Loading...
HomeMy WebLinkAboutBack Up Info 07.0772 - 2 OF ' PRio Uxxf White - Building ...)4'INNEsc Canary -Engineering Pink -Planning BUILDING PERMIT APPLICATION DEPARTMENT CHECKLIST NAME OF APPLICANT /2/e6 1-A166 C'tN.l"7 Je.T/cit✓ C- iCoc/P APPLICATION RECEIVED 6. Z. (j The Building, Engineering, and Planning Departments have reviewed the building permit application for construction activity which is proposed at: /(33.5 /pi—,5—CA ,4V6/vae— 5 Accepted Accepted With Corrections t,' ` Denied Reviewed By: i,M�- -- Date: ,541D-7 Comments: SCC Pc.--/i/J ier.f lics"-o- < <�-, ,6vt-r-6- c. .c-- 21 2 co 7 7 -0(2, ee)414-76A-rs 7-41-11 A7245 /"Ic.,--(4.4o L & SLVC-(60 /1(c- /i - , ,--, (-1:6,72_, (R,,tha--. .,n . c2.,,,,,,,7 5--sc..), i0 "The issuance or granting of a permit or approval of plans, specifications and computations shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other ordinance of the jurisdiction. Permits presuming to give authority to violate or cancel the provisions of this code or other ordinances of the jurisdiction shall not be valid." White -Building �P Canary -Engineering 40-tNNESo Pink -Planning BUILDING PERMIT APPLICATION DEPARTMENT CHECKLIST NAME OF APPLICANT &/ce- C..i`-I4-t' S ( OATS /t'c//CAI 01--) APPLICATION RECEIVED 6. Z. ( 7 The Building, Engineering, and Planning Departments have reviewed the building permit application for construction activity which is proposed at: /(7335- / S -i AVel:A-'uG Accepted Accepted With Corrections Denied Reviewed By: ''�7 �� . Date: 1/2ZIZ Comments: A v-! I"- , reo� Pr~ 0cp Ca, i( 1SZ —qc17 - 9 830 -k LI ( -I, y "The issuance or granting of a permit or approval of plans, specifications and computations shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other ordinance of the jurisdiction. Permits presuming to give authority to violate or cancel the provisions of this code or other ordinances of the jurisdiction shall not be valid." BR1901 t=1 `ate White -Building ivEsQ? • _ . -Engineering Pink -P tinning BUILDING PERMIT APPLICATION DEPARTMENT CHECKLIST NAME OF APPLICANT L A-, „Ai APPLICATION RECEIVED The Building, Engineering, and Planning Departments have reviewed the building permit application for construction activity which is proposed at: wool. r 1 ;# /it • Accepted Accepted With Corrections Denied CE:Reviewed By: '' Date: 42'3/x"7 Comments:43, "The issuance or granting of a permit or approval of plans, specifications and computations shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other ordinance of the jurisdiction. Permits presuming to give authority to violate or cancel the provisions of this code or other ordinances of the jurisdiction shall not be valid." It Metropolitan Council July 6,2007 Bob Hutchins Building Official City of Prior Lake 4646 Dakota Street SE Prior Lake, MN 55372 Dear Mr. Hutchins: The Metropolitan Council Environmental Services(MCES)Division has reviewed the SAC assignment for the City of Prior Lake Water Treatment Plant. The original letter for this determination was dated July 5,2007, letter reference 070705A3. This project is located at 16335 Itasca Avenue SE within the City of Prior Lake. This project should be charged 25 SAC Units, instead of the 45 units originally assigned. The SAC review is based on updated information. This determination follows: SAC Units Charges: Backwash 5650 gal/day @ 274 gallons/SAC Unit 20.62 Fixture Units 56 f.u. @ 17 f.u./SAC Unit 3.29 Lockers(with showers) 10 lockers @ 14 lockers/SAC Unit 0.71 Total Charge: 24.62 or 25 The business information was provided to MCES by the applicant at this time. It is the City's responsibility to substantiate the business use and size at the time of the final inspection. If there is a change in use or size, a redetermination will need to be made. If you have any questions,call me at 651- 6024378. 51- 602-1373. Sincerely, Jessie Nye SAC Technician Environmental Services Division JN:kb: 070706B1 cc: S. Selby,MCES Seth Peterson,Bolton&Menk www.metrocouncil.org 390 Robert Street North • St. Paul,MN 55101-1805 • (651) 602-1000 • Fax(651) 602-1550 • TTY(651) 291-0904 An Equal Opportunity Employer • . Minnesota Department of Labor and Industry 443 Lafayette Road North, St. Paul, MN 55155-4342 Phone: (651) 284-5064, TTY/MRS: (651) 297-4198 www.electricity.state.mn.us Electrical Inspection Report Date Request for Inspection Serial Number Date Filed 8/12/09 23704026 9/18/08 Electrical Contractor/Installer License Number KILLMER ELECTRIC CA01003 Owner/Occupant County CITY OF PRIOR LAKE SCOTT Job Address—Street Cityrrownship 16335 ITASKA AVE PRIOR LAKE The following items are deviations from the accepted standards of construction at the premises identified above. NEC 230.95 (C) PERFORMANCE TESTING OF GROUND FAULT SYSTEM The ground fault protection systemshall be performanced tested when first installed at the site. The test shall be conducted in accordance with instructions that shall be provided with the equipment. A written record of this test shall be made and shall be available to the authority having jurisdiction. TEST THE GROUND FAULT SYSTEMS ON THE BUILDING SERVICE AND THE GENERATOR AND PROVIDE A WRITTEN DOCUMENTATION OF THIS PERFORMANCE TEST BY NO LATER THAN 8/26/09 Correct the noted deficiencies and: 0 Notify the inspector for reinspection before concealing wiring ❑ Reinspection will be made at final inspection ®Sign and return this form to the inspector when deficiencies are corrected but no later than 8/26/09 Inspector Name Number Inspector Telephone Number Inspector E-mail/Website WALT LUSIAN 184 952 934 0229 wlusian@comcast.net Inspector Address State Zip 16275 SHELDON AVE EDEN PRAIRIE MN 55344 Signature of Installer Compliance Date This material