Site ID: 022 -0129 HVAC Load Analysis for Mcdonald's 5020 160TH STREET S.E. PRIOR LAKE, MINNESOTA Elitt 41 COMMERCIAL HVAC LOADS V r ,/. � �� 25 . C' I L Prepared Sy: Lucas W. Sook Dunham 50th S. 6th Street, Suite 1100 Minneapolis, Mn. 55402 -1540 612 -465 -7550 Tuesday, May 08, 2012 • Chvac - Fol1 Commercial HVAG Loads Calculation Program Elite Software Development, Inc. Dunham Associates;' Inc. Site ID: 04 -0129 Minneapolis, MN 55402. e 2 Building Summary Loads 1 Building peaks in July at 5pm. }} q - 1' Gig L w s V i a c ** h ' a - .'w �, ',11, -X. 4-' ''le � -, a � $ +gyp i , ,.. «h.�: ®.��_�, ��_���.�:._�'�.", 4 . 3 �� �. ��,�.e ..��.�. � n.�� �, '�. E�r's'9 �` � rc ti�. ��.0 .�, ,. ��.. IF Roof 3,712 11,637 2.53 0 4,188 4,188 1.08 Wall 3,210 31,193 6.77 0 6,297 6,297 1.63 Glass 535 35,199 7.64 0 34,915 34,915 9.03 Floor Slab 281 19,107 4.15 0 0 0 0.00 Skin Loads 97,136 21.09 0 45,399 45,399 11.74 Lighting 7,424 0 0.00 0 27,865 27,865 7.20 Equipment 22,500 0 0.00 10,890 84,450 95,340 24.65 People 103 0 0.00 25,326 28,153 53,479 13.83 Partition 0 0 0.00 0 0 0 0.00 Cool. Pret. 0 0 0.00 0 0 0 0.00 Heat. F "ret. 0 0 0.00 0 0 0 0.00 Cool. Vent. 3,650 0 0.00 98,449 66,223 164,672 42.58 Heat. Vent. 3,650 363,342 78.91 0 0 0 0.00 Cool. [ail. 0 0 0.00 0 0 0 0.00 Heat. Infil. 0 0 0.00 0 0 0 0.00 Draw -Thru Fan 0 0 0.00 0 0 0 0.00 Blow -Thru Fan 0 0 0.00 0 0 0 0.00 Reserve Cap. 0 0 0.00 0 0 0 0.00 Reheat Cap. 0 0 0.00 0 0 0 0.00 Supply Duct 0 0 0.00 0 0 0 0.00 Return Duct 0 0 0.00 0 0 0 0.00 Misc. Supply 0 0 0.00 0 0 0 0.00 Misc. Return 0 0 0.00 0 0 0 0.00 Building Totals 460,477 100.00 134,665 252,091 386,756 100.00 L. ,, .3zaE . .r t.4 " a. M_ ; ,- ,N l ` ,4#. ti} �: 4 , , X.n A% � ' A',"'20. I N. ? mss.. • Ventilation 363,342 78.91 98,449 66,223 164,672 42.58 Infiltration 0 0.00 0 0 0 0.00 Pretreated Air 0 0.00 0 0 0 0.00 Zone Loads 97,136 21.09 36,216 185,868 222,084 57.42 Plenum Loads 0 0.00 0 0 0 0.00 Fan & Duct Loads 0 0.00 0 0 0 0.00 Building Totals 460,477 100.00 134,665 252,091 386,756 100.00 x � - �: ,e.r� z. 8"'�, y_ K�•� rr,� s � as ��.��,� �Ei aY.>� Zar ,Z _ ,_ _ ra W4kiagintil _.. Total Building Supply Air (based on a 18° TD): 9,781 CFM Total Building Vent. Air (37.32% of Supply): 3,650 CFM Total Conditioned Air Space: 3,712 Sq.ft Supply Air Per Unit Area: 2.6351 CFM / Sq.ft Area Per Cooling Capacity: 115.2 Sq.ft/Ton Cooling Capacity Per Area: 0.0087 Tons / Sq.ft Heating Capacity Per Area: 124.05 Btuh /Sq.ft Total Heating Required With Outside Air: 460,477 Btuh Total Cooling Required With Outside Air: 32.23 Tons P:\ ...\0412817 - 018 -00 -PRIOR LAKE.CHV Tuesday, May 08, 2012, 03:17 PM C#waC Co rn s rclal HVAC t oa ds C Etite Software Devolopr 8nt Ir •Dunham ASsetiti es, :ifc Site ID' :022 -012'9 Nlinfl apois; : MN 55402 P89 s 3 Air Handler #1 - RTU -1 Kitchen - Summary Loads .i d r , a m 9 w � 3< f ¢ Ytt ` .. j 0 0 "' !', 1 1 K , , a k ». 33 $ o d`*g" , Y � i: t �, � icw ° T"i?1,. : z ,. € `0, / _-.a � , a "� y a "' a � ; r s i i a s& "� • 4 4 T' i �4 ', �3a " a w i and w„ . $ ' .hwkrt t :.�'. o� ....: ..!1. .. " , i� *, , 1z '•r 4.. ` 10 Kitchen 725 10,138 92,291 16,286 Direct Direct 1pm July 9 1,500 4,804 0 1,500 1,500 6,525 2.07 6.63 0 1,500 1,500 Zone Peak Totals: 725 10,138 92,291 16,286 Total Zones: 1 9 1,500 4,804 0 1,500 1,500 Unique Zones: 1 6,525 2.07 6.63 0 1,500 1,500 P:\ ...\ 0412817 -018 -00 -PRIOR LAKE.CHV Tuesday, May 08, 2012, 03:17 PM Chvac - FUII Comm HVAC.Loads Galculatlon program Elite Software Qevotopmsiat, tnc.• Dunham 'Associates Inc. Site 1P. 022.17129: Minnea MN 65402 Page 4' Air Handler #1 - RTU -1 Kitchen - Total Load Summary Air Handler Description: RTU -1 Kitchen Constant Volume- Proportion Sensible Heat Ratio: 0.85 -- This system occurs 1 time(s) in the building. -- Air System Peak Time: 1 pm in July. Outdoor Conditions: CIg: 91° DB, 75° WB, 108.40 grains, Htg: -20° DB Indoor Conditions: CIg: 75 DB, 50% RH, Htg: 75° DB Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Zone Space sensible loss: 10,138 Btuh Infiltration sensible loss: 0 Btuh 0 CFM Outside Air sensible loss: 149,319 Btuh 1,500 CFM Supply Duct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: 159,457 Btuh Heating Supply Air: 10,138 / (.970 X 1.08 X 6) = 1,500 CFM Winter Vent Outside Air (100.0% of supply) = 1,500 CFM Zone space sensible gain: 92,291 Btuh Infiltration sensible gain: 0 Btuh Draw -thru fan sensible gain: 0 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: 92,291 Btuh Cooling Supply Air: 92,291 / (.970 X 1.1 X 18) = 4,804 CFM Summer Vent Outside Air (31.2% of supply) = 1,500 CFM Return duct sensible gain: 0 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 25,614 Btuh 1,500 CFM Blow -thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: 25,614 Btuh Total sensible gain on air handling system: 117,905 Btuh Zone space latent gain: 16,286 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 42,071 Btuh Total latent gain on air handling system: 58,356 Btuh Total system sensible and latent gain: 176,262 Btuh Total Air Handler Supply Air (based on a 18° TD): 4,804 CFM Total Air Handier Vent. Air (31.22% of Supply): 1,500 CFM Total Conditioned Air Space: 725 Sq.ft Supply Air Per Unit Area: 6.6265 CFM /Sq.ft Area Per Cooling Capacity: 49.4 Sq.ft/Ton Cooling Capacity Per Area: 0.0203 Tons /Sq.ft Heating Capacity Per Area: 219.94 Btuh / Sq.ft Total Heating Required With Outside Air: 159,457 Btuh Total Cooling Required With Outside Air: 