HomeMy WebLinkAboutSprinkler Report 4/2/2009 Report of Inspection/Test Annual April 01, 2009 Property Prior Lake City Hall 4646 Dakota Street Prior Lake, MN Owner/Agent ~ AUTOMATIC SPRINKLER CO 10351 Jamestown St. NE - Blaine, MN 55449 Tel (763) 784-8902 Fax (763) 784-5787 '~-t ~,~ \' Conducted by: Jim Staricha Inspection Ref: 11906 Contact: Signatures Inspector - Printed Inspector --signature Date I state that the information on this form is correct at the Jim Staricha Il/~ 4/2/09 time and fllace of my inspection, and all equipment tested at his time was left in operational condition upon 9:57 am comoletion of this insoection exceot as noted. System Off 12:00 Monitoring Company Operator Alarm Panel/Code USA central S-K 5820XL System On 1:30 451-7183 Pull 4 nac wires. Water Based System Yes Gauges on wet pipe system in good condition and showing normal water supply pressure? Yes Alarm devices free from physical damage? Yes Hydraulic nameplate, if provided, securely attached to riser and legible? Yes Valve supervisory switches indicate movement? Fire Department Connection Yes Visible and accessible? Yes Couplings and swivels not damaged and rotate smoothly? Yes Plugs or caps in place and undamaged? Yes Gaskets in place and in good condition? Yes Identification sign(s) in place? Yes Check valve is not leaking? Yes Automatic drain valve in place and operating properly? NA Interior free of obstructions (if caps are not in place) ? NA Valve clapper operational over its full range (if caps are not in place)? Pipe Yes Yes Yes Yes Yes Yes In good condition? Free of mechanical damage and not leaking? No external corrosion? Properly aligned? No external loads ? Visible pipe hangers and seismic braces not damaged or loose? Print Date: 4/23/2009 (All "NO" answers are to be fully explained.) Copywrite 2002-5 Life Safety Inspector, OnSite Software, Inc. Page 1 of 3 Report of Inspection/Test Annual April 01, 2009 Property: Prior Lake City Hall Owner: ~ AUTOMATIC SPRINKLER CO Inspection Ref: 11906 Sprinklers Yes Yes Yes Yes No Sprinkler wrench with spare sprinklers? Proper number and type of spare sprinklers? Free of corrosion? Free of obstructions to spray patterns? Free of foreign materials including paint? Tape on heads up high on 1st floor by bump outs of glass. Free of physical damage? Are all sprinklers in service dated 1920 or later? Fast Response sprinklers in service for less than 20 years? If "no" test sample now and every 10 years. Standard sprinklers less than 50 years old? If no test sample now and every 10 years. If sprinklers have been replaced, were they proper replacements? Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced except for bulb-type which show no signs of grease buildup? Yes Yes Yes Yes Yes NA Sprinklers Extra high, very extra high and ultra high temperature sprinklers tested? Valve Interior Inspection NA Alarm valves and their associated strainers, filters and restriction orifices passed internal inspection? Check valves internally inspected and all parts operate properly,move freely and are in good condition? Not at 5 year yet. Strainers, filters, restricted orifices and diaphragm chambers on dry pipe, preaction and deluge valves passed internal inspection? Gauges checked against calibrated gauge or replaced? NA NA Yes Flow Test Connection Outlet Pressure (psi) Alarms Waterflow Results System Flowed Size Actuate devices comparable Static Resid Static pass test to prior test Riser in mech rm LL Main drain 2 99 74 92 Yes Yes Yes across from stairs. Put hose on main drain. ITVon 1st fI ne Inspector's test 1/2 Yes Yes Yes corner next to exit. Valve Inspection List CIl 'tl 'tl t/l CIl >.;f! CIl CIl - CIl r:: t/l t/l ecu Description o > Type .~ Secured CIl :: t/l r:: .~ 'ltiii U) c. t/l t/l Cl .! .g III CIl > 0 w u en CIl U)..c >< u W :l <( ..J Control Valve Chart/lnsp/Maint 1 Post Indicator 6" Supervised Yes Yes Yes Yes NA Control Valve Chart/lnsp/Maint 2 Butterfly 4" Supervised Yes Yes Yes Yes NA Print Date: 4/23/2009 (All "NO" answers are to be fully explained.) Copywrite 2002-5 Life Safety Inspector, OnSite Software, Inc. Page 2 of 3 Report of Inspection/Test Annual April 01, 2009 Property: Prior Lake City Hall Owner: ~ AUTOMATIC SPRINKLER CO Inspection Ref: 11906 Deficiency Summary These items were deficient and do not meet the requirements of the applicable code at the time of the inspection. Items marked Recommendation are not required by the applicable code but are opportunities to improve the Life Safety of the property. Sprinklers No Free of foreign materials including paint? Tape on heads up high on 1st floor by bump outs of glass. NFPA-25-2002 5.2.1.1 Sprinklers shall be inspected from the floor level annually. Sprinklers shall be free of corrosion, foreign materials, paint, and physical damage and shall be installed in the proper orientation (e.g., upright, pendant, or sidewall). Any sprinkler shall be replaced that is painted, corroded, damaged, loaded, or in the improper orientation. Valve Interior Inspection NA Check valves internally inspected and all parts operate properly, move freely and are in good condition? Not at 5 year yet. NFPA-25-2002 12.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate properly, move freely, and are in good condition. Print Date: 4/23/2009 (All "NO" answers are to be fully explained.) Copywrite 2002-5 Life Safety Inspector, OnSite Software, Inc. Page 3 of 3