can be made available in different forms,such as large print, Braille or on a tape. To request, call 1-800-342-6364(DIAL-DLI) %/..10....TRO MC41 007 A400 •CONTRACTOR'S MATERIAL & TEST CERTIFICATE PARTS A & C — SPRINKLER & WATER SPRAY ABOVEGROUND PIPING (Fill Out Separate Certificate For Each Mier) • PROCEDURE UPON COMPLETION or WORK,INSPECTION AND TEST$SHALL BE MADE BY THE CONTRACTOR'S REPRESENTATIVE AND WIT AN OWNER'S REPRESENTATIVE. ALL DEFECTS SHALL BE CORRECTED AND SYSTEM LEFT IN SERVICE BEFORE CONTRACTORNES'SSED M CINALLY LEAVE THE JOB. A CERTIFICATE SHALL BE PILLED our AND SIGNED BY BOTii REPRESENTATIVES. COPIES SHALL BC PREPARED FORLAPWPRtOVRIAUTHOR $. OWNERS ANC) CE1OORREPRESENTATIVE'S AGAINST ron FAUt.TY MiQTIALOPWORKMANSHIP. Oil FAILURE TO COMPLY QUi AUTHORITY'S REQUIREMENTS On LOCAL ORDINANCES. PROPERTY NAME Prior Lake Water Treatment Facility DATE PROPERTY ADDRESS 11-3-08 16335 Itasca Ave: ACCEPTED BY APPROVING AUTHORITY(•$) NAMES • City of Prior Lake . ADORES$ PLANS 170-7. _Adelmann St . SE Prior Lake, MN 55372 • INSTALLATION CONFORMS TO ACCEPTED PLANS' YES ID NO Q EQUIPMENT USED IS APPROVED YES•f]r NO Q IF NO,STATE DEVIATIONS • HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OF CONTROL VALVES AND CARE OF THIS NEW EQUIPMENT? YES A NO 0 IF YES. GIVE NAME. IF NO,EXPLAIN. INSTRUC- TIONS HAVE COPIES OF APPROPRIATE INSTRUCTIONS AND CARE AND MAINTENANCE CHARTS AND NFPA 13A BEEN LEFT ON PREMISES? YES NO 0 IF YES, GIVE NAME. IF NO, EXPLAIN. • • HYDROSTATIC* Hydrostatic tests shalt be made at not less than 200 PSI (I3.11 bars) for two hours or SO P51 (3.4 ba above Italic pressure In excess 65.150 PSI (10.3 bars). Dlfferenttal•dry-Rlpe valve clappers shall be lift open during test TEST Prevent damage. All aboveground piping faecal', shall be stopped. • D ESCR IP- TION PNEUMATIC: Establish 40 PSI 12.5 bars) air pressure and measure drop which shell not exceed 1W PSI (0.1 bars) In hours. Test pressure tanks at normal water level and air pressure end measure air pressure drop which shall not exceed PSI (0.1 bars) In 24 hours. HYDROSTATIC: ALL PIPING. 2" TESTS PNEUMATIC: DRY PIPING DRAIN REQUIRED EQUIPMENT OPERATION: ALL. s ' SERVES BLDG$: LOCATION Southeast part of building Generator Room MAKE MODEL SIZE QUANTITY TEMPERATURE RAT SPRINKLERS Tyco TY-FRB 1/2" 16 • 17;, OR - • SPRAY • NOZZLES MATERIAL ANO KIND CONFORMS TO META 13 STANDARD PIPE AND IF NOME. EXPLAIN FITTINGS A L A P H DEVICE MA(lMVM TIME TO OPERATE THROUGH TEST I ALARM VALVE TYPE MAKE MODEL MIN. _— SEC. OR FLOW Vane Potter VSR-F INDICATOR _ ^- FORM a, AC REVISED APRIL 1979 PRINTED iN U.S.A. FCR NAS & FCA, INC., P•O. PDX 719,MT. KISCO. N.Y. CON'T'RACT'OR'S MATERIAL & TEST CERTIFICATE __FL_ PARTS A & C — SPRINKLER & WATER SPI(AY ABOVEGROUND PIPING (Fill Out Separate Cartificote For Each Riser) • PROCEDURE • UPON COMPLETION OF WORK.INSPECTION nr•IU TESTS SHALL BE MADE BY THE CONTRACTOR'S REPRESENTATIVE AND WITNESSED AN OWNER'S REPRESENTATIVE. ALL DEFECTS SHALL BE CORRECTED ANO SYSTEM LEFT IN SERVICE BEFORE CONTRACTOR'S M FINALLY LEAVE THE JOB. A CERTIFICATE SHALL BE FILLED our AND SIGNED BY BOTH REPRESENTATIVES. COPIES SHALL BE PREPARED FOR APPROVI AUTIIORtTIES. OWNERS AND cowlrinciOrl. IT IS UNDERSTOOD THE OWNER'S REPRESENTATIVES SIGNATURE IN NO wAY PR VOICES ANY CLAIM AGAINST co sr:Acton roil FAULTY MATERIAL. POOP WORKMANSHIP. OR FAILURE TO COMPLY WITH e PROVING AUTHORITY'S REQUIREMENTS On LOCAL ORDINANCES. PROPERTY NAME DATE Prior Lake Water Treatment Facility 11-3-08 PROPERTY ADDRESS 16335 Itasca Ave: ACCEPTED BY APPROVING AUTHORITY('S) NAMES • City of PriorLake . - _ ADDRESS PLANS 170-7,3 _Adelmann St . SE Prior Lake, MN 55372 INSTALLATION CONFORMS TO ACCEPTED PLANS: YES SI NO 0 YES k) NO 0 EQUIPMENT USED IS APPROVED • IF NO,STATE DEVIATIONS • HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION YES Ic7 NO 0 OF CONTROL VALVES ANO CARE OF THIS NEW EQUIPMENT? IF YES, GIVE NAME. IF NO,EXPLAIN. • INSTRUC• TIONS HAVE COPIES OF APPROPRIATE INSTRUCTIONS ANO CARE AND MAINTENANCE• YES 21 NO 0 CHARTS ANO NEPA 13A BEEN LEFT ON PREMISES? IF YES, GIVE NAME. IF NO, EXPLAIN.• • HYDROSTATIC: Hydrostatic tests shall be made at not less than 200 PSI (I3.3 bars) for two hours or So PSI (3.4 pa above static pressure in excess Of 150 PSI (10.3 bars). DIIferentlal•dry.plpe valve clappers shall be lift open during test TEST prevent damage. All aboveground piping leakage shall be stopped. - . DESCRIP- • TION PNEUMATIC: Estab)lsh 40 PSI (2.3 bars) air pressure and measure drop which shell notdrop exceeewhd ich IVs shall PSI (0no!.1 bars)slrtatd In hours. Test pressure tanks at normal water level and air pressure and measure air pressure PSI (0.1 bars) In 24 hours. HYDROSTATIC: ALL PIPING. 2tt TESTS PNEUMATIC: DRY PIPING DRAIN REQUIRSO EQUIPMENT OPERATIONS ALL. s • • SERVES BLOCS: , . LOCATION Southeast part of building Pump Room MARE MOOEL SIZE ^Tyco TY-FRB White 1/2" QUAt`tT7IT" TEMPERATURE RAISPRINKLERS Tyco TY-FRB • 1/211 . 172 OR • SPRAY Tyco TY-FRB 1/2" . 24 NOZZLES MATERIAL AND KING CONFORMS TO TI '17A 13 STANDARD PIPE AND tF NONE. EXPLAIN FITTINGS ALARM DEVICE MAXIMUM TIME TO O PgRATE THROUGH T£ST I SEC. TYP£ MAKE MODEL MIN. ALARM VALVE / ' OR FLOW Vane Potter VSR-F INDICATOR — . ..