14.69 Tons P:\ ... \0412817 - 018- 00;PRIOR LAKE.CHV `'a'.klr; Tuesday. May 08, 2012,"03517'PM Chva O Icutation Program Etito s. #yelopoleo Ine, DUnham A.0 tes, Inc Site ID 0220129 Minnea MN 65402 'Page 5' Air Handler #2 - RTU -2 Support - Summary Loads 1 S 1- tl E .aN •A : '1 �, = 0 , �a zt yr " s e a J.' � , F • , i , '7,1• : .,=,,,5 \ „.4.k,, L r,t,iv,„ ,i. ,le.o. ,',,,tz4-:. j 1 ? , ! riliw :. Ili '',.. -'1,,: e, ',i ki. '#6.zil iv. :;',.. ' z s lixel ;,1, ,. i ' 6 Support 490 8,579 6,022 539 Direct Direct 5pm August 2 409 310 0 246 246 5,145 0.84 0.63 0 174 182 7 Manager's 55 1,926 2,512 0 Direct Direct 6pm July 0 92 129 0 24 24 495 1.67 2.35 0 39 76 8 Crew 100 4,145 1,858 341 Direct Direct 6pm June 1 198 96 0 43 43 900 1.98 0.96 0 84 56 9 Order 320 7,508 4,510 600 Direct Direct 3pm June 1 358 232 0 138 138 2,880 1.12 0.73 0 152 136 Zone Peak Totals: 965 22,158 14,903 1,480 Total Zones: 4 4 1,057 767 0 450 450 Unique Zones: 4 9,420 1.10 0.79 0 450 450 i. P:\ ... \0412817- 018 -00 -PRIOR LAKE.CHV"'• " <' , : ' .: Tuesday, May 08, 2012, 03:17 PM Chvac p Full Commercial HVAC Loads Calculation Program ' 3 Ella Software I avelopinent, Inc.' Dunham Associates, Inc, ` F Site IO 022- 0129 Minneaolis, MN 55402 Page 61 Air Handler #2 - RTU -2 Support - Total Load Summary Air Handler Description: RTU -2 Support Constant Volume - Proportion Sensible Heat Ratio: 0.91 -- This system occurs 1 time(s) in the building. - -- Air System Peak Time: 5pm in July. Outdoor Conditions: Clg: 92° DB, 75° WB, 108.02 grains, Htg: -20° DB Indoor Conditions: Clg: 75° DB, 50% RH, Htg: 75° DB Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in June at 6pm is different from the total system peak time, hence the air system CFM was computed using a zone sensible load of 14,736. Summer: Ventilation controls outside air, - -- Winter: Ventilation controls outside air. Zone Space sensible loss: 22,158 Btuh Infiltration sensible loss: 0 Btuh 0 CFM Outside Air sensible loss: 44,796 Btuh 450 CFM Supply [)uct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible Toss: 0 Btuh Total System sensible toss: 66,953 Btuh Heating Supply Air: 22,1581(.970 X 1.08 X 20) = 1,057 CFM Winter Vent Outside Air (42.6% of supply) = 450 CFM Zone space sensible gain: 14,651 Btuh Infiltration sensible gain: 0 Btuh Draw -thru fan sensible gain: 0 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: 14,651 Btuh Cooling Supply Air: 14,736 / (.970 X 1.1 X 18) = 767 CFM Summer Vent Outside Air (58.7% of supply) = 450 CFM Return duct sensible gain: 0 Btuh Retum plenum sensible gain: 0 Btuh Outside air sensible gain: 8,164 Btuh 450 CFM Blow -thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: 8,164 Btuh Total sensible gain on air handling system: 22,816 Btuh Zone space latent gain: 1,480 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 12,138 Btuh Total latent gain on air handling system: 13,617 Btuh Total system sensible and latent gain: 36,433 Btuh a Total Air Handler Supply Air (based on a 18° TD): 767 CFM Total Air Handler Vent. Air (58.66% of Supply): 450 CFM Total Conditioned Air Space: 965 Sq.ft Supply Air Per Unit Area: 0.7949 CFM /Sq.ft Area Per Cooling Capacity: 317.8 Sq.ft/Ton Cooling Capacity Per Area: 0.0031 Tons / Sq.ft Heating Capacity Per Area: 69.38 Btuh /Sq.ft Total Heating Required With Outside Air: 66,953 Btuh Total Cooling Required With Outside Air: 3.04 Tons P :\ :.. \0412817- .018 -00- _PRIOR LAKE.CHV Tuesday,' May 08, 2012, 03:17 PM GhVAC' p comm rcial HVA toads Calculatian'Program Elite Software i�eyelopnne4i; lne- Ounharn Associates, Inc. $tte 1O O22-Q1 M�hriea, MN 55402 Page 7 Air Handler #3 - RTU -3 Dining & Toilets - Summary Loads d r i 6 a g � 9 '] pi ka a,,, r ° bg �a ®�., `::R ki ° 0y 4 � 4 k a� F ''''.'. if t,,,‘' ''''' "' W .,' aRat#,I P SI' 0.r.,' 11* Y , t : = '::". 4. g e iiSki: ,- A 4 W:ii:1° , 4*If . y.. q" :k7I*,144 . 4Wilit 1 1 1 41441 61 7 ! 1 Dining 1,675 47,485 68,205 19,800 Direct Direct 6pm August 90 2,266 3,456 0 1,450 1,450 16,750 1.35 2.06 0 1,245 1,396 2 Women's Toilet 138 3,925 1,831 0 Direct Direct 6pm August 0 187 93 0 96 96 1,104 1.36 0.67 0 103 37 3 Men's Toilet 122 382 1,076 0 Direct Direct 3pm July 0 18 55 0 84 84 976 0.15 0.45 0 10 22 4 Vestibule 1 42 7,554 5,915 0 Direct Direct 6pm June 0 360 300 0 34 34 391 8.58 7.14 0 198 121 5 Vestibule 2 45 5,494 6,060 0 Direct Direct 3pm September 0 262 307 0 36 36 419 5.83 6.82 0 144 124 Zone Peak Totals: 2,022 64,840 83,087 19,800 Total Zones: 5 90 3,094 4,210 0 1,700 1,700 Unique Zones: 5 19,639 1.53 2.08 0 1,700 1,700 P:1 ...10412817 -018 004?RIOR LAKE.CHV '` 110-1•= (iic'. Tuesday, May 08, 201Z:03:17. PM } ' Chya�c - CUP Chi . rrrercial HVAC Loads Calculation Program lltu So Daveloprnan Inc Dunham Asscrc,ates,:Inc Sate ID,.02 -0t29x • Mtnnea 55902 Pape 8 Air Handler #3 - RTU -3 Dining & Toilets - Total Load Summary Air Handler Description: RTU -3 Dining & Toilets Constant Volume - Proportion Sensible Heat Ratio: 0.80 -- This system occurs 1 time(s) in the building. --- Air System Peak Time: 5pm in July. Outdoor Conditions: CIg: 92° DB, 75° WB, 108.02 grains, Htg: -20° DB Indoor Conditions: CIg: 75° DB, 50% RH, Htg: 75° DB Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in August at 6pm is different from the total system peak time, hence the air system CFM was computed using a zone sensible Toad of 80,878. Summer: Ventilation controls outside air, - -- Winter: Ventilation controls outside air. Zone Space