Loading...
HomeMy WebLinkAboutFire Sprinkler Report 10/17/2008 Fire Sprinkler System Inspection Report ~ G I L B E R T Gilbert Mechanical Contractors, Inc. 4451 West 76th Street Edina, MN 55435 (952) 835-3810 Inspected By: Dean Kaminski Inspection Date: 10/17/2008 Inspection #:2617 Property Name: North Lake Office Center #2 Property Address: 14180 Commerce Avenue NE Prior Lake, MN 55372 Bill To: Enqelsman Limited Partnershio Bill To Address: C/o Kraus-Anderson Realty Co. 4210 WOld Shakopee Road Contact & Phone #: Contact: Bloominqton, MN 55437 Was owner representative contacted prior to inspection? 0 Ves 0 No Representative's Name: Rep present during inspection? OVes 0No * Were all rooms available for inspection? 0Ves ONo Are as-built drawings available? OVes 0No Date Contacted: Rep's Name: Last inspection report available? 0Ves 0 No Zone map available? OVes 0 No * If no, see notes on following page [l] GENERAL SYSTEM INFORMATION 1 # of Systems 1 # of Wet # of Dry # of Preaction # of Other Location of Valve Assembly: [l] SPRINKLER SYSTEM INSPECTION System components have been inspected as follows: (circle all that apply) Gauges (Dry, Preaction, Deluge) OVes ONo 0N/A o Other (see notes) Waterflow Devices 0Ves ONo ON/A o Other (see notes) Valve Supervisory Devices 0Ves ONo ON/A o Other (see notes) Supervisory Signal Devices (Except Valve) OVes ONo 0N/A o Other (see notes) Supervisory Switches OVes ONo 0N/A o Other (see notes) Gauges (Wet System) 0Ves ONo ON/A o Other (see notes) Hydraulic Nameplate 0Ves ONo ON/A o Other (see notes) Buildings 0Ves ONo ON/A o Other (see notes) Hanger/Seismic Bracing OVes 0No ON/A o Other (see notes) Pipe & Fittings OVes 0No ON/A o Other (see notes) Sprinklers 0Ves ONo ON/A o Other (see notes) Spare Sprinklers 0Ves ONo ON/A o Other (see notes) Fire Department Connection 0Ves ONo ON/A o Other (see notes) Page 1 of 8 [Z] SPRINKLER SYSTEM INSPECTION Valves (All Types) 0Ves ONo ON/A o Other (see notes) Control Valves 0Ves ONo ON/A o Other (see notes) Alarm Valves OVes ONo 0N/A o Other (see notes) Check Valves OVes ONo 0N/A o Other (see notes) Pre-Action/Deluge OVes ONo 0N/A o Other (see notes) Dry Pipe Valves OVes ONo 0N/A o Other (see notes) Pressure Reducing & Relief OVes ONo 0N/A o Other (see notes) Backflow Prevention Assemblies OVes ONo 0N/A o Other (see notes) Sprinkler System Inspection Notes: [l] OBSTRUCTION INVESTIGATION NFPA 25 (2002) "An investigation of piping and branch line conditions shall be conducted every 5 years by opening a flushing connection at the end of one main and by removing a sprinkler toward the end of one branch line for the purpose of investigating for the presence of foreign organic and inorganic material." (Stated in NFPA 25,2002 Chapter 13.2.1) Has the owner been informed of the obstruction investigation requirement? Date last obstruction investigation was performed: Is an obstruction investigation required with this inspection? *If Ves, owner's authorization: Not authorized OVes 0No o Ves * 0 No (Owner/Rep name) OVes 0No Has an obstruction investigation been performed? Obstruction Investigation Notes: Page 2 of 8 D Fire Sprinkler System Inspection Report STANDPIPE & HOSE SYSTEM INSPECTION System components have been inspected as follows: (circle all that apply) Control Valves aVes aNa ON/A o Other (see notes) Pressure Regulating Devices OVes ONo ON/A o Other (see notes) Piping OVes ONo ON/A o Other (see notes) Hose Connections OVes ONo ON/A o Other (see notes) Cabinet OVes ONo ON/A o Other (see notes) Hose OVes ONo ON/A o Other (see notes) Hose Storage Device OVes ONo ON/A o Other (see notes) Hose Nozzle OVes ONo ON/A o Other (see notes) Standpipe and Hose System Inspection Notes: D PRIVATE FIRE SERVICE MAIN INSPECTION System Components have been Inspected as Follows: (circle all that apply) Hose Houses Hose Hydrants (Dry Barrel & Wall) Monitor Nozzles Hydrants (Wet Barrel) Mainline Strainers Piping (Exposed) Piping (Underground) OVes OVes OVes OVes OVes OVes OVes o Other (see notes) o Other (see notes) o Other (see notes) o Other (see notes) o Other (see notes) o Other (see notes) o Other (see notes) ONo ONo ONo ONo ONo ONo ONo ON/A ON/A ON/A ON/A ON/A ON/A ON/A Private Fire Service Main Inspection Notes: D FIRE PUMP INSPECTION & TESTING (see Fire Pump Inspection form on separate page) Page 3 of 8 D WATER STORAGE TANK INSPECTION Fire Sprinkler System Inspection Report System components have been inspected as follows: (circle all that apply) Condition of Water in Tank OVes ONo ON/A o Other (see notes) Water Temperature 0 Heating System OVes ONo ON/A o Other (see notes) Control Values OVes ONo ON/A o Other (see notes) Water Level OVes ONo ON/A o Other (see notes) Air Pressure PSI Tank Exterior OVes ONo ON/A o Other (see notes) Support Structure OVes ONo ON/A