— FOM a! AC REVtSEOAPnIL 1979 PN RITED IN U.S.A. FOR HAS 6 FCA. INC.. P.Q. BOX 719, MT. KIS`CO'N.Y. R FUNDAMENTALS OF FIRE ALARM SYSTEMS 72-Si FIRE ALARM SYSTEM _ RECORD OF COMPLETION Name of prottc ed roPerty: Pap *� '' tele-4,-1"-K- TrY-011- do(''- Address: 1� 13 9 4d q V er,'o i 1,-4 Ie,e/ file c.5- 3 7 'y Representative of protected propertx(name/p one): Authority having jurisdiction: f"i'i Pr 4 ' ,'/r .7,e Address!telephone number: y�11 Organization name/phone Representative name I phone Installer ' v C i✓ b 17) LI ry- f% 3 G 4i Supplier e 41i t, 4--" o , ')1 y 3 A C of S 8 Service organization M t 1'r A /j f. ✓(rt �(p( r � �( �`Q� Location of record(as-built)drawings: Location of operation and maintenance manuals: _. Location of test reports: A contract for test and inspection in accordance with NFPA standard(s) Contract No(s): Effective date: Expiration date: System Software (a)Operating system(executive)software revision level(s): (b)Site-specific software revision date: (c)Revision completed by: _ (name) (firm) 1.Type(s)of System or Service .NFPA 72,Chapter 6—Local If alarm is transmitted to location(s)off premises,list where received: _______NFPA 72,Chapter 8—Remote Station Telephone numbers of the organization receiving alarm: Alarm: Supervisory: _ Trouble: If alarms are retransmitted to public fire service communications centers or others,indicate location and telephone numbers of the organization receiving alarm: Indicate how alarm is retransmitted: ___NFPA 72,Chapter 8—Proprietary Telephone numbers of the organization receiving alarm: Alarm: Supervisory: Trouble:_ If alarms are retransmitted to public fire service communications centers or others,indicate location and telephone numbers of the organization receiving alarm: _ Indicate how alarm is retransmitted: i( NFPA 72,Chapter 8--Central Station Prime contractor: M e r rp A I 4 c'\ Central station location: la 5 4' C eel 1.r 4 ( (i. Pv l (NFPA 72,1 of 4) 12'.Edition 72-32 NATIONAL,FIRE ALARM CODE Means of transmission of signals from the protected premises to the central station: McCulloh Multiplex One-way radio X Digital alarm communicator Two-way radio Others Means of Mylannissian of alarms to the public fire service communications center: (a) lcurjG P4Fn4 Lrn GJ' (b) System loation: T Y�,!r q f/y _ _NFPA 72,Chapter 9—Auxiliary Indicate type of connection: Local energy _ ,_Shunt Parallel telephone Location of telephone number for receipt of signals: 2.Record of System Installation (Fill out after installation is complete and wiring is checked for opens,shorts,ground faults,and improper branching, but prior to conducting operational acceptance tests.) This system h§s been installed in accordance with the NFPA standards as s o below,was inspected by B, ` ole y in 5 and 6,and has been in service since tl iii D-� ,includes the devices shown le_NFPA 72,Chapters 1 2 3 4 5 6 7 8 9 10 11 (circle all that apply) ._ NFPA 70,National Electrical Code,Article 760 Manufacturer's instructions ..._—Other(specify):__/� Date: J Signed: . ' i/n/467 -� OrganizatioT. be ! 6, ! 3.Record of System Operation Documentation in accordance with Inspection Testing Form,Figure 10.6.2.3,i,attached All operational features and functions of this system were tested by f?, 2 o )- 1 G e' }/ date 6/. 13/1/ r and found to be operating properly in accordance with the requirements of: ._-y.NFPA 72,Chapters 1 2 9 4 5 6 7 8 9 IO l 1 (circle all that apply) __1.NFPA 70,National Electrical Code,Article 760 . P Manufacturer's instructions _____Other(specify):. Signed:__.. < _ . —., __ Date: 11-31.0 �1 Organizat' — _01 h1 11-— 4.Signaling Line Circuits Quantity and class of signaling line circuits connected to system(see NFPA 72,Table 6.6.1): Quantity:_,___L___,_ Style: __., Class: '— (NFPA72,2of4) FIGURE 4.5.2.1 Continued 2002 Edition FUNDAMENTALS OF FIRE ALARM SYSTEMS 72-33 5.Alarm-Initiating Devices and Circuits Quantity and class f initiating device circuits(see NFPA 72,Table 6.5): Quantity: Style: - Class: MANUAL (a)Manual stations Noncoded 5 TransmittersCoded Addressable L" (b)Combination manual fire alarm and guard's tour coded stations AUTOMATIC Coverage: Complete Partial x Selective Nonrequired (a)Smoke detectors Ion d Photo _ Addressable _17 b)Duct detectors Ion Photo _ Addressable (c)Heat detectors FI' RR FT/RR RC Addressable (d)Sprinkler waterflow indicators: Transmitters___ Noncoded )" Coded Addressable 6„„.-- (e)The alarm verification feature is disabled_ or enabled X ,changed from seconds to seconds. (f)Other(list): 6.Supervisory Signal-Initiating Devices and Circuits(use blanks to indicate quantity of devices) GUARD'S TOUR (a) Coded stations (b) Noncoded stations (c) Compulsory guard's tour system comprised of _ transmitter stations and intermediate stations Note:Combination devices are recorded under 5(b),Manual,and 6(a).Guard's Tour. SPRINKLER SYSTEM Check if provided (a) _Valve supervisory switches (b) Building temperature points (c)_____._.,Site water temperature points (d)____Site water supply level points Electric fire pump: (e) Fire pump power (f) Fire pump running (g). Phase reversal Engine-driven fire pump: (h) Selector in auto position (i) Engine or control panel trouble (j)._..Fire pump running ENGINE-DRIVEN GENERATOR: (a)___.._.Selector in auto position (h) Control panel trouble (c) Transfer switches (d) Engine running Other supervisory function(s)(specify): (NFPA 72,3of4) FIGURE 4.5.2.1 Continued 2002 Edition 72-34 NATIONAL.FIRE ALARM CODE 7.Annunciators) Number: Type: Location: 8,Alarm Notification Appliances and Circuits NFPA 72,Chapter 6 Emergency Voice/Alarm Service Quantity of voice/alarm channels: Single: Multiple: Quantity of speakers installed: Quantity of speaker zones: Quantity of telephones or telephone jacks included in system: Quantity and the class of notification appliance circuits connected to system(see NFP.72,Table 6.7): Quantity: -)"'" Style: Class: Types and quantities of notification appliances installed: (a) Bells With Visible_ (h) Speakers With Visible (c) Horns 5 With Visible 5- (d)Chimes With Visible (e) Other:_ With Visible (fl Visible appliances without audible: 9.System Power Supplies (a)Fire Alarm Control Panel: Nominal voltage: --...- Current rating: Overcurrent protection: Type: C,'re s i t r-t w 4' Current rating 4_621/Location: te_i• E rrr _C i reP• r 9-et (b) Secondary(standby): Storage battery: Amp-hour rating:. 7 Calculated capacity to drive system,in hours: Engine-driven generator dedicated to fire alarm system: Location of fuel storage: (c) Emergency system used as backup to primary power supply: Emergency system described in NFPA 70,Article 700: 10.Comments Frequency of routine tests and inspections,if other than in accordance with the referenced NFPA standard(s): System deviations from the referenced NFPA standard(s)are:.. p (s' }for installationTic A 7't contract liar (title) (dale) / 0A 9 (signed)for alarm service company (title) (date) (signed)for central :tion (title) (date) / ,lif f .4,,r eti of the: =. . (a)satisfactory test(s) tjsed(if resuieed by the authority having jurisdi 'on): .:ziedig ii (sign having Jurisdiction rep :-ntaiive of the authority v ev) 05 (title) ( V (NFPA 72,4 of 4) FIGURE 4.5.2.1 Continued 2002 Edition #c li64 4646 Dakota Street Southeast V Prior Lake,MN 55372 May 6, 2009 Mr. Seth A. Peterson Bolton& Menk, Inc. 12224 Nicollet Ave. Burnsville, MN 55337 RE: WTF fire alarm correction items Dear Seth, The following are addressing fire alarm items from the March 31, 2009 Water Treatment Facility Final Correction List. Added are the Code sections that address the requirement. The section numbers are from the 2007 Minnesota State Building Code (MSBC) which adopted with amendments the 2006 International Building Code (IBC) also requirements of the 2007 Minnesota State Fire Code (MSFC), which adopted with amendments the 2006 Fire Code (IFC). 1. Add manual alarm-initiating device for the chemical room locate outside corridor at chemical room door 109B. MSFC 2704.9. 2. Add manual alarm-initiating device for the generator room in garage at generator room door 104B MSFC 2704.9. 3. Add horn/strobe outside corridor at chemical room by door 109B and between fluoride room. MSFC 2704.9. 4. Add horn/strobe in garage at generator room door 104B. MSFC 2704.9. 5. Add exit light above door 104B in generator room. MSBC 1011.1. 6. Add a smoke detector in the chemical room. IFC 4004.1.7. 7. Provide continuous ventilation in chemical and fluoride rooms or provide an alternate design. IFC 2704.3. 8. Provide a manual emergency shutoff valves and controls for the remotely activated emergency shutoff valves, identify and the location shall be clearly visible, accessible and indicated by means of a sign for the piping systems in the chemical and fluoride rooms . IFC 2703.2.2.1 #4. 9. Add ventilation manual shut off outside corridor at chemical room and outside exterior door in fluoride room. Switch shall be a break glass type and labeled"VENTILATION SYSTEM EMERGENCY SHUTOFF". IFC 2703.1 #4. www.cityofpriorlake.com Phone 952.447.4230 / Fax 952.447.4263 10.As per memorandum to Seth Peterson from Wentz Associates dated June 4, 2008,provide the generator room ventilation system with a programmable time clock and interlock for a complete air change once an hour. 10. Provide a fire alarm test to prove above items #1, 2, 3, 4 and 6. Also prove items #7, 8 and 9. Also during the WTF fire alarm test on March 31, 2009, it was brought to my attention that the 411UDAC Fire Alarm Communicator panel that was installed as per specification manual 15330 part 2.3 is not UL labeled as a Fire alarm Control Panel. I spoke with technical support person Jacob (1-800- 627-3473) of Fire-Lite Alarms by Honeywell, manufacturer of the panel and he stated that this panel is not UL listed as a Fire Alarm Control panel which the Fire Code requires. It is used for communication between panels, it functions as a fire alarm control panel but it is not UL listed as one. He indicated that Fire-Lite does make a product that is 5 zone 12 volt systems and is UL listed as a fire alarm control panel. Also in looking in NFPA 72 the National Fire Alarm Code, states that flow switches, supervisory/tamper switches, pull stations, smoke detectors and low air supervisory switches must have separate zones in a fire alarm panel, thus any of the 12 volt UL listed fire alarm panels that provide 4 zones would not be Code acceptable in the building project. The fire alarm control panel would require 5 separate zones. An addressable system is not required for this installation. With the above information, the communicator panel that is installed in the water treatment facility is not acceptable and must be removed and replaced with an approved fire alarm panel. See IBC 907.1.2 which states: Systems and their components shall be listed and approved for the purpose for which they are installed. The fire alarm system is required to have a final test completed before final occupancy. I have also discussed the above information with installer Dale of J. Becker & Associates, the panel and device installation contractor. In addition final inspection items from the March 31, 2009 Water Treatment Facility Final Correction List that was addressed at our April 2 meeting remains to be completed. Questions, please call me at 952-447-9851. Sincerely, Robert D. Hutchins Building Official Fire sprinkler alarm NFPA13 section 6.1.1 Materials or devices not specifically designated in this standard shall be used in accordance with all conditions and limitations and requirements of there special listings. NFPA 13 section 8.16.1.1 Local water flow alarm shall be provided on all sprinkler systems with more than 20 sprinkler heads. IBC 907.1.1 Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not limited to all of the following: 1. Floor plan which indicates the use of the room. 2. Location of alarm-initiating and notification appliance 3. Alarm control and trouble singling equipment 4. Annunciation 5. Battery calculations 6. Conductor type and size 7. Power connections. 