sensible loss: 64,840 Btuh Infiltration sensible loss: 0 Btuh 0 CFM Outside Air sensible loss: 169,228 Btuh 1,700 CFM Supply Duct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: 234,068 Btuh Heating Supply Air: 64,840 / (.970 X 1.08 X 20) = 3,094 CFM Winter Vent Outside Air (54.9% of supply) = 1,700 CFM Zone space sensible gain: 79,411 Btuh Infiltration sensible gain: 0 Btuh Draw -thru fan sensible gain: 0 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: 79,411 Btuh Cooling Supply Air: 80,878 / (.970 X 1.1 X 18) = 4,210 CFM Summer Vent Outside Air (40.4% of supply) = 1,700 CFM Return duct sensible gain: 0 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 30,844 Btuh 1,700 CFM Slow -thru fan sensible gain: 0 Btuh Total sensible gain on retum side of coil: 30,844 Btuh Total sensible gain on air handling system: 110,255 Btuh Zone space latent gain: 19,800 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 45,853 Btuh Total latent gain on air handling system: 65,653 Btuh Total system sensible and latent gain: 175,908 Btuh � � a E* *N�� t��a 4^'? x� � ��e a ?v su °�' e" � ^" i �. x � +: - Tz i :*4.,;," , { >aT i.,.� r, m .ivttn.:. .' 3. ' h , ,'E t?"' "«.<t i :..CFM Total Air Handler Supply Air (based on a 18° TD): 4,210 CFM Total Air Handler Vent. Air (40.38% of Supply): 1,700 CFM Total Conditioned Air Space: 2,022 Sq.ft Supply Air Per Unit Area: 2.0821 CFM /Sq.ft Area Per Cooling Capacity: 137.9 Sq.ftfTon Cooling Capacity Per Area: 0.0072 Tons/Sq.ft Heating Capacity Per Area: 115.76 Btuh /Sq.ft Total Heating Required With Outside Air: 234,068 Btuh Total Cooling Required With Outside Air: 14.66 Tons P:1...10412817- 018 -00 -PRIOR LAKE:CI4V i a , s Tuesday, May 08, 2012, 03:17 PM ' -? ' Special Structural Testing and Inspection Program Summary Schedule Project Nome McDonald's Restaurant _ Project No, Location an 160th Sfrsat._SF ., . Prior t olie ldN Permit No. chnical 2 Te Type of Specific Report Assigned Section Article Description (3) Inspector (4) F�r X_..5�) _ Firm (6) 1704.4 Concrete Bonn (ruction TA Table 1704.4 of _ ffi e 444/ 2006 IBc e.✓yw/vzeat. PT, 1704,6 s .I 1 Ta i ,1 , 2006 IBC „„1204.7 .. — .Solis.. TA Table 1704.7 of — /r _ 2006 18C 4204.3 .. . „StasL ansirmation TA Table 1.704.3 of // 7005.lB_ Note: This schedule shall be filled out and included in a Special Structural Testing and Inspection Program. (1) Permit No. to be provided by the Building Official (2) Referenced to the specific technical scope section in the program. (3) Use descriptions per IBC Chapter 17 (4) Special Inspector -- Technical (SIT); Special Inspector - Structural (Si5) (5) Weekly, monthly, per test /inspection, per floor, etc. (6) Nome of Firm contracted to perform services. / ACKNOWLEDGEMENTS (each appropriate representative sholll sign below) J } / ,�,,,,, _... „ Firm: + G 0 ir/0,1 Date: fir' 2 7 / 2___ Owner; Contractor ", Firm: Cc� �- - � Dat e: ' 7 ( r - 4-.- Arah ; f i 1 '' _ Firm: •Reprise Design, Inc, Date: 05-09 -12 M ir SER: r _ T', 1 Firm: VOIGT AND ASSOCIATES, INC. Dale: 5 - - 12 Si--S: F1rm: Dote: TA: ___ Firm: /r<a•27 / /r�r rcHr-a-Z. 4/n/c. Date:. / /- 2 / -Zv /4. F: Firm: - Dote: .,,,,,, ,..,,, If requested by engineer /orchitect of record or building official, the individual names of all prospective . . special Inspectors and the work they Intend to observe shall be identified as an attochment. Legend: SER m Structural Engineer of Record S1 -T = Special Inspector - Technical TA = Tes'ng Agency Sl -S = Special Inspector - Structural F = ab cater Accepted for the Building Department By ,_ Dale: if Z? (/0 _MN 13CSG -PROla 4/03 • • • 0 IN tnk T&B CERTIFIED TEST ADJUST BALANCE REPORT PROJECT: McDonald's #220129 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 ARCHITECT: Reprise Design MECH. ENGINEER: Dunham Associates GEN. CONTRACTOR: Greiner Construction PROJECT NUMBER: P1011020 "THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIROMENTAL SYSTEMS. ANY VARIANCES FROM DESIGN QUANTITES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE TEST - ADJUST- BALANCE REPORT PROJECT SUMMARY." T & B ENGINEER: Stephen K. Melink, PE COr ORIGINAL VISIT DATE: 2/28/2013 ► - 00 STEMEN N. MINK 2706 5140 River Valley Road, Milford, Ohio 45150 USA Phone: (513) 965 -7300 • Fax: (513) 965 -7350 www.melinkcorp.com • mail @melinkcorp.com TABLE OF CONTENTS PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 Table of Contents • Cover Page • Table of Contents • Abbreviations • Melink Credentials • Contact Information • Equipment Information • 1 Visit Summary • * Visit Summary • * Visit Summary • * Visit Summary • *Punch List • *Recommendations • *1 Visit Photos • * Visit Photos • * Visit Photos • *4 Visit Photos • *Rooftop Inspection • *Above Ceiling Inspection • *Below Ceiling Inspection • * Visit Inspection • Building Balance • *Motor Load Summary • RTU Data • *Air Distribution Data • Exhaust Fan Data • *Supply Fan Data • *Hood Data • *Smoke Detector • *Thermostat Settings • *Water Pump Valve Data • *Water Coil Data • *VAV & FPB Data • Building Layout *Indicates page inserted as necessary Melink Corporation Energy solutions for a brighter tomorrow Page 2 ABBREVIATIONS PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 ABBREVIATIONS AHU - Air Handling Unit AMP - Amperage BP - Building Pressure CFM - Cubic Feet/Minute EF - Exhaust Fan EH - Entry Heater ERU - Energy Recycling Unit ESP - External Static Pressure FLA - Full Load Amperage HP - Horse Power HZ - Hertz KH - Kitchen Hood KW - Kilowatt MUA - Makeup Air Unit Volts - Voltage OA - Outside Air RA - Return Air RPM - Revolutions Per Minute RTU - Roof Top Unit SF - Supply Fan / Safety Factor SP - Static Pressure VAV - Variable Air Volume WC - Water Column Melink Corporation Energy solutions for a brighter tomorrow Page 3 i MELINK CREDENTIALS PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 About Melink Values Our core values — integrity, innovation, and service excellence — are the essence of who we are as a company. They serve as the foundation for our words, actions and goals. Our culture starts with the above core values but also promotes professionalism, excellence, and leadership, as well as respect, fairness and charity. Experience For more than 25 years, Melink has been providing independent testing and balancing and installation verification services, thereby reducing operating costs and improving comfort for thousands of buildings. Collectively, Melink staff has over 150 years of experience in testing and balancing, installation verification, kitchen ventilation controls, HVAC design /consulting, HVAC service /installation, LEED building certification, indoor air quality testing, and solar PV installation /application. Certifications Melink has individuals on staff with the following certifications: • NEBB Certified TAB Professionals • NEBB Certified TAB Technicians • Professional Engineers (PE) • LEED Accredited Professionals (LEED AP) • North American Board of Certified Energy Practitioners (NABCEP) • Project Management Professionals (PMP) • Certified Project Managers (CPM) • Six Sigma Certified (SSWB, SSGB, SSBB) Affiliations Melink is proud to be associated with the following organizations: • The National Environmental Balancing Bureau (NEBB) • The American Society of Heating, Refrigerating and Air - Conditioning Engineers (AS H RAE) • The U.S. Green Building Council (USGBC) • The Professional Retail Store Maintenance Association (PRSM) • The Restaurant Facility Management Association (RFMA) • The Association of Energy Engineers (AEE) • The American Solar Energy Society (ASES) • The Solar Energy Industries Association (SEIA) • The North American Association of Food Equipment Manufacturers (NAFEM) Melink Corporation Energy solutions for a brighter tomorrow Page 4 TEST AND BALANCE CONTACT INFORMATION PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 PROJECT MANAGER: Raymond Croaston, Jr. Phone: (952) 884 -4355 Fax: N/A E -mail: ray.croaston@us.mcd.com SUPERINTENDENT: Bill Weinberger Phone: (612) 338 -1696 Fax: (612) 338 -1892 E -mail: bweinberger @greinerconstruction .biz MECH. CONTRACTOR: N/A Phone: N/A Fax: N/A E -mail: N/A MELINK TECHNICIAN: Joe Levy Phone: (513) 965 -6067 Fax: (513) 965 -7350 E -mail: jlevy @melinkcorp.com STRATEGIC ACCOUNT MANAGER: Michael McKinney Phone: (513) 965 -7024 Fax: (513) 965 -7350 E -mail: michaelmckinney_pmelinkcor•.com Melink Corporation Energy solutions for a brighter tomorrow Page 5 FIELD SUMMARY: CORRECTIONS PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 This air balance report is based on actual field readings and measurements taken from the store's HVAC Systems during operation. All systems were also balanced to within +/- 10% of design unless noted otherwise. The following corrections were performed by Melink and /or the contractors on -site. 1. Job site arrival. Melink arrived on the job site and met with the general contractor Bill Weinberger from Greiner Construction. Bill showed Melink the latest drawings to use for the Test and Balance visit. The electrical contractor was onsite for the duration of the Test and Balance visit to the restaurant. The mechanical contractor was not onsite for the Test and Balance visit to the restaurant. 2. Design Discrepancies. • EF -4 design horsepower is' /, actual horsepower is' . Seeing that desired CFM was achieved, no further action is needed. • EF -6 design horsepower is 1/4; actual horsepower is 1/2. Seeing that desired CFM was achieved, no further action is needed. • EF -7 design model number does not match installed unit. (See punch list for further details) • RTU's 1, 2, and 3 design model numbers do not match installed units. (See punch list for further details) • RTU -3 design CFM was listed as 5325. Connected load added up to 5300. RTU -3 was balanced to connect load CFM. 3. Roof top units (RTU's) adjustments and comments. RTU -1 was operating above total design airflow. The fan speed was decreased by adjusting the motor pulley. The outside air damper was set at or near design specifications. RTU -2 was operating above total design airflow. The fan speed was decreased by adjusting the MSAV settings. The outside air damper was set at or near design specifications. Diffuser 2C is operating below design CFM. The volume damper was verified to be 100% open and no comfort issues were noticed. No further action will be needed. RTU -3 was operating above total design airflow. The fan speed was decreased by adjusting the motor pulley. The outside air damper was set at or near design specifications. Diffusers 3H, 3I and 3J are operating below design CFM. The volume dampers were verified to be 100% open and no comfort issues were noticed. Diffusers 3Q and 3R are operating above CFM. Due to the location of the volume dampers being inaccessible, Melink was unable to adjust the CFM. No comfort issues were noticed. No further action will be needed. 