HomeMy WebLinkAboutFire Sprinkler Inspection Repor
Inspection Report
GILBERT MECHANICAL CONTRACTORS, INC.
4451 W. 76th St. - Minneapolis, MN 55435
Office phone 952-835-3810 Fax 952-835-4765
1nspection#
Inspection Date: 3/15/05
Bil/ing Info1'1lUlJWn:
Name: R ak Construction
Addres" 171001 Highway 65
City. State, Zip: Ham Lake, MN 55304
Job Information:
New Horizon Daycare
*'llC 4/~()O
Prior Lake, MN
rl.lt- H,'flS
1. GRNRRA 1
a: Is the building occupied?
b. Is occupancy same as previous inspection?
c. Are all the systems in service?
d. Are all fire protection systems same as last inspection?
e. Is hazard completely sprinldered?
f. Are all new additions and buildinJ!: changes ...w..........,. v~.u'"-'-.;;.!
g. Is all stock or stornte ~operly below sprinkler p~?
h. Was property free of fire since last inspection? (Explain any fire-on Pue 2)
I. In areas protected by wet system, does the building appear to be properly heated in all areas, including blind attics
and perimeter areas aod are all exterior oJ>enin2s proteCted a.2ainst entrance of cold air?
2. CONTROl" VAl_VR.~ (.~P.I! ,~l'.tinn. 161
a. Are all sprinkler system main control valves open?
b. Are aD other valves in Droner oosition?
c. Are all control valves in good condition and sealed or supervised?
3. WATRR t;;llPPT lRfl: (SPR. ,'\'-mfln. 'Zl
a. Was a water flow test made and results satisfactory?
4. TANK.r; P1TUP,ro: F'lRR nRPARTMRNTCONNRrT/ONS
a. Are fire pumps, gravity tanks, reservoirs and pressure tanks in good condition and properly maintained?
b. Are fire ~ connections in satisfactory condition, couplings free. caps in place and check valv~ tight?
S. WRT ~YSTRM.f; (.~" S,r.tion B)
a. Are cold weather valves open or closed as necessary?
b. Have antifreeze systeIllS been tested and left in satisfactory condition?
c. Are alarm valves. water flow indicators and retards in satisfactory condition?
6. DRY .~Y.~TEMS ('\" S.~r.tion 141
a. Is dry valve in service and in good condition?
b. Is air pressure and prim.ing water level normal?
c. Is air compressor in good condition?
d. Were low points drained d~ fall and winter inspection?
e. Are Quick: Opening Devices in service?
f. Has piping been checked for stoppa~e within past 10 years?
g. Has piping been checked for ~ pitch within past 5 years?
h. Have dry check valves been trip tested satisfactorily as required?
L Are dry valves adequately protected from freezing?
j. V~e house and heater condition satisfactory?
7. SPECIAl, .~Y~TRM.fl fSp.p. .~I!r.ti.on INI
a. Were valve systems teSted as required?
b. Were all heat responsive systems tested and results satisfactory?
c. Were supervisOry features tested and results satisfactory?
8. AlARMS
a. Water motor and ~omr: test satisfactory?
b. Electric alarm test satisfactory?
c. Supervisory alarm service test satisfactory?
9. ,flPRTNK1 RR,~ _ PTPlNG
a. Are all sprinklers in J;!;ood condition, not obstructed, and free of corrosion or loading?
b. Are all sprinklers less than 50 years old?
c. Are extra sprinklers readily available?
d. Is condition of pipi.n2. drain valves. check valves. hangers. pressure gauges, open sprinklers, strainers satisfactory?
e. Are all sprinklers of proper __..._..___ rating?
f. Are portable fire extinguishers in good condition?
g. Is hand hose on sprinkler systems satisfactory?
x
X
I X I
X -
X
X
X
X
X
Yes N/A No.
X L
X
X
Yes N/A No'
X
Ye, N/A No.
X J
X
Yes N/A No.
X
X
X
Yes N/A No.
X I
X I
X I
X
X I
X I
X I
X I
X J
X
N/A No.
X
X
X
Yes N/A No.
I I X I
X
X
Yes N/A
X
X
X
X
X
"'Explain "No. answer.ton Page 2
GILBERT MECHANICAL CONTRACTORS, INC.
4451 W. 76th St. - Minneapolis, MN 55435
Inspection #
Inspector: Dean Kaminski
10. Date Dry System PiPinst last checked for stotmaae:
11. Date Dry System PiPing last checked. for proper pitch:
12. Date Dry !'iDe Valve last trio tested:
13. Wet Systems: MiIre and Model?
14. Dry SystemS: MiIre and Model?
IS. Special Sys_ Type?
MiIre and Model?
Number
Type
PIV
Open
Yes No
X
Condition?
Secured
Yes No
X
Good
Closed
Yes No
Signs
Yes No
X
Condition
16. CONTR()(. VA1.VE.f;
City Connection Control Valve
DrySvstem
Sectional Control Vilives
System Control Valves
17. WATER flLOW TEST
Water Pressure?
Water Flow Test?
Butterfly X
X
X
Test Pipe Located
MechauicaI Room
95 CITY PSI TANK PSI FIRE PUMP PSI
Yes (If none made, Why?)
Size Pressure Flow Pressore Size Pressure Flow Pressure
Test Pipe Before Pressor. After Test Pipe Locau:d Test Pipe Before Pressor. After
1-1/4" 95 85 92
18. B~at Responsive Devit:es: Type of Test?
Valve # A B C D E F Valve # A B C D E F
Valve # A B C D E F Valve # A B C D E F
Valve # A B C D E F Valve # A B C D E F
Valve II A B C D E F Valve # A B C D E F
Auxiliary Equipment? Number? Type? LoCation? Test Results?
19. Erplanalion of any "No" onS'<<rs:
Both check gauges are plugged and need to be replaced.
Outside horn works, but inside horn and strobes not working.
20. Recent c1uJnges in building occupancy or fire protection equipment:
21. A4iust1nent or corrections moile:
22. lJesirable improvements: