HomeMy WebLinkAboutSprinkler Report 4/2/2009
Report of Inspection/Test
Annual
April 01, 2009
Property
Prior Lake Police Station
4649 Dakota Street
Prior Lake, MN
~ AUTOMATIC SPRINKLER CO
10351 Jamestown St. NE - Blaine, MN 55449
Tel (763) 784-8902 Fax (763) 784-5787
Owner/Agent
Conducted by: Jim Staricha
Inspection Ref: 11905
Contact:
Signatures
Inspector - Printed Inspector - :SIgnature I Date I state that the information on this form is correct at the
Jim Staricha ~~ 4/2/09 time and glace of my insRection, and all equipment
tested at his time was left in operational condition upon
10:04 am comoletion of this insoection exceot as noted.
System Off 1:30 Monitoring Company Operator Alarm Panel/Code
USA central S-K 5820 XL
System On 3:00 451-7152
Pull 4 nac wires.
Water Based System
Yes Gauges on wet pipe system in good condition and showing normal water supply pressure?
Yes Alarm devices free from physical damage?
Yes Hydraulic nameplate, if provided, securely attached to riser and legible?
Yes Valve supervisory switches indicate movement?
Had to reset tamper on PIV,hit by something.
Fire Department Connection
Yes Visible and accessible?
Yes Couplings and swivels not damaged and rotate smoothly?
Yes Plugs or caps in place and undamaged?
Yes Gaskets in place and in good condition?
Yes Identification sign(s) in place?
Yes Check valve is not leaking?
Yes Automatic drain valve in place and operating properly?
NA Interior free of obstructions (if caps are not in place) ?
NA Valve clapper operational over its full range (if caps are not in place) ?
Pipe
Yes
Yes
Yes
Yes
Yes
Yes
In good condition?
Free of mechanical damage and not leaking?
No external corrosion?
Properly aligned?
No external loads ?
Visible pipe hangers and seismic braces not damaged or loose?
Print Date: 4/23/2009
(All "NO" answers are to be fully explained.)
Copywrite 2002-5 Life Safety Inspector, OnSite Software, Inc.
Page 1 of 3
Report of Inspection/Test
Annual
April 01, 2009
Property: Prior Lake Police Station
Owner:
Extra high, very extra high and ultra high temperature sprinklers tested?
Valve Interior Inspection
NA Alarm valves and their associated strainers, filters and restriction orifices passed internal
inspection?
Check valves internally inspected and all parts operate properly,move freely and are in good
condition?
Not yet time to do this.
Strainers, filters, restricted orifices and diaphragm chambers on dry pipe, preaction and deluge
valves passed internal inspection?
Gauges checked against calibrated gauge or replaced?
Sprinklers
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
NA
Sprinklers
NA
NA
Yes
Flow Test
~ AUTOMATIC SPRINKLER CO.
Inspection Ref: 11905
Sprinkler wrench with spare sprinklers?
Proper number and type of spare sprinklers?
Free of corrosion?
Free of obstructions to spray patterns?
Free of foreign materials including paint?
Free of physical damage?
Are all sprinklers in service dated 1920 or later?
Fast Response sprinklers in service for less than 20 years? If "no" test sample now and every
10 years.
Standard sprinklers less than 50 years old? If no test sample now and every 10 years.
If sprinklers have been replaced, were they proper replacements?
Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems
replaced except for bulb-type which show no signs of grease buildup?
Connection Outlet Pressure (psi) Alarms Waterflow Results
System Size Actuate devices comparable
Flowed Static Resid Static pass test to prior test
Riser in mech rm of Main drain 2 97 77 87 Yes Yes NA
QaraQe.
Put hose on main drain.
ITV sw corner of Inspector's test 1/2 Yes Yes NA
garaQe.
Valve Inspection List
CIl "C "C
III >o,;e CIl CIl
- CIl CIl c: III III E1ii
Description o > Type N Secured CIl :: III c: 'u
en III III $ .g
'ltiV Q. III CIl .21 ...
> 0 w u U) CIl U),Q
><
u W :J
c:( ..J
Control Valve Chart/lnsp/Maint 1 Post Indicator 6" Supervised Yes Yes Yes Yes NA
Control Valve Chart/lnsp/Maint 1 Butterfly 4" Supervised Yes Yes Yes Yes NA
Print Date: 4/23/2009
(All "NO" answers are to be fully explained.)
Copywrite 2002-5 Life Safety Inspector, OnSite Software, Inc.
Page 2 of 3
Report of Inspection/Test ~ AUTOMATIC SPRINKLER CO. 'ff).
:!l 'l~
I "
Annual . \
April 01, 2009
Property: Prior Lake Police Station
Owner: Inspection Ref: 11905
Deficiency Summary
These items were deficient and do not meet the requirements of the applicable code at the time of the inspection.
Items marked Recommendation are not required by the applicable code but are opportunities to improve the Life
Safety of the property.
Water Based System
Yes Valve supervisory switches indicate movement?
Had to reset tamper on PIV,hit by something.
NFPA-25-2002 12.3.3.5 Valve supervisory switches shall be tested semiannually. A distinctive signal shall
indicate movement from the valve's normal position during either the first two revolutions of a hand wheel or
when the stem of the valve has moved one fifth of the distance from its normal position. The signal shall not be
restored at any valve position except the normal position.
Valve Interior Inspection
NA Check valves internally inspected and all parts operate properly, move freely and are in
good condition?
Not yet time to do this.
NFPA-25-2002 12.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate
properly, move freely, and are in good condition.
Print Date: 4/23/2009
(All "NO" answers are to be fully explained.)
Copywrite 2002-5 Life Safety Inspector, OnSite Software, Inc.