4. Exhaust fan (EF) adjustments and comments. EF -1 was operating above total design airflow. The fan speed was decreased by adjusting the VSC located on the blower motor to help achieve total design airflow. Melink Corporation Energy solutions for a brighter tomorrow Page 6 FIELD SUMMARY: CORRECTIONS PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 This air balance report is based on actual field readings and measurements taken from the store's HVAC systems during operation. All systems were also balanced to within +/- 10% of design unless noted otherwise. The following corrections were performed by Melink and /or the contractors on -site. Continued: EF -2 was operating above total design airflow. The fan speed was decreased by adjusting the VSC located on the blower motor to help achieve total design airflow. EF -3 was operating above total design airflow. The fan speed was decreased by adjusting the VSC located on the blower motor to help achieve total design airflow. EF -4 was operating above total design airflow. The fan speed was decreased by adjusting the VSC located on the blower motor to help achieve total design airflow. EF -5 was operating at or near design. No fan speed adjustments were necessary. EF -6 was operating above total design airflow. The fan speed was decreased by adjusting the VSC located on the blower motor to help achieve total design airflow. EF -7 was operating at or near design. No fan speed adjustments were necessary. TF -1 was operating at or near design. No fan speed adjustments were necessary. TF -1 and EF -7 does not have an impact on the actual building pressure so they are not included on the building balance page within this report. 5. Thermostats and remote sensors. All thermostats and remote sensors are installed in the manager's office. All thermostats are programmed per customer's specification. 6. Kitchen hood smoke capture. All four kitchen hoods are capturing smoke satisfactorily. 7. Conclusion and final comments. The final results of the balance were discussed with Bill. The punch list for this location was emailed to the appropriate contacts. The final building pressure measured at +.006" W.C. Business cards were left onsite for any future questions. Melink Corporation Energy solutions for a brighter tomorrow Page 7 FIELD SUMMARY: PUNCH LIST PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 The following list details the remaining deficiencies of the store's HVAC and exhaust systems. These corrections are necessary to comply with the design specifications. Contractor Responsible. 1. Provide approval for model number discrepancy on EF -7. Owner The actual model number on EF -7 does not match the design model number, listed in the Design Prints. EF -7 is scheduled to be a Greenheck unit with model number MCGB -091 -4 and actually installed is a Greenheck unit with model number S- 099- V6 -4 -X. This discrepancy will need to be approved by the appropriate party. 2. Provide approval for model number discrepancy on RTU -1, RTU -2 and RTU -3. Owner The actual model number on RTU -1, RTU -2 and RTU -3 does not match the design model number, listed in the Design Prints. RTU -1 and RTU -3 are scheduled to be Lennox units with model number LGH180H4BS1Y and actually installed are Lennox units with model number LGH180H4BM2Y. RTU -2 is scheduled to be a Lennox unit with model number LGH048H4EM1Y and actually installed is a Lennox unit with model number LGH048H4EH1Y. This discrepancy will need to be approved by the appropriate party. Melink recommends revisiting this store due to the deficiencies listed above. Revisit necessary? No 30 -60 days after opening? No Before opening? No Project Manager: Please contact Melink in order to authorize the revisit. Melink Corporation Energy solutions for a brighter tomorrow Page 8 FIELD SUMMARY: RECOMMENDATIONS PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 The following list details the recommendations for improving comfort and energy efficiency. These items are not requirements of the design specifications. 1. Provide and install bypass duct work in both dining area entry vestibules. Melink recommends bypass duct work to properly relieve excess pressure in the entry vestibules. Melink Corporation Energy solutions for a brighter tomorrow Page 9 [ PHOTOS PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55 id = �u I ' IG Picture 1; Gas lines painted Picture 2 : Static pressure test ports plugged 7 4 'f.°' , :,,,, 1 - w c . t o � )a Picture 3: Filters clean Picture 4: Drains in talle sd s a Fro, i f Picture 5: RTU -1 and RTU -3 model number Picture 6: EF -7 model number Melink Corporation Energy solutions for a brighter tomorrow Page 10 PHOTOS PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 dl ; ' Y e , r-° �' ^� 7 " s,,y t .