HomeMy WebLinkAboutSprinkler Report 4/2/2009
Report of Inspection/Test
Annual
April 01, 2009
Property
Prior Lake City Hall
4646 Dakota Street
Prior Lake, MN
Owner/Agent
~ AUTOMATIC SPRINKLER CO
10351 Jamestown St. NE - Blaine, MN 55449
Tel (763) 784-8902 Fax (763) 784-5787
'~-t
~,~
\'
Conducted by: Jim Staricha
Inspection Ref: 11906
Contact:
Signatures
Inspector - Printed Inspector --signature Date I state that the information on this form is correct at the
Jim Staricha Il/~ 4/2/09 time and fllace of my inspection, and all equipment
tested at his time was left in operational condition upon
9:57 am comoletion of this insoection exceot as noted.
System Off 12:00 Monitoring Company Operator Alarm Panel/Code
USA central S-K 5820XL
System On 1:30 451-7183
Pull 4 nac wires.
Water Based System
Yes Gauges on wet pipe system in good condition and showing normal water supply pressure?
Yes Alarm devices free from physical damage?
Yes Hydraulic nameplate, if provided, securely attached to riser and legible?
Yes Valve supervisory switches indicate movement?
Fire Department Connection
Yes Visible and accessible?
Yes Couplings and swivels not damaged and rotate smoothly?
Yes Plugs or caps in place and undamaged?
Yes Gaskets in place and in good condition?
Yes Identification sign(s) in place?
Yes Check valve is not leaking?
Yes Automatic drain valve in place and operating properly?
NA Interior free of obstructions (if caps are not in place) ?
NA Valve clapper operational over its full range (if caps are not in place)?
Pipe
Yes
Yes
Yes
Yes
Yes
Yes
In good condition?
Free of mechanical damage and not leaking?
No external corrosion?
Properly aligned?
No external loads ?
Visible pipe hangers and seismic braces not damaged or loose?
Print Date: 4/23/2009
(All "NO" answers are to be fully explained.)
Copywrite 2002-5 Life Safety Inspector, OnSite Software, Inc.
Page 1 of 3
Report of Inspection/Test
Annual
April 01, 2009
Property: Prior Lake City Hall
Owner:
~ AUTOMATIC SPRINKLER CO
Inspection Ref: 11906
Sprinklers
Yes
Yes
Yes
Yes
No
Sprinkler wrench with spare sprinklers?
Proper number and type of spare sprinklers?
Free of corrosion?
Free of obstructions to spray patterns?
Free of foreign materials including paint?
Tape on heads up high on 1st floor by bump outs of glass.
Free of physical damage?
Are all sprinklers in service dated 1920 or later?
Fast Response sprinklers in service for less than 20 years? If "no" test sample now and every
10 years.
Standard sprinklers less than 50 years old? If no test sample now and every 10 years.
If sprinklers have been replaced, were they proper replacements?
Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems
replaced except for bulb-type which show no signs of grease buildup?
Yes
Yes
Yes
Yes
Yes
NA
Sprinklers
Extra high, very extra high and ultra high temperature sprinklers tested?
Valve Interior Inspection
NA Alarm valves and their associated strainers, filters and restriction orifices passed internal
inspection?
Check valves internally inspected and all parts operate properly,move freely and are in good
condition?
Not at 5 year yet.
Strainers, filters, restricted orifices and diaphragm chambers on dry pipe, preaction and deluge
valves passed internal inspection?
Gauges checked against calibrated gauge or replaced?
NA
NA
Yes
Flow Test
Connection Outlet Pressure (psi) Alarms Waterflow Results
System Flowed Size Actuate devices comparable
Static Resid Static pass test to prior test
Riser in mech rm LL Main drain 2 99 74 92 Yes Yes Yes
across from stairs.
Put hose on main drain.
ITVon 1st fI ne Inspector's test 1/2 Yes Yes Yes
corner next to exit.
Valve Inspection List
CIl 'tl 'tl
t/l CIl >.;f! CIl CIl
- CIl r:: t/l t/l ecu
Description o > Type .~ Secured CIl :: t/l r:: .~
'ltiii U) c. t/l t/l Cl .! .g
III CIl
> 0 w u en CIl U)..c
><
u W :l
<( ..J
Control Valve Chart/lnsp/Maint 1 Post Indicator 6" Supervised Yes Yes Yes Yes NA
Control Valve Chart/lnsp/Maint 2 Butterfly 4" Supervised Yes Yes Yes Yes NA
Print Date: 4/23/2009
(All "NO" answers are to be fully explained.)
Copywrite 2002-5 Life Safety Inspector, OnSite Software, Inc.
Page 2 of 3
Report of Inspection/Test
Annual
April 01, 2009
Property: Prior Lake City Hall
Owner:
~ AUTOMATIC SPRINKLER CO
Inspection Ref: 11906
Deficiency Summary
These items were deficient and do not meet the requirements of the applicable code at the time of the inspection.
Items marked Recommendation are not required by the applicable code but are opportunities to improve the Life
Safety of the property.
Sprinklers
No Free of foreign materials including paint?
Tape on heads up high on 1st floor by bump outs of glass.
NFPA-25-2002 5.2.1.1 Sprinklers shall be inspected from the floor level annually. Sprinklers shall be free of
corrosion, foreign materials, paint, and physical damage and shall be installed in the proper orientation (e.g.,
upright, pendant, or sidewall). Any sprinkler shall be replaced that is painted, corroded, damaged, loaded, or in
the improper orientation.
Valve Interior Inspection
NA Check valves internally inspected and all parts operate properly, move freely and are in
good condition?
Not at 5 year yet.
NFPA-25-2002 12.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate
properly, move freely, and are in good condition.
Print Date: 4/23/2009
(All "NO" answers are to be fully explained.)
Copywrite 2002-5 Life Safety Inspector, OnSite Software, Inc.
Page 3 of 3