? 0 Yes 0 No XNj A
2 Control Valves (See Item 15) .
a, Do sprinkler system control valves appear to be in the appropriate open or closed position? /J(Yes 0 No
b, Are control valves in the open position locked, sealed or equipped with a tamper switch? \1\ Yes 0 No
3 Water Supplies (See Item 16) r
a. Was a water flow test of main drain made at the sprinkler riser(s)? 0 Yes ~NO
4 Tanks, Pumps, Fire Department Connections
a. Are fire pumps, gravity tanks, reservoirs and pressure tanks in good condition and properly maintained? 0 Y~\-r 0 No ~j A
b. Are fire department connectio~satisfactory condition, couplings free, caps in place, and check valves tight?11 Yes 6No 0 Nj A
Are they accessible and VlSible~,,\ Yes 0 No 0 Nj A
5 Wet Systems .
a. Are cold weather valves (0.5. & Y.) in the appropriate open or closed position? JX:res 0 No 0 Nj A
b. Have antifreeze system solutions been tested? 0 Yes 0 No ~Nj A
c. Were the antifreeze test results satisfactory? 0 Yes 0 No ~ Nj A
d. In areas protected by wet system(s), does the buildinR appear to be properly heated in all areas, including blind attics and perimeter areas
where accessible? /fYes 0 No 0 Nj A Do all exterior openings appear to be protected against freezing?~Yes 0 No 0 Nj A
6 Dry System (See Items 11 to 13)
a. Aredryvalves(s)inservice?)(Yes DNo DNjA ~'
b. Are the air pressures and priminR water levels in accordance Wl~ the manufacture's instructions? Yes 0 No 0 Nj A
c. Hastheoperationoftheairornitrogensuppliesbeentest~J. es DNo DNjA Aretheyinservi ? DYes DNo DNjA
d. Were all know low points drained during this ins~on? ~ Ye 0 No 0 Nj A
e. Did quick-opening devices operate satisfactorily? AYes 0 No 0 Nj A
f, Did the dry valve(s) trip properly during the trip pressure test? \.(yes D No D Nj A
g, Did the heating equipment in the dry-pipe valve room(s) opera~t time of inspection? ~Yes 0 No 0 Nj A
7 Special Systems (See Item 14)
a. Did the deluge or pre-action valves operate properly during testing? 0 Yes 0 No')(Nj A
b. Did the heat-responsive devices operate properlx 1urin~ testing? 0 Yes 0 No 'Yfi! A
c. Did supervisory devices operate durinR testing? AYes 0 No 0 Nj A
8 Alarms
a. Did water motor(s) and gong(s) test satisfactorily? 0 Yes 0 No ~ Nj A
b. Did electric alarm(s) test satisfactory? \fYes 0 No 0 Nj A (\
c. Did supervisory alarm service test sa~lactory?~ Yes 0 No 0 Nj A
9 Sprinklers
a. Do visible sprinklers appear to be free from corrosion, loadinR or obstruction to spray discharRe? V Yes 0 No
b. Are sprinklers less than 50 years old? (Older sprinklers require sample testinR) 0 Yes )(No ^
c. Are quick response and residential sprinklers less than 20 years old? (Older sprinklers r~uire sample testinR) 0 Y es ~. No 0 N j A
d. Is stock of spare sprinklers available? )(Yes D No
e. Does the exterior condition of sprinklJr ~ystem appear to be satisfactory? i(../y es 0 N.o
f. Do visible sprinklers appear to be of proper teJ!l.perature ;;ating for their lo!itions?!,!s 0 No
10 lWlain~ "No" ~wers I)d c.~ o--~>~.'; IY ") ... . " .' ;;0 _ "' .
~ ! ~
V\
--
~.M:I"Gi
AUTOMATIC SPRINKLER CO.
Setting The Standard...
St. Paul, Minnesota :':'11/
(651) 558-3300 . (800) 229-6263
Fax: (651) 558-3310
SHEET 2 of 2 - Use separate sheet for each system inspected
System No. or Description if multiple
systems .
Inspection Report
No. "2-\ \ '\ je.:,
11 Date dry-pipe valve trip tested (control valve partially open)
12 Date dry-pipe valve trip tested (contro,l valve ~llY open)
13 Date quick-opening device tested (A7) q C/.Y
DRY VALVE / I
MAKE MODEL
k~ I
DRY PIPE
OPERATING
TEST
Time to Trip
Thru Test Pipe
MIN, SEe.
(See Trip Test Table which follows)
(See Trip Test Table which follows)
( ee Trip Test Table which follows)
SERIAL NO.
PSI
PSI
PSI
Time Water Reached
Test Outlet
MIN. SEe.
Alarm Operated
Properly
YES NO
Water
Pressure
Air
Pressure
Trip Point
Air Pressure
n \. 1'\
r t:.........1' r,-Ji..
Without
Q.o.IJ
With
Q.O.D
8'
'/
DELUGE &
PREACTION
V ALVES
Operation o PNEUMATIC o ELECTRIC o HYDRAUliC
Piping Supervised DYES D NO IDetecting Media Supervised DYES D NO
Does valve operate from the manual trip and/ or remote control stations D YES o NO
Is there an accessible facility in each circuit for testing DYES D NO IMethod ofTesting Circuits
Does each circuit operate Does each circuit Maximum time to
MAKE MODEL supervision loss alarm operate valve release operate release
YES I NO YES T NO YES I NO
I I I
(See Trip Test Table which follows)
TRIP TEST TABLE
14 Date deluge or preaction valve tested
15 See Control Valve Maintenance Table
Explain
Abnormal
Control Valves Number Tvpe Open Secured Closed Signs Condition
City Control Valves
Bypass Valves
Tank Control Valves
Pump Control Valves
Sectional Control Valves 7_ 11.:, )( -oj ....
System Control Valves aJp-'2.- II II ')G \i X'
Other Control Valves ()",.. r~l D<1.Ji K ~ )<
Kitchen Control Valves \
CONTROL VALVE MAINTENANCE TABLE
16 Water Flow Test at Sprinkler Riser
Water Su I Source:
Last Water Flow Test
This Water Flow Test
Test Pipe
Location
Size of
Test Pi e
Static
Pressure
Pum
Residual
(Flow)
Pressure
Ci
Tank
17
inspection:
~ ~
18
19
e improvements are recommen e
Date:
Signature:
(Rev. 2/8/06)