� '=•���fiyj F '4r `x �� � 8 tE '� w= . pp G Y 4 �1 b y ry ' -�,sr � '� i `C � b » I � Picture 7: Diffuser 3Q and 3R inaccessible Picture 8: Functioning thermostat I it or 0 = » ,.. Picture 9: Final building pressure Melink Corporation Energy solutions for a brighter tomorrow Page 11 ROOFTOP INSPECTION PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 DESCRIPTION STATUS RTU STANDARD 1 2 3 Verify proper unit locations NUE IN BURN Ell BE MEM Verify units marked for easy identification Irmun Inspect units • Unit sealed and properly seated to roof curb rivisi • Unit nameplate data matches design © ©© • Motor nameplate data matches design 11111111/ • No unusual vibration or noise OEM MIEMMOM FM M IMP • All filters installed, clean and secure MI MI IM • Condenser coil clean and free of damage Evann • Evaporator coil clean and free of damage Eismu • Gas cocks turned on IEME1 • Gas pipe painted MI IM El RI MMI lia Mt 14.1.11111 • Condensate drain lines properly installed Egrifin gym on spj FM Witifin • P -Traps properly installed go n immilt#14jimi • Drain lines properly sloped IM EA 111 12 Mt la MI BEIMENIS Remove unit access panels • Panels open freely and fully Maw ,:, • Panels latch securely WA El KIM ` • Belts properly tensioned and free of damage cji NA • Pulleys properly aligned Ei NA n in on Ifill pi rox Rm. tom • Blower wheel clean and free of damage 10113111 • Control transformer wired for correct voltage Ea MEI Buli 5111 III IM MI Mil LIMMI 1M Check disconnect switches and covers • Verify on /off disconnects work r • Verify voltage input correct EA WIEI 13 _ • Verify switch covers installed IMEISMISMI Iiii IN 1111 MI MI MI Power -on diagnostic check • Fans operating in correct rotation EIWIE1 MB El MI WM El Enin Euni • Compressors operating in correct rotation mg gmet • No unusual vibration or noise El MINIM Outside air (OA) dampers • Outside air dampers installed and operational MI MO • Ensure slightly positive building pressure In EIEt • Position marked for reference EEME • Sticker affixed to unit to preclude tampering minge Melink Corporation Energy solutions for a brighter tomorrow Page 12 ROOFTOP INSPECTION PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 DESCRIPTION STATUS EF TF STANDARD 1 2 3 4 5 6 7 1 Verify proper unit locations Ell 1111E111011E1E11181 Verify units marked for easy identification ESIBENEIMIE11111 e U Inspect units • Unit sealed and properly seated to roof curb 11E/ • Unit nameplate data matches design 1111111E11EllEME11 • Motor nameplate data matches design Ell ElEIEIE111E1© • No unusual vibration or noise E111011111111‘11111111111 Ell Exhaust fans (EF) • Transition from exhaust duct to fan installed mane NA MUM NA RAT jfrig • Duct continuously welded and liquid tight made NA =EL NA • Fan hinged and opened for easy access nano NA me NA • Grease traps properly installed 1111111111 NA NA NA NA E NA Remove unit access panels • Panels open freely and fully icutudd NA IrJE11 " , NA EiliUtt • Panels latch securely 1111011E11 Ell NA Eltilai NA • Belts properly tensioned and free of damage NA NA NA NA NA NA NA NA • Pulleys properly aligned NA NA NA NA NA NA NA MP NA rAirni • Blower wheel clean and free of damage IFIEMIEIE1 NA 1E11E1 ''` NA in EMI Check disconnect switches and covers • Verify on /off disconnects work Ell ElII1ESEMI1E11 • Verify voltage input correct ENEMA KIM MEI • Verify switch covers installed Ell Ell El Ell IPA; 70 ': Power -on diagnostic check • Fans operating in correct rotation EllE11111111/11WEIE Melink Corporation Energy solutions for a brighter tomorrow Page 13 ABOVE CEILING INSPECTION PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 DESCRIPTION STATUS STANDARD RTU Supply duct system 1 2 3 • Ductwork is installed as per design III W M Illi LIN gam 1111 MI BM NM • All volume dampers are properly installed EmEmgr • Dampers are accessible and operable Vilna Et EAR 111101 gitokaggio • Ductwork is properly covered with insulation, tIEIEi and insulation is secure • Tops of diffusers are properly insulated EMEIMI • Installed diffusers match design Ell EN El BOILSiglaill 1111 BM MB Biliti EF TF Exhaust duct system 1 2 3 4 5 6 7 1 • Cleanouts are installed where applicable 111111111E1 Ell ICI Ell 5; • Fire wrap is installed on duct as specified misisimiumi t o 1 • Horizontal duct is sloped as specified E1011111111Ell MIMI Ell r! d IMENHEE am • Welds appear to be liquid tight 1011111‘111121011111M Melink Corporation Energy solutions for a brighter tomorrow Page 14 BELOW CEILING INSPECTION PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 DESCRIPTION STATUS STANDARD RTU Thermostats 1 2 3 • Remote sensor is installed in its correct location 1E111E1 11111116111101111111111 ME 111111111011 • Remote sensor is wired to the proper thermostat EN a Ei • Thermostat is wired to the correct unit EIngr • Thermostat has proper operation Ell CI IIVJ NM tto iii IN bel PENN. NW illed • Thermostat is programmed correctly 111E11 El • Unit was cycled to verify proper operation mann • Heating mode tested satisfactorily Ell Ell III BM BM MI REfek 1111111111111111.11 • Cooling mode tested satisfactorily 111111111/11 KH Exhaust hoods 1 2 3 4 • Grease cups are installed E1EICIEI q' • All grease filters are installed ICIEIIMIVI • Filters are of correct type and size £lrl I l _ • Cooking appliances are operating KIM �J� " • Cooking appliances properly located under hoods inegme max;_ • Smoke capture is satisfactory MIEIEIE11 Comfort • Noticeable drafts? No • Comfort is good in all areas? Yes Communication • Final results were discussed with: — Superintendent Yes — Project manager NA — Store manager (if applicable) . NA • A punch list of deficiencies was provided to: — Superintendent and /or operations Yes — Project manager Yes —Store manager (if applicable) No • Business card was left on site with contact info. Yes Mellnk Corporation Energy solutions for a brighter tomorrow Page 15 BUILDING AIR BALANCE PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 TEST RESULTS (IN CFM ) MAKE -UP AIR EXHAUST AIR Design Final Design Final RTU -1 1500 1591 EF -1 1175 1185 RTU -2 450 464 EF -2 720 756 RTU -3 1700 1781 EF -3 720 726 EF -4 400 427 #' �ti 1� EF -5 75 78 EF 76 450 482 .1 ' K _ . ." a <; ` �' `:! Ig I Y h :.:: 1 - :: ,. Ld ui: ,' , x. t 4.z ... DESIGN TOTAL + 3650 DESIGN TOTAL — 3540 FINAL TOTAL + 3836 FINAL TOTAL — 3655 DESIGN BUILDING BALANCE = 110 CFM FINAL BUILDING BALANCE = 181 CFM FINAL BUILDING PRESSURE = +0.006" W.C. Melink Corporation Page 16 Energy solutions for a brighter tomorrow BALANCE SUMMARY PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 TEST RESULTS INITIAL CONDITIONS FINAL CONDITIONS RPM AMPS RPM AMPS RTU -1 857 9.7 RTU -1 753 7.9 RTU -2 1130 2.9 RTU -2 980 1.8 RTU -3 821 9.8 RTU -3 731 8.3 M ,- li4 V' EF -1 VSC 6.1 EF -1 VSC 1.4 EF -2 VSC 2.4 EF -2 VSC 1.1 EF -3 VSC 2.4 EF -3 VSC 1.1 EF -4 VSC 0.9 EF -4 VSC 0.6 EF -5 VSC N/A EF -5 VSC N/A EF -6 VSC 2.4 EF -6 VSC 1.1 EF -7 VSC 1.5 EF -7 VSC 1.5 TF -1 VSC N/A TF -1 VSC N/A TOTAL AMPS 38.1 TOTAL AMPS 24.8 MOTOR AMP SAVINGS 13.3 AMPS EFFICIENCY 35% Melink Corporation Energy solutions for a brighter tomorrow Page 17 ROOFTOP UNITS (RTU) DATA PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 RTU -1 RTU -2 RTU -3 Kitchen Support Dining _ DESIGN DATA SUPPLY CFM 5480 1600 5300 RETURN CFM 3980 1150 3600 O UTSIDE AIR CFM 1500 450 1700 ; 4 .. O UTSIDE AIR RATIO % 27% 28% 32% MODEL NUMBER LGH180H4BS1Y LGH048H4EM1Y LGH180H4BM1Y .' CAPACITY (TONS) 15 4 15 `" ` EXTERNAL S.P. 1.0" 1.0" 1.0" FAN HP 5 3/4 5 . I VOLTS / PHASE 208/3 208/3 208/3 FAN RPM 1075 810 1075 . A EQUIP. DATA UNIT MFR. Lennox Lennox Lennox ' • MODEL NO. LGH180H4BM2Y LGH048H4EH1Y LGH180H4BM2Y I ,'t' • SERIAL NO. 5612J06473 5612H10393 5612J03902 WriatattiR3 • RATED TONS 15 4 15 "i FAN MOTOR Baldor Genteq Baldor ,.n g t' ' ''' • MODEL NO. 103021 -01 101564 -07 103021 -01 "; r5 °'' • HP 5 3/4 atAIR • RPM 1750 1550 1750 FhigainGAZ • VOLTS / PHASE 208/3 208/1 208/3 E,',> C` • FLA / SF 14.6 1.2 6.1 1.2 14.6 1.2 MOTOR SHEAVE VP50 x 1 1/8" Direct Drive VP50 x 1 1/8" , FAN SHEAVE MB98 x 1 7/16" Direct Drive MB98 x 1 7/16" BELT(S) BX61 Direct Drive BX61 :,,' SHEAVE CENTERLINE 20 1/2" Direct Drive 20 1/2 " TEST DATA RPM - INITIAL / FINAL 857 753 1130 980 821 731 Ening,,iiiiiiiat 1:;t! ACTUAL VOLTS 217 217 216 218 217 216 217 217 216 OPERATING AMPS 8.4 7.6 7.6 1.8 N/A N/A 8.7 8.1 8.1 S UCTION / DISCHARGE 0.44" 0.56" 0.19" 0.42" 0.36" 0.48" EXTERNAL S.P. 0.77" 0.48" 0.65" ItiAltr&C;;_nbiptNiN, MOTOR HERTZ N/A N/A N/A SUPPLY CFM 5306 1529 5362 l infiSk -' -5' , 1: ' RETURN CFM 3725 1072 3575 OUTSIDE AIR CFM 1591 464 1781 ¢ OUTSIDE AIR RATIO % 30% 30% 33% ll,; Melink Corporation Energy solutions for a brighter tomorrow Page 18 AIR DISTRIBUTION DATA PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 SYSTEM: RTU -1 Kitchen DESIGN PRELIM FINAL NO. AREA SERVED TYPE OUTLET SIZE CFM CFM CFM _ 1A Kitchen _ 4 -Way _12" Round 635 563 614 _ 1B Kitchen _ 4 -Way 12" Round 635 482 589 _ 1 C Kitchen _ 4 -Way 12" Round 635 524 593 _ 1D Kitchen 4 -Way 12" Round 635 553 640 _ 1 E Kitchen 4 -Way _12" Round 635 476 573 _ 1 F Kitchen 4 -Way _ 12" Round_ 635 514 636 1G Kitchen 4 -Way 12" Round 635 576 607 1H Kitchen 4 -Way 12" Round 635 475 676 11 Kitchen 4 -Way 12" Round 400 634 378 SUPPLY AIR ( f 5480 I 4797 I 5306 RA -1A Kitchen Return Grille 16" Round 796 N/A 731 _ RA-1B Kitchen Return Grille 16" Round 796 N/A 753 _ RA-1C Kitchen Return Grille 16" Round 796 N/A 744 RA-1D Kitchen Return Grille 16" Round 796 N/A 742 RA-1E Kitchen Return Grille 16" Round 796 N/A 755 RETURN AIR 3980 3725 OUTSIDE AIR 1500 1591 %OUTSIDE AIR 27% 30% Melink Corporation Energy solutions for a brighter tomorrow Page 19 L AIR DISTRIBUTION DATA PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 SYSTEM: RTU -2 Support DESIGN PRELIM FINAL NO. AREA SERVED TYPE OUTLET SIZE CFM CFM CFM _ 2A Once 2 -Way _ 8" Round 150 205 136 _ 2B Hallway 2 -Way _ 8" Round 150 188 146 2C Break Room _ 3 -Way 8" Round 250 239 176 _ 2D Hallway _ 4 -Way _ 8" Round 150 206 146 _ 2E Rear Entry 4 -Way _ 10" Round 250 383 272 2F Storage 3 -Way _ 8" Round 200 264 218 _ 2G Storage _ 4 -Way 8" Round 225 254 221 2H Storage 4 -Way 8" Round 225 232 214 I SUPPLY AIR n 1600 I 1971 I 1529 I RA -2A Storage Return Grille 14" Round 575 N/A 525 _RA -2B Storage Return Grille 14" Round 575 N/A 547 RETURN AIR 1150 1072 OUTSIDE AIR 450 464 %OUTSIDE AIR 28% 30% Melink Corporation Energy solutions for a brighter tomorrow Page 20 r AIR DISTRIBUTION DATA PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 SYSTEM: RTU -3 Dining DESIGN PRELIM FINAL NO. AREA SERVED TYPE OUTLET SIZE CFM CFM CFM _ 3A Men's RR _ 4 -Way 8" Round 150 146 135 _ 3B Women's RR 4 -Way 8" Round 150 148 144 3C Side Dining _ 4 -Way 8" Round 250 384 253 _ 3D Side Dining _ 4 -Way 8" Round 225 375 240 _ 3E Side Dining 4 -Way 10" Round 250 269 261 _ 3F Side Dining _ 4 -Way 14" Round 250 289 265 _ 3G Entrance 4 -Way 8" Round 150 61 164 3H Dining Room _ 4 -Way 10" Round 350 222 199 _ 31 Dining Room _ 4 -Way 10" Round 350 232 208 3J Dinin. Room 4 -Wa 10" Round 350 269 241 3K Dining Room _ 4 -Way 10" Round 350 439 343 _ 3L Dining Room _ 4 -Way 10" Round 350 432 360 _ 3M Entrance _ 4 -Way 8" Round 150 342 145 3N Dining Room 4 -Way 10" Round 350 341 369 30 Beverages 4 -Way 10" Round 300 379 295 _ 3P Drive Thru 4 -Way _ 10" Round 300 269 298 _ 3Q Dining Room 4 -Way 10" Round 350 633 591 3R Dining Room 4 -Way 8" Round 225 403 376 3S Cashier 4 -Way — 8" Round 225 286 247 3T Cashier 4 -Way 8" Round 225 315 228 I SUPPLY AIR I 1 5300 I 6234 I 5362 I