8. Voltage drop 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. IBC 907.1.2 Systems and their components shall be listed and approved for the purpose for which they are installed. Chemical Room: 1. Chimerical Room requires automatic smoke detection due to the presence of oxidizers per MSFC section 4004.1.6 Installed in the chemical room per listing. 2. Manual fire alarm required for H occupancy MSBC 901.6.3 3. Manual emergency local alarm(Pull station) required out side any interior exit MSDC 2704.9. To be located in the corridor next to the interior exit. 4. Local alarm required to inform occupants of an emergency situation per MSFC 2794.9. To be located in the corridor near the interior exit. Fluoride Room: 1. No additional requirements Generator Room: 1. Exit signs per MSBC 1011.1 Lighted exit signs are required at all required exit doors Generator room continued 2.Manual emergency alarm(pull station) located outside interior exit per MSFC 2704.9 3. Local alarm located near interior exit door on garage side. Per MSFC 2704.9 HAZARDOUS MATERIALS—GENERAL PROVISIONS ,a. 2704.2.3 Containment pallets. When used as an alterna- 2704.5 Automatic sprinkler systems. Indoor storage areas � , tive to spill control and secondary containment for outdoor and storage buildings shall be equipped throughout with an .> storage in accordance with the exception in Section 2704.2, approved automatic sprinkler system in accordance with Sec- ir containment pallets shall comply with all of the following: tion 903.3.1.1.The design of the sprinkler system shall not be 1. A liquid tight sump accessible for visual inspection less than that required for Ordinary Hazard Group 2 with a min- .''',; shall be provided. imum design area of 3,000 square feet (279 m2). Where the ti materials or storage arrangement are required by other regula- F, ,, 2. The sump shall be designed to contain not less than 66 tions to be provided with a higher level of sprinkler system pro- 4 gallons(250 L). tection,the higher level of sprinkler system protection shall be 3. Exposed surfaces shall be compatible with material provided. -, stored. 2704.6 Explosion control. Indoor storage rooms, areas and 4. Containment pallets shall be protected to prevent col- buildings shall be provided with explosion control in accor- lection of rainwater within the sump. dance with Section 911. *Ntt, 2704.3 Ventilation.Indoor storage areas and storage buildings 2704.7 Standby or emergency power. Where mechanical If shall be provided with mechanical exhaust ventilation or natu- ventilation, treatment systems, temperature control, alarm, ;; ral ventilation where natural ventilation can be shown to be detection or other electrically operated systems are required, acceptable for the materials as stored. such systems shall be provided with an emergency or standby ",k1 Exception: Storage areas for flammable solids complying power system in accordance with the ICC Electrical Code and with Chapter 36. Section 604. 2704.3.1 System requirements. Exhaust ventilation sys- Exceptions: tems shall comply with all of the following: 1. Storage areas for Class 1 and 2 oxidizers. 1. Installation shall be in accordance with the Interna 2. Storage areas for Class III,IV and V organic perox- tional Mechanical Code. 5 ides. , v 2. Mechanical ventilation shall be at a rate of not less 3. For storage areas for highly toxic or toxic materials, than 1 cubic foot per minute per square foot , , see Sections 3704.2.2.8 and 3704.3.2.6. k [0.00508 m3/(s • m2)] of floor area over the storage 5 area. 4. Standby power for mechanical ventilation,treatment ' 3. Systems shall operate continuously unless alternative systems and temperature control systems shall not be designs are approved. required where an approved fail-safe engineered sys- tem is installed. T k 4. A manual shutoff control shall be provided outside of the room in a position adjacent to the access door to 2704.8 Limit controls. Limit controls shall be provided in the room or in an approved location.The switch shall accordance with Sections 2704.8.1 and 2704.8.2. be a break-glass or other approved type and shall be 2704.8.1 Temperature control.Materials that must be kept labeled: VENTILATION SYSTEM EMERGENCY at temperatures other than normal ambient temperatures to SHUTOFF. prevent a hazardous reaction shall be provided with an 5. Exhaust ventilation shall be designed to consider the approved means to maintain the temperature within a safe density of the potential fumes or vapors released.For range. Redundant temperature control equipment that will fumes or vapors that are heavier than air,exhaust shall operate on failure of the primary temperature control system be taken from a point within 12 inches(305 mm)of shall be provided.Where approved,alternative means that the floor.For fumes or vapors that are lighter than air, prevent a hazardous reaction are allowed. exhaust shall be taken from a point within 12 inches 2704.8.2 Pressure control.Stationary tanks and equipment (305 mm)of the highest point of the room. containing hazardous material liquids that can generate 6. The location of both the exhaust and inlet air openings pressures exceeding design limits because of exposure fires shall be designed to provide air movement across all or internal reaction,shall have some form of construction or portions of the floor or room to prevent the accumula- other approved means that will relieve excessive internal tion of vapors. pressure. The means of pressure relief shall vent to an 7. Exhaust air shall not be recirculated to occupied areas approved location or to an exhaust scrubber or treatment if the materials stored are capable of emitting hazard-. system where required by Chapter 37. ous vapors and contaminants have not been removed. 