HomeMy WebLinkAboutReport of Inspection 3/12/2010
Report of InspectionlTest
Annual Wet
March 11,2010
Property Owner/Agent
Prior Lake Maintenance Bldg.
~AUTCWAT~SPRHtJS~ t
10351 JamesloVtTl 81. NE . Blaine, MN 55449
Tel (763) 784-8002 Fax (763) 784-5797
Conducted by: Joel Hirsch
Inapection Ref: 11899
Owner. Printed
City of Prior Lake
I
Owner. Signature
3111110
12:00 am
td.
3111110
12:00 am
~
3111/10
12:00 am
I state that the infori'n8tlon on INs form Ia'coritct at the
time and DIace of my Inllrl8c11on. and alt equ.ent
tested at this time was teft in operallonal COniIIlIon upon
comoletlon of this lnaoecllon ".....Ias noted.
I acknow~ this reP<!rt has been revIelVed with me.
Exc!!pt as noted. the... have been no changes to the
orlairial aDOroved system.
Owner. Cefic . Printed
City of Prior Lake
Owner- ~fic - "nature
This acknowled~s notlllcltlonof d~1n lhe
system. These CleflClencles could endanaer clllty
~ants. Thisacknowledg,' ,lis nor an
authOrIzation to reDair these deficiencies.
System Off
System On
Monitoring Company
Metro Alarm
(952)346-9452
Operator
USA Central
Alarm PaneflCode
SK 5207
451.1318
Gauges on wet pipe system in good condition and showing normal water supply pressure?
Alarm devices free from physical damage?
Hydraulic nameplate. if provided. securely attached to riser and legible?
Valve su iso switches indicate movement?
Yes
Yes
Yes
Yes
Yes
Yes
Yes
NA
NA
Visible and accessible?
Couplings and swivels' not damaged and rotate smoothly?
Plugs or caps in place and undamaged?
Gaskets in place and in good condition?
Identification sign(s) in place?
Check valve is not leaking?
Automatic drain valve in place and operating properly?
Interior free of obstruct.ions (if caps are not in place) ?
Valve cia r 0 erati at over its full ran if . are not in
NA
Alarm valves and their associated strainers, filters and restriction orifices passed internal
inspection?
Check valves internally inspected and all parts operate properly. move freely and are in good
condition?
Strainers, filters, restricted orifices and diaphragm chambers on dry pipe, preaction and deluge
valves passed internal inspection?
Gauges checked against calibrated gauge or replaced?
No
NA
Yes
Print
3/1212010
(All "NO" answers a18 to be fully explained.)
CopyrIght 2002-2009 life Safety Intpedor. OnSlte Software. Inc.
P...1of3
Report of Inspectiol1/Test
Annual Wet
March 11, 2010
Property: Prior Lake Maintenance Bldg.
Owner:
~AIJTQMA11CSPlINKLEftCo. "
Inspection Ref: 11899
I n good condition ?
Free of mechanical damage and not leaking?
No external corrosion?
Properly aligned ?
No extemalloads ?
Visible' h ers and seismic braces not
Yes Sprinkler wrench with spare sprinklers?
Yes Proper number and type of spare sprinklers?
Yes Free of corrosiOn?
Yes Free of obstructiOns to spray patterns?
Yes Free of foreign materials including paint?
Yes Free of phySical damate?
Yes Are all spriAklers in se""ice dated 1920 or 1ater?
Yes Fast Response Sprinklers in service for less than 20 years? If "no. test sample now and every
10 years.
Yes Standard sprinklers Ie8s than 50 years okI? If no test sample now and every 10 years.
No If sprinklers have been replaced, were they proper replacements?
1 recalled sprinkler . foe Lube Stbnige.
NA Sprinklers and spray noZZles protecting commercial cooking equipment and ventilating systems
re laced ex for bulb- which show no sins ofse build 1
Connection Outlet P.....ur. (PSI) Alanna W......ow .Reeults
System Flowed Size Actuate devices comparable
Static Reskl Static pass test toPl'tor test
Main Main drain 2 101 72 80 NA NA Yes
ITV on riser & se Inspector's test 1/2 Yes Yes Yes
comer of Qara e
Description
.. .~ ~! I jJ
'S~ Type Secured c I
.:: en & sl 0 enl
0 rn
c .3
1 Os&Y 4" Supervised Yes Yes Yes Yes Yes
1 Post Indicator 6" Pad Locked Yes Yes Yes Yes NA
Control Valve ChartllnsplMaint
Control Valve Chartllnsp/Maint
Print
3/1212010
(All "NO" answers are to be fully explained.)
Copyright 2002.2009 life Saftty Inspector. OnSite Sotlwa.... Inc.
p... 2 of 3
Report of InspectionlTest
Annual Wet
March 11,2010
ProPftrty: Prior Lake Maintenance Bldg.
Owner:
~~nCSMNKL!RCCl t
Inspection Ref: 11899
I
Deftciency Summary
These items were deficient and do not meet the requirements of the applicable code at the time of tie inspection.
Items marked Recommendation are not required by the applicable code but are opportunities to improve the Life
Safety of the property.
No Check valves Internally Inspected and aU pa.... operate properly ,move freely and are in
good condition?
NFPA-25-2002 12.4.2.1 Valves shall be inspected internally eve/)' 5 years to verify that all components operate
properly, move freely, and are in good condition.
No If sprinklers have been replaced, were they proper replacements?
1 recalled sprinkler @ 108 Lube Stofllge.
NFPA-25.2002 5.4.1.1 Replacement Sprinklers shall have the proper characteristics for the application intended.
Print
3/1212010
(All "NO" answers ate to be fully explained.)
Copyright 2Q02.2009l.1f1t Stftty I '" ,..or, 0nSite Software, Inc.
Page 3 of 3