o Other (see notes) Catwalks and Ladders OVes ONo ON/A o Other (see notes) Surrounding Area OVes ONo ON/A o Other (see notes) Hoops & Grillage OVes ONo ON/A o Other (see notes) Painted/Coated Surfaces OVes ONo ON/A o Other (see notes) Expansion Joints OVes ONo ON/A o Other (see notes) Interior OVes ONo ON/A o Other (see notes) Check Valves OVes ONo ON/A o Other (see notes) Water Storage Tank Inspection Notes: Page 4 of 8 D WATER SPRAY FIXED SYSTEM INSPECTION Fire Sprinkler System Inspection Report System components have been inspected as follows: (circle all that apply) Backflow Preventer OVes ONo ON/A o Other (see notes) Check Valves OVes ONo ON/A o Other (see notes) Control Valves OVes ONo ON/A o Other (see notes) Deluge Valves OVes ONo ON/A o Other (see notes) Detection Systems OVes ONo ON/A o Other (see notes) Detector Check Valves OVes ONo ON/A o Other (see notes) Drainage OVes ONo ON/A o Other (see notes) Electric Motor OVes ONo ON/A o Other (see notes) Engine Drive OVes ONo ON/A o Other (see notes) Fire Pump OVes ONo ON/A o Other (see notes) Fittings OVes ONo ON/A o Other (see notes) Fittings (Rubber-Gasketed) OVes ONo ON/A o Other (see notes) Gravity Tanks OVes ONo ON/A o Other (see notes) Hangers OVes ONo ON/A o Other (see notes) Heat (Deluge Valve House OVes ONo ON/A o Other (see notes) Nozzles OVes ONo ON/A o Other (see notes) Pipe OVes ONo ON/A o Other (see notes) Pressure Tank OVes ONo ON/A o Other (see notes) Steam Driver OVes ONo ON/A o Other (see notes) Strainers OVes ONo ON/A o Other (see notes) Suction Tanks OVes ONo ON/A o Other (see notes) Supports OVes ONo ON/A o Other (see notes) Water Supply Piping OVes ONo ON/A o Other (see notes) UHSWSS-Detectors OVes ONo ON/A o Other (see notes) UHSWSS-Controllers OVes ONo ON/A o Other (see notes) UHSWSS-Valves OVes ONo ON/A o Other (see notes) Water Spray Fixed System Inspection Notes: Page 5 of 8 D FOAM WATER SPRINKLER SYSTEM INSPECTION Fire Sprinkler System Inspection Report System components have been inspected as follows: (circle all that apply) Discharge Device Location (Sprinkler) OVes ONo ON/A o Other (see notes) Discharge Device Location (Spray Nozzle) OVes ONo ON/A o Other (see notes) Discharge Device Position (Sprinkler) OVes ONo ON/A o Other (see notes) Discharge Device Position (Spray Nozzle) OVes ONo ON/A o Other (see notes) Foam Concentrate Strainer OVes ONo ON/A o Other (see notes) Drainage in System Area OVes ONo ON/A o Other (see notes) Proportioning System(s) - All OVes ONo ON/A o Other (see notes) Pipe Corrosion OVes ONo ON/A o Other (see notes) Pipe Damage OVes ONo ON/A o Other (see notes) Fitting Corrosion OVes ONo ON/A o Other (see notes) Fitting Damage OVes ONo ON/A o Other (see notes) Hangers/Supports OVes ONo ON/A o Other (see notes) Waterflow Devices OVes ONo ON/A o Other (see notes) Water Supply Tanks OVes ONo ON/A o Other (see notes) Fire Pump(s) OVes ONo ON/A o Other (see notes) Water Supply Piping OVes ONo ON/A o Other (see notes) Control Valves OVes ONo ON/A o Other (see notes) Deluge/Preaction Valve(s) OVes ONo ON/A o Other (see notes) Detection System OVes ONo ON/A o Other (see notes) Foam-Water Sprinkler System Inspection Notes: Sprinkler System Testing D QUARTERLY TESTS Waterflow Devices Water Motor Gong: # Present Did the Alarm Sound: 0 VES o NO (circle one) Notes: Page 6 of 8 [l] SEMI-ANNUAL TESTS Waterflow Devices Vane Type # ~ Pressure Switch Type # _ Do All Waterflow Devices Operate Properly: 0 YES o NO (circle one) Notes: Valves Supervisory Devices 2 Do All Supervisory Devices Operate Properly: 0 VES o NO (circle one) # Present Notes: Supervisory Signal Devices # Present Type: Notes: [l] ANNUAL TESTS Main Drain Test Static: flL PSI Antifreeze Solution Residual: 88 PSI Specific Gravity at 600 F: Freezing Point: Adjustment Needed: OF OVES 0 NO (circle one) Notes: Page 7 of 8 D 5 YEAR TESTS Gauges **Gauges shall be replaced every 5 years or tested every 5 years by comparison with calibrated gauuge. Gauges not accurate to within 3% to the full scale shall be recalibrated or reduced. # Present: # Recalibrated: # Tested: # Replaced: Notes: Sprinklers (Extra High Temperature) Date of Initial Installation: o Sprinklers Operate Properly: o Replace Sprinklers: Date Last Tested: See Sprinkler Test Report See Sprinkler Test Report D SPRINKLER TESTING (20 YEARS OR OLDER) Fast Response Sprinklers Date of Initial Installation: o Sprinklers Operate Properly: o Replace Sprinklers: Date of Last Test: See Sprinkler Test Report See Sprinkler Test Report Notes: D SPRINKLERS 50 YEARS OLD OR OLDER Date of Initial Installation: o Sprinklers Operate Properly: o Replace Sprinklers: Date of Last Test: See Sprinkler Test Report See Sprinkler Test Report Notes: [l] Control valves left opened and system placed back in service? 0Ves o No Page 8 of 8