2704.9 Emergency alarm. An approved manual emergency Air contaminated with explosive or flammable alarm system shall be provided in buildings, rooms or areas vapors, fumes or dusts; flammable, highly toxic or toxic gases; or radioactive materials shall not be used for storage of hazardous materials.Emergency alarm-ini- tiating larm itu-tiating devices shall be installed outside of each interior exit or, recirculated. exit access door of storage buildings,rooms or areas.Acfiva 2704.4 Separation of incompatible hazardous materials. 'tion o£.an.emergency alarm initiating device shall sound a locat.: Incompatible materials shall be separated in accordance with alarm to alert occupants of an emergency situation involving,, Section 2703.9.8. hazardous materials. ;t. 2006 INTERNATIONAL FIRE CODE® 257 ' r CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 an appr• ed superv,sing station in accordance with Section GENERAL 907.14. 901.1 Scope.The provisions of this chapter shall specify where Excep Vons: fire protection systems are required and shall apply to the 1. S ng -- and multiple-station smoke alarms design,installation and operation of fire protection systems. re k, 'red by Section 907.2.10. 901.2 Fire protection systems.Fire protection systems shall 2. S '•ke detectors in Group I-3 occupancies. be installed,repaired,operated and maintained in accordance 3. :upi isory service is not required for automatic with this code and the International Fire Code. spri er systems in one- and two-family dwell- Any fire protection system for which an exception or reduc- ings. tion to the provisions of this code has been granted shall be con- 901.6.3 Group H.Manual fire alarm,automatic fire-extin- sidered to be a required system. guishing and emergency alarm systems in Group H occu- Exception: Any fire protection system or portion thereof pancies shall be monitored by an approved supervising not required by this code shall be permitted to be installed station. for partial or complete protection provided that such system meets the requirements of this code. Exception: When approved by the building official, on-site monitoring at a constantly attended location shall ,'; Vit 901.3 Modifications.No person shall remove or modify any be permitted provided that notifications to the fire £ fire protection system installed or maintained under the provi- department will be equal to those provided by an sions of this code or the International Fire Code without approved supervising station. approval by the building official. 901.7 Fire areas. Where buildings, or portions thereof, are ,f 901.4 Threads.Threads provided for fire department connec- divided into fire areas so as not to exceed the limits established tions to sprinkler systems, standpipes, yard hydrants or any for requiring a fire protection system in accordance with this other fire hose connection shall be compatible with the connec- chapter,such fire areas shall be separated by fire barriers hav- ', tions used by the local fire department. ing a fire-resistance rating of not less than that determined in accordance with Section 706.3.9. ' $_ 901.5 Acceptance tests.Fire protection systems shall be tested `;; in accordance with the requirements of this code and the Inter- national Fire Code. When required, the tests shall be con- SECTION 902 ducted in the presence of the building official.Tests required by DEFINITIONS this code,the International Fire Code and the standards listed 902.1 Definitions.The following words and terms shall,for the in this code shall be conducted at the expense of the owner or ! ~. the owner's representative.It shall be unlawful to occupyor purposes of this chapter, and as used elsewhere in this code, ? P P have the meanings shown herein. f tions of a structure until the required fire protection systems !L within that portion of the structure have been tested and [F]ALARM NOTIFICATION APPLIANCE.A fire alarm ;- approved. system component such as a bell, horn, speaker, light or text display that provides audible,tactile or visible outputs,or any 901.6 Supervisory service. Where required, fire protection combination thereof. systems shall be monitored by an approved supervising station ` in accordance with NFPA 72. [F] ALARM SIGNAL. A signal indicating an emergency requiring immediate action,such as a signal indicative of fire. 901.6.1 Automatic sprinkler systems. Automatic sprin- kler systems shall be monitored by an approved supervising [F] ALARM VERIFICATION FEATURE. A feature of station. automatic fire detection and alarm systems to reduce unwanted alarms wherein smoke detectors report alarm conditions for a Exceptions: minimum period of time,or confirm alarm conditions within a 1. A supervising station is not required for automatic given time period,after being automatically reset,in order to be sprinkler systems protecting one-and two-family accepted as a valid alarm-initiation signal. �; dwellings. ,> [F]ANNUNCIATOR.A unit containing one or more indica- 2. Limited area systems serving fewer than 20 sprin- tor lamps,alphanumeric displays or other equivalent means in klers. which each indication provides status information about a cir- ;� 901.6.2 i e alarm systems.Fire alarm systems required cuit,condition or location. bythe r isions of Section 907.2 of this code and Section � P [F]AUDIBLE ALARM NOTIFICATION APPLIANCE.A 907.2 o th International Fire Code shall be monitored by notification appliance that alerts by the sense of hearing. 