HomeMy WebLinkAboutFire Sprinkler Report Fire Sprinkler System Inspection Report '~ G I L B E 1 T Gilbert Mechanical Contractors, Inc. , 4451 West 76th Street \-.." Edina, MN 55435 (952) 835-3810 Inspected By: Dean Kaminski I nspection Date: 1/6/08 Inspection #:2754 Property Name: Friendshio Church Property Address: 17741 Fairlawn Avenue Prior Lake, MN 55372 Contact & Phone #:Todd 952-447-0545 Bill To: Friendshio Church Bill To Address: 17741 Fairlawn Avenue Prior Lake, MN 55372 Contact: Was owner representative contacted prior to inspection? Representative's Name: Rep present during inspection? 0Ves ONo * Were all rooms available for inspection? 0 Ves 0 No Are as-built drawings available? OVes 0No OVes 0 No Date Contacted: Rep's Name: Last inspection report available? 0Ves 0 No Zone map available? OVes 0 No * If no, see notes on following page [l] GENERAL SYSTEM INFORMATION 1 # of Systems 1 # of Wet # of Dry # of Preaction # of Other Fire pump - no date of install Basement mechanical room Location of Valve Assembly: [l] SPRINKLER SYSTEM INSPECTION System components have been inspected as follows: (circle all that apply) Gauges (Dry, Preaction, Deluge) OVes ONo 0N/A o Other (see notes) Waterflow Devices 0Ves ONo ON/A o Other (see notes) Valve Supervisory Devices OVes ONo 0N/A o Other (see notes) Supervisory Signal Devices (Except Valve) OVes ONo 0N/A o Other (see notes) Supervisory Switches OVes ONo 0N/A o Other (see notes) Gauges (Wet System) 0Ves ONo ON/A o Other (see notes) Hydraulic Nameplate OVes 0No ON/A o Other (see notes) Buildings OVes 0No ON/A o Other (see notes) Hanger/Seismic Bracing OVes 0No ON/A o Other (see notes) Pipe & Fittings OVes 0No ON/A o Other (see notes) Sprinklers 0Ves ONo ON/A o Other (see notes) Spare Sprinklers 0Ves ONo ON/A o Other (see notes) Fire Department Connection 0Ves ONo ON/A o Other (see notes) Page 1 of 8 [l] SPRINKLER SYSTEM INSPECTION Valves (All Types) 0Ves ONo ON/A o Other (see notes) Control Valves 0Ves ONo ON/A o Other (see notes) Alarm Valves OVes ONo 0N/A o Other (see notes) Check Valves OVes ONo 0N/A o Other (see notes) Pre-Action/Deluge OVes ONo 0N/A o Other (see notes) Dry Pipe Valves OVes ONo 0N/A o Other (see notes) Pressure Reducing & Relief OVes ONo 0N/A o Other (see notes) Backflow Prevention Assemblies OVes ONo 0N/A o Other (see notes) Sprinkler System Inspection Notes: Basement system only - all sprinkler heads on system have been recalled. [l] OBSTRUCTION INVESTIGATION NFPA 25 (2002) "An investigation of piping and branch line conditions shall be conducted every 5 years by opening a flushing connection at the end of one main and by removing a sprinkler toward the end of one branch line for the purpose ofinvestigating for the presence offoreign organic and inorganic material." (Stated in NFP A 25, 2002 Chapter 13.2.1) Has the owner been informed of the obstruction investigation requirement? Date last obstruction investigation was performed: Is an obstruction investigation required with this inspection? "If Ves, owner's authorization: Not authorized 0ves ONo 0Ves" 0 No Has an obstruction investigation been performed? (Owner/Rep name) OVes 0No Obstruction Investigation Notes: Page 2 of 8 D Fire Sprinkler System Inspection Report STANDPIPE & HOSE SYSTEM INSPECTION System components have been inspected as follows: (circle all that apply) Control Valves OVes ONo ON/A o Other (see notes) Pressure Regulating Devices OVes ONo ON/A o Other (see notes) Piping OVes ONo ON/A o Other (see notes) Hose Connections OVes ONo ON/A o Other (see notes) Cabinet OVes ONo ON/A o Other (see notes) Hose OVes ONo ON/A o Other (see notes) Hose Storage Device OVes ONo ON/A o Other (see notes) Hose Nozzle OVes ONo ON/A o Other (see notes) Standpipe and Hose System Inspection Notes: D PRIVATE FIRE SERVICE MAIN INSPECTION System Components have been Inspected as Follows: (circle all that apply) Hose Houses Hose Hydrants (Dry Barrel & Wall) Monitor Nozzles Hydrants (Wet Barrel) Mainline Strainers Piping (Exposed) Piping (Underground) OVes OVes OVes OVes OVes OVes OVes o Other (see notes) o Other (see notes) o Other (see notes) o Other (see notes) o Other (see notes) o Other (see notes) o Other (see notes) ONo ONo ONo ONo ONo ONo ONo ON/A ON/A ON/A ON/A ON/A ON/A ON/A Private Fire Service Main Inspection Notes: [Z] FIRE PUMP INSPECTION & TESTING (see Fire Pump Inspection form on separate page) Page 3 of 8 [{] WATER STORAGE TANK INSPECTION Fire Sprinkler System Inspection Report System components have been inspected as follows: (circle all that apply) Condition of Water in Tank OVes 0No ON/A o Other (see notes) Water Temperature Heating System OVes ONo ON/A o Other (see notes) Control Values @Ves ONo ON/A o Other (see notes) Water Level 0Ves ONo ON/A o Other (see notes) Air Pressure NA PSI Tank Exterior OVes ONo 0N/A o Other (see notes) Support Structure OVes ONo 0N/A o Other (see notes) Catwalks and Ladders OVes ONo 0N/A o Other (see notes) Surrounding Area 0Ves ONo ON/A o Other (see notes) Hoops & Grillage OVes ONo 0N/A o Other (see notes) Painted/Coated Surfaces OVes ONo 0N/A o Other (see notes) Expansion Joints OVes ONo 0N/A o Other (see notes) Interior OVes ONo 0N/A o Other (see notes) Check Valves 0Ves ONo ON/A o Other (see notes) 'Water Storage Tank Inspection Notes: Outside underqround water tank Page 4 of 8 D WATER SPRAY FIXED SYSTEM INSPECTION Fire Sprinkler System Inspection Report System components have been inspected as follows: (circle all that apply) Backflaw Preventer OVes ONo ON/A o Other (see notes) Check Valves OVes ONa ON/A o Other (see notes) Control Valves OVes ONo ON/A o Other (see notes) Deluge Valves OVes ONa ON/A o Other (see notes) Detection Systems OVes ONo ON/A o Other (see notes) Detector Check Valves OVes ONa ON/A o Other (see notes) Drainage OVes ONa ON/A o Other (see notes) Electric Motor OVes ONa ON/A o Other (see notes) Engine Drive OVes ONa ON/A o Other (see notes) Fire Pump OVes ONo ON/A o Other (see notes) Fittings OVes ONo ON/A o Other (see notes) Fittings (Rubber-Gasketed) OVes ONa ON/A o Other (see notes) Gravity Tanks OVes ONa ON/A o Other (see notes) Hangers OVes ONo ON/A o Other (see notes) Heat (Deluge Valve House OVes ONa ON/A o Other (see notes) Nozzles OVes ONa ON/A o Other (see notes) Pipe OVes ONo ON/A o Other (see notes) Pressure Tank OVes ONo ON/A o Other (see notes) Steam Driver OVes ONa ON/A o Other (see notes) Strainers OVes ONa ON/A o Other (see notes) Suction Tanks OVes ONa ON/A o Other (see notes) Supports OVes ONa ON/A o Other (see notes) Water Supply Piping OVes ONa ON/A o Other (see notes) U HSWSS-Detectors OVes ONa ON/A o Other (see notes) UHSWSS-Contrallers OVes ONa ON/A o Other (see notes) UHSWSS-Valves OVes ONo ON/A o Other (see notes) Water Spray Fixed System Inspection Notes: Page 5 of 8 D FOAM WATER SPRINKLER SYSTEM INSPECTION Fire Sprinkler System Inspection Report System components have been inspected as follows: (circle all that apply) Discharge Device Location (Sprinkler) o Yes ONo ON/A o Other (see notes) Discharge Device Location (Spray Nozzle) o Yes ONo ON/A o Other (see notes) Discharge Device Position (Sprinkler) o Yes ONo o N/A o Other (see notes) Discharge Device Position (Spray Nozzle) o Yes ONo ON/A o Other (see notes) Foam Concentrate Strainer o Yes ONo ON/A o Other (see notes) Drainage in System Area o Yes ONo ON/A o Other (see notes) Proportioning System(s) - All o Yes ONo o N/A o Other (see notes) Pipe Corrosion o Yes ONo ON/A o Other (see notes) Pipe Damage o Yes ONo ON/A o Other (see notes) Fitting Corrosion o Yes ONo ON/A o Other (see notes) Fitting Damage o Yes ONo o N/A o Other (see notes) Hangers/Supports o Yes ONo ON/A o Other (see notes) Waterflow Devices o Yes ONo ON/A o Other (see notes) Water Supply Tanks o Yes ONo ON/A o Other (see notes) Fire Pump(s) o Yes ONo ON/A o Other (see notes) Water Supply Piping o Yes ONo ON/A o Other (see notes) Control Valves o Yes ONo ON/A o Other (see notes) Deluge/Preaction Valve(s) o Yes ONo o N/A o Other (see notes) Detection System o Yes ONo ON/A o Other (see notes) Foam-Water Sprinkler System Inspection Notes: Sprinkler System Testing D QUARTERLY TESTS Waterflow Devices Water Motor Gong: # Present Did the Alarm Sound: 0 YES o NO (circle one) Notes: Page 6 of 8 [ZJ SEMI-ANNUAL TESTS Waterflow Devices Vane Type # 1 Notes: Valves Supervisory Devices # Present Notes: All valves chained Supervisory Signal Devices # Present Notes: [ZJ Pressure Switch Type # _ Do All Waterflow Devices Operate Properly: 0 YES ONO Do All Supervisory Devices Operate Properly: 0 YES Type: _ ONO (circle one) (circle one) ANNUAL TESTS Main Drain Test Static: 70 Antifreeze Solution Specific Gravity at 600 F: Notes: PSI Residual: 50 pump kicks in PSI Freezing Point: Adjustment Needed: OF OYES 0 NO (circle one) Page 7 of 8 [l] 5 YEAR TESTS Gauges **Gauges shall be replaced every 5 years or tested every 5 years by comparison with calibrated gauuge. Gauges not accurate to within 3% to the full scale shall be recalibrated or reduced. # Present: 4 # Recalibrated: - # Tested: - # Replaced: 3 Notes: Sprinklers (Extra High Temperature) Date of Initial Installation: o Sprinklers Operate Properly: o Replace Sprinklers: Date Last Tested: See Sprinkler Test Report See Sprinkler Test Report D SPRINKLER TESTING (20 YEARS OR OLDER) Fast Response Sprinklers Date of Initial Installation: o Sprinklers Operate Properly: o Replace Sprinklers: Date of Last Test: See Sprinkler Test Report See Sprinkler Test Report Notes: D SPRINKLERS 50 YEARS OLD OR OLDER Date of Initial Installation: o Sprinklers Operate Properly: o Replace Sprinklers: Date of Last Test: See Sprinkler Test Report See Sprinkler Test Report Notes: [{] Control valves left opened and system placed back in service? o Yes o No Page 8 of 8 Fire Pump Test Data Tested By: Dean Kaminski Gilbert Mechanical Contractors, Inc. 4451 West 76th Street Edina, MN 55435 (952) 835-3810 Tested Date: 1/6/2009 Inspection #: 2754 Bill To: Friendship Church Bill To Address: 17741 Fairlawn Avenue Prior Lake, MN 55372 ~ejGILBERT Property Name: Friendship Church Property Address: 17741 Fairlawn Avenue Prior Lake, MN 55372 Contact & Phone #: Todd 952-447-0545 Contact & Phone# Was owner representative contacted prior to test? aVes 0 No Representative's Name: Date Contacted: Rep present during test? 0 Ves a No. · If no, see notes on following page Rep's Name: Todd FIRE PUMP INFORMATION Manufacturer Model Number Serial Number Pump Motor EnQine Controller Patterson Marathon Metron M30A-20-230B EL9310571-01 PUMP Manufacturer: Patterson Approved: FM Shaft: V Horizontal Vertical. - Vertical Rated GPM: 300 Rated Max PSI: 78 Rated PSI: 65 Rated RPM: 3525 Rated PSI: at 1.5 50 Suction From: Tank Tank Size: Tank Height underground VERTICAL PUMP (if applies) Vertical Distance Discharge Gauge to Water Level: Right Angle Gear Drive: Static 70 ft. Pumping 75 ft. Manufacturer Patterson Model 93FP0193TL3 o Smooth a Rough Type JOCKEY PUMP INFORMATION Manufacturer Model Number Serial Number Jockey Pump Panel Jockey Pump Metron Baldoor M15B-1-230 AK931 0571-02 Page 1 of 3 DRIVER Manufacturer: Marathon Electric Motor: Rated Volt: Operating Volt: Engine Type: 230/460 230 RPM: 3550 Horse Power: 60 Diesel Gas Gasoline Steam Turbine CONTROLLER Start PSI Stop PSI Manual ./ Manual Auto Auto Water Flow ./ Pressure Drop Control Valves Number Type Open Secured Signs Condition City Conection Control Valves 1 OS&Y 0YON (e)yON ,;)YON Chained onlv Test & Control Valves 1 OS&Y OY(e)N 0YON :)Y(e)N Chained only Pump Control Valves 0Y(;')N nynN jynN Sectional Control Valves 1 BFV 0:!:..ON Q.Y..0N :)Y€)N System Control Valves 1 BFV 0.Y...ON 0!:.ON .Jr.0N Chained only * Circle Yes or No PERFORMANCE Suction Discharge Boost Pressure Pressure PSI TDH GPM VOLTS AMPS 1 AMPS 2 AMPS 3 RPM Churn 38 74 36 3530 100% 150% Fire Pump Jockey Pump ON 50 ON 57 PSI PSI OFF - OFF 74 PSI PSI Notes: Churn test on Iv because of with the cold weather. the owner did not want ice oroblems. Puma controller has timer in it but it did not work. Page 2 of 3