RA -3A Dining Room Return Grille - 16" Round 720 N/A 701 _ RA -3B Dining Room Return Grille 16" Round 720 N/A 727 RA -3C Dining Room Return Grille 16" Round 720 N/A 722 _RA -3D Dining Room _ Return Grille 16" Round 720 N/A 709 RA-3E , Dining Room Return Grille 16" Round 720 N/A 716 RETURN AIR 3600 3575 OUTSIDE AIR 1700 1781 %OUTSIDE AIR 32% 33% Melink Corporation Energy solutions for a brighter tomorrow Page 21 Y r AIR DISTRIBUTION DATA PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 SYSTEM: EF -4 Restrooms DESIGN PRELIM FINAL NO. AREA SERVED TYPE INLET SIZE CFM CFM CFM — _ EF4A Mens's RR Ceiling Grille 8" x 8" 200 236 215 EF4B Women's RR Ceiling Grille 6" Round 200 262 212 I EXHAUST AIR CFM I I 400 I 498 I 427 I SYSTEM: EF -5 Janitor's Closet DESIGN PRELIM FINAL NO. AREA SERVED TYPE INLET SIZE CFM CFM CFM EF5A Janitor's Closet Ceiling Grille 8" x 8" 75 78 78 I EXHAUST AIR CFM I I 75 I 78 I 78 I SYSTEM: EF -7 Garage DESIGN PRELIM FINAL NO. AREA SERVED TYPE INLET SIZE CFM CFM CFM EFTA Garage Ceiling Grille 12" x 12" 800 780 780 I EXHAUST AIR CFM 1 I 800 I 780 I 780 I Melink Corporation Energy solutions for a brighter tomorrow Page 22 [ AIR DISTRIBUTION DATA PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 SYSTEM: TF -1 Computer Closet DESIGN PRELIM FINAL NO. AREA SERVED TYPE INLET SIZE CFM CFM CFM TF1A Computer Closet Ceiling Grille 8" x 8" 250 235 235 I EXHAUST AIR CFM ` I 250 ' 235 1 235 I Melink Corporation Energy solutions for a brighter tomorrow Page 23 r EXHAUST FAN (EF) DATA PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 EF -1 EF -2 EF -3 EF -4 KH -1 KH -2 KH -3 Restrooms _ DESIGN DATA EXHAUST CFM 1175 720 720 400 MODEL NUMBER MCD- CUE162 MCD- CUE142 MCD- CUE142 MCD -G -098 EXTERNAL S.P. 0.77 0.79 0.79 0.5 FAN HP 3/4 1/2 1/2 1/2 VOLTS / PHASE 120/1 120/1 120/1 120/1 FAN RPM 1124 1284 1402 1118 EQUIP. DATA UNIT MFR. Greenheck Greenheck Greenheck Greenheck _» MODEL NO. MCD- CUE162 MCD- CUE142 MCD- CUE142 MCD -G -098 _» SERIAL NO. 13098853 13096155 13106273 13043208 FAN MOTOR Greenheck Greenheck Greenheck Greenheck MODEL NO. N/A N/A N/A N/A HP 3/4 1/2 1/2 1/4 _- RPM 1725 1725 1725 1725 _ VOLTS / PHASE 120/1 120/1 120/1 120/1 FLA / SF 10.1 I N/A 6.2 I N/A 6.2 I N/A 3.9 I N/A MOTOR SHEAVE Direct Drive Direct Drive Direct Drive Direct Drive FAN SHEAVE Direct Drive Direct Drive Direct Drive Direct Drive BELT(S) Direct Drive Direct Drive Direct Drive Direct Drive SHEAVE CENTERLINE Direct Drive Direct Drive Direct Drive Direct Drive TEST DATA RPM - INITIAL / FINAL VSC I VSC VSC I VSC VSC 1 VSC VSC I VSC ACTUAL VOLTS 117 N/A N/A 117 N/A N/A 117 N/A N/A 117 N/A N/A OPERATING AMPS 1.4 N/A N/A 1.1 N/A N/A 1.1 N/A N/A 0.6 N/A N/A SUCTION / DISCHARG: N/A I N/A N/A I N/A N/A I N/A N/A I N/A EXTERNAL S.P. N/A N/A N/A N/A MOTOR HERTZ N/A N/A N/A N/A EXHAUST CFM 1185 756 726 427 Melink Corporation Energy solutions for a brighter tomorrow Page 24 EXHAUST FAN (EF) DATA PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 EF -5 EF -6 EF -7 TF -1 Janitor's Closet KH - Garage Computer Closet DESIGN DATA EXHAUST CFM 75 450 800 250 MODEL NUMBER SP -A90 MCD- CUBE -101 HP MCGB -091 -4 SP -Al25 EXTERNAL S.P. 0.2 0.79 0.75 0..20 FAN HP N/A 1/4 1/4 N/A VOLTS / PHASE 120/1 120/1 120/1 120/1 FAN RPM 900 900 N/A 1075 EQUIP. DATA UNIT MFR. Greenheck Greenheck Greenheck Greenheck • MODEL NO. SP -A90 MCD- CUBE -101 HP S- 099- V6 -4 -X SP -Al25 SERIAL NO. N/A 13095084 13095083 N/A FAN MOTOR McMillan Greenheck Greenheck McMillan !_• MODEL NO. N/A N/A N/A N/A _ • HP N/A 1/2 1/4 N/A _^ RPM 900 2500 1725 N/A _ VOLTS / PHASE 120/1 120/1 120/1 120/1 • FLA / SF 0.43 I N/A 6.5 I N/A 3.9 I N/A N/A I N/A MOTOR SHEAVE Direct Drive Direct Drive Direct Drive Direct Drive FAN SHEAVE Direct Drive Direct Drive Direct Drive Direct Drive BELT(S) Direct Drive Direct Drive Direct Drive Direct Drive SHEAVE CENTERLINE Direct Drive Direct Drive Direct Drive Direct Drive TEST DATA RPM - INITIAL / FINAL VSC 1 VSC VSC I VSC VSC I VSC VSC I VSC ACTUAL VOLTS 117 N/A N/A 117 N/A N/A 117 N/A N/A 117 N/A N/A OPERATING AMPS N/A N/A N/A 1.1 N/A N/A 1.5 N/A N/A N/A N/A N/A SUCTION / DISCHARGE N/A I N/A N/A I N/A N/A I N/A N/A I N/A EXTERNAL S.P. N/A N/A N/A N/A MOTOR HERTZ N/A N/A N/A N/A EXHAUST CFM 78 482 780 235 Melink Corporation Energy solutions for a brighter tomorrow Page 25 KITCHEN HOOD (KH) DATA PROJECT: McDonald's #220129 DATE: 2/28/2013 LOCATION: 16831 Highway 13, Prior Lake, MN 55372 KH -1 KH -2 KH -3 KH -4 Clam Shell Grill Fryers Fryers Steamer DESIGN DATA _MAKE -UP CFM N/A N/A N/A N/A EXHAUST CFM 1175 720 720 450 BALANCE RATIO % N/A N/A N/A N/A EQUIP. DATA HOOD MFR. HKD HKD HKD Greenheck • MODEL NO. UH -83 UH -50 UH -50 GO -3.5 -S _ • HOOD TYPE Low Profile Low Profile Low Profile Exhaust Only FUEL TYPE Gas Electric Gas N/A _MUA OPEN. TYPE NA NA NA N/A _MUA WIDTH /LENGTH N/A 1 ,1 N/A N/A ', r " ' N/A N/A N/A N/A N/A FILTER MFR. Franke Franke Franke Raw opening FILTER HEIGHT 10 10 10 12" x 12" FILTER LENGTHS � m 5 4 w 4 4, , ,�u "r A 20 16 f 16 '4 Correlates B 20 �r, 16 �, 16 ht with filter C 20 16 16 4 I velocities D 20 k ��,� I otto below E F :IIIII .414 TEST DATA MUA AVG. FPM N/A N/A N/A N/A MUA CFM N/A N/A N/A N/A EXH. AVG. FPM m A 248 257 _ _ 257 482 Correlates B 253 263 'm'a _ 262 ill with filter C 259 262 253 __ velocities D 249 __ — above E p F ILL Iii __ ea __ EXH. CFM 1185 756 726 482 BALANCE RATIO N/A N/A N/A N/A Melink Corporation Page 26 Energy solutions for a brighter tomorrow