2006 INTERNATIONAL BUILDING CODE® 171 OXIDIZERS 4003.1.1.2 Class 3 liquid and solid oxidizers.A maxi- 4004.1.3 Explosion control. Indoor storage rooms, areas mum of 200 pounds(91 kg)of solid or 20 gallons(76 L) and buildings containing Class 4 liquid or solid oxidizers of liquid Class 3 oxidizer is allowed in Group I occupan- shall be provided with explosion control in accordance with cies when such materials are necessary for maintenance Section 911. purposes or operation of equipment.The oxidizers shall .and in an approved 4004.1.4 Automatic sprinkler system. The automatic be stored in approved containers manner. sprinkler system shall be designed in accordance with 4003.1.1.3 Oxidizing gases. Except for cylinders not NFPA 430. exceeding a capacity of 250 cubic feet(7 m3)each used 4004.1.5 Liquid-tight floor. In addition to Section for maintenance purposes, patient care or operation of 2704.12,floors of storage areas for liquid and solid oxidiz- equipment,oxidizing gases shall not be stored or used in ers shall be of liquid tight construction. Group A,B,E,I or R occupancies. TABLE 4004.1.2 The aggregate quantities of gases used for mainte- OXIDIZER LIQUIDS AND SOLIDS—DISTANCE FROM DETACHED BUILDINGS AND OUTDOOR STORAGE AREAS TO EXPOSURES nance purposes and operation of equipment shall not exceed the maximum allowable quantity per control area MINIMUM DISTANCE TO BUILDINGS, listed in Table 2703.1.1(1). LOT LINES,PUBLIC STREETS, PUBLIC ALLEYS,PUBLIC WAYS OR Medical gas systems and medical gas supply cylinders OXIDIZERCLASSWEIGHT MEANS OF EGRESS (pounds) (feet) shall also be in accordance with Section 3006. 4003.1.2 Emergency shutoff. Compressed gas systems 1 Note a Not Required ' conveying oxidizing gases shall be provided with approved 2 Note a 35 manual or automatic emergency shutoff valves that can be activated at each point of use and at each source. 3 Note a 50 4003.1.2.1 Shutoff at source. A manual or automatic Over 10 to 100 75 fail-safe emergency shutoff valve shall be installed on supply piping at the cylinder or bulk source.Manual or 101 to 500 100 automatic cylinder valves are allowed to be used as the 501 to 1,000 required emergency shutoff valve when the source of 125 supply is limited to unmanifolded cylinder sources. 4 1,001 to 3,000 200 4003.1.2.2 Shutoff at point of use.A manual or auto- 3,001 to 5,000 300 matic emergency shutoff valve shall be installed on the supply piping at the point of use or at a point where the 5,001 to 10,000 400 equipment using the gas is connected to the supply sys- As required by the tern. Over 10,000 fire code official i 4003.1.3 Ignition source control.Ignition sources in areas For SI: 1 foot=304.8 mm,1 pound=0.454 kg. containing oxidizing gases shall be controlled in accor- a. Any quantity over the amount required for detached storage in accordance '4,--,t,. >. ` dance with Section 2703.7. % 1 with Section 2703.8.2,or over the outdoor maximum allowable quantity for 4003.2 Quantities exceeding the maximum allowable quan- outdoor control areas. r tity per control area. The storage and use of oxidizers in 4004.1.6 Smoke detection.An approved supervised smoke detection system in accordance with Section 907 shall be amounts exceeding the maximum allowable quantity per con - installed area indicated in Section 2703.1 shall be in accordance installed in liquid and solid oxidizer storage areas.Activa =s tion of the smoke detection system shall sound a local alarm. with Chapter 27 and this chapter. Exception:Detached storage buildings protected by an SECTION 4004 approved automatic fire-extinguishing system. °, STORAGE 4004.1.7 Storage conditions. The maximum quantity of 4004.1 Indoor storage.Indoor storage of oxidizers in amounts oxidizers per building in detached storage buildings shall not exceed those quantities set forth in Tables 4004.1.7(1) exceeding the maximum allowable quantity per control area indicated in Table 2703.1.1(1)shall be in accordance with Sec- through 4004.1.7(4). tions 2701,2703,2704 and this chapter. The storage configuration for liquid and solid oxidizers 4004.1.1 Detached storage.Storage of liquid and solid ori shall be as set forth in Tables 4004.1.7(1) through dizers shall be in detached buildings when required by Sec- 4004.1.7(4). d tion 2703.8.2. Class 2 oxidizers shall not be stored in basements except 4004.1.2 Distance from detached storage buildings to When such storage is in stationary tanks. exposures.In addition to the requirements of the Interna- Class 3 and 4 oxidizers in amounts exceeding the maxi- 4' tional Building Code, detached storage buildings shall be mum allowable quantity per control area set forth in Section ,', located in accordance with Table 4004.1.2. 2703.1 shall be stored on the ground floor only. 4a, 370 2006 INTERNATIONAL FIRE CODE®,r ' HAZARDOUS MATERIALS—GENERAL PROVISIONS 2704.2.3 Containment pallets.When used as an alterna- 2704.5 Automatic sprinkler systems. Indoor storage areas five to spill control and secondary containment for outdoor and storage buildings shall be equipped throughout with an '•storage in accordance with the exception in Section 2704.2, approved automatic sprinkler system in accordance with Sec- „''containment pallets shall comply with all of the following: tion 903.3.1.1.The design of the sprinkler system shall not be 1. A liquid-tight sump accessible for visual inspection less than that required for Ordinary Hazard Group 2 with a min " shall be provided. imum design area of 3,000 square feet (279 m2). Where the materials or storage arrangement are required by other regula- ` 2. The sump shall be designed to contain not less than 66 tions to be provided with a higher level of sprinkler system pro- gallons(250 L). tection,the higher level of sprinkler system protection shall be } 3. Exposed surfaces shall be compatible with material provided. stored. 2704.6 Explosion control. Indoor storage rooms, areas and : .; 4. Containment pallets shall be protected to prevent col- buildings shall be provided with explosion control in accor- lection of rainwater within the sump. dance with Section 911. 704.3 Ventilation.Indoor storage areas and storage buildings 2704.7 Standby or emergency power. Where mechanical ;'all be provided with mechanical exhaust ventilation or natu- ventilation, treatment systems, temperature control, alarm, ventilation where natural ventilation can be shown to be detection or other electrically operated systems are required, ":cceptable for the materials as stored. such systems shall be provided with an emergency or standby Exception: Storage areas for flammable solids complying power system in accordance with the ICC Electrical Code and with Chapter 36. Section 604. 2704.3.1 System requirements. Exhaust ventilation sys- Exceptions: tems shall comply with all of the following: ,. 1. Storage areas for Class 1 and 2 oxidizers. 1. Installation shall be in accordance with the Internet- 2. Storage areas for Class III,IV and V organic perox- ;" tional Mechanical Code. ides. 2. Mechanical ventilation shall be at a rate of not less than 1 cubic foot per minute per square foot 3. For storage areas for highly toxic or toxic materials, [0.00508 m3/(s • m2)] of floor area over the storage see Sections 3704.2.2.8 and 3704.3.2.6. area. 4. Standby ower for mechanical ventilation,treatment 3. Systems shall operate continuously unless alternative systems and temperature control systems shall not be , designs are approved. required where an approved fail-safe engineered sys- tern is installed. 4. A manual shutoff control-shall be provided outside of the room in a position adjacent to the access door to 2704.8 Limit controls. Limit controls shall be provided in the room or in an approved location.The switch shall accordance with Sections 2704.8.1 and 2704.8.2. I be a break glass or other approved type and shall be 2704.8.1 Temperature control.Materials that must be kept labeled: VENTILATION SYSTEM EMERGENCY at temperatures other than normal ambient temperatures to • $ SHUTOFF. prevent a hazardous reaction shall be provided with an 5. Exhaust ventilation shall be designed to consider the approved means to maintain the temperature within a safe • :•" density of the potential fumes or vapors released.For range. Redundant temperature control equipment that will 4 fumes or vapors that are heavier than air,exhaust shall operate on failure of the primary temperature control system • "" be taken from a point within 12 inches (305 mm)of shall beprovided.Where approved,alternative means that PP ,: the floor.For fumes or vapors that are lighter than air, prevent a hazardous reaction are allowed. exhaust shall be taken from a point within 12 inches :, (305 mm)of the highest point of the room. 2704.8.2 Pressure control.Stationary tanks and equipment containing hazardous material liquids that can generate 6. The location of both the exhaust and inlet air openings pressures exceeding design limits because of exposure fires shall be designed to provide air movement across all or internal reaction,shall have some form of construction or portions of the floor or room to prevent the accumula- other approved means that will relieve excessive internal tion of vapors. pressure. The means of pressure relief shall vent to an 4, " 1 7. Exhaust air shall not be recirculated to occupied areas approved location or to an exhaust scrubber or treatment if the materials stored are capable of emitting hazard-. system where required by Chapter 37. '`" ous vapors and contaminants have not been removed. Air-contaminated with explosive or flammable 2704.9 Emergency alarm. An approved manual emergency vapors, fumes or dusts; flammable, toxic or alarm system shall be provided in buildings, rooms or areas toxic gases; or radioactive materials highly shall not ber used for storage of hazardous materials.Emergency alarm-irii- toxic gases;d. tiating devices shall be installed outside of each interior exit or rexit access door of storage buildings,rooms or areas.A 5'ti a 2704.4 Separation of incompatible hazardous materials. ,qion o,f an..emergency--aiartn=iriittating device shall sound a local Incompatible materials shall be separated in accordance with alarm to alert occupants of an emergency situation involving Section 2703.9.8. hazardous materials. 1 2006 INTERNATIONAL FIRE CODE® 257 PAGE i 1PRIp60, ite N soiIring NE Pink -Planning BUILDING PERMIT APPLICATION DEPARTMENT CHECKLIST ,p NAME OF APPLICANT f�. S , EC4 AN(C ALL APPLICATION RECEIVED ( 1/ I / 0 7 The Building, Engineering, and Planning Departments have reviewed the building permit application for construction activity which is proposed at: n °ATTER- TREK—w�.��r- 1 Co 3'3 S 1 lass A AYE . FAcittTY . Accepted Accepted With Corrections Denied Reviewed By: - Date: /Z//% 7 Comments: L41. T i 4%-e-eG l ,— -4...44.-r.:84...0 & ,t, nu-4..a.t'' .lam . 6...27a.)1 - I x 2 e..1°--4) /6". ja,..6.6.,:, ze,r4:6, _idiot,* 4- fe..., ....,,... e.../1-424-3, .f. I -,^o--e ` TZ. f „..ca1-0 te'`'a e, eor 6 . ( ivt '*e ) *- V-1:1-e.' 141a1-1 pcia--•--4-e--?Z:41-ftu.. -4-2-4-AA4z1' joace ,ag.ratea * I No& D`*a�r�.sL tr � c..s 1..-rcjA1 ... - . ! 3 .3Fu¢.e...c.., 04.4 , e.Ge 2c j) ''/7/5;0600 kiAsp e. '1715.06/0 0.� ` • - sr 0k -•-i''G .a-f-a.-�`_2....--e) . i "The issuance or granting of a permit or approval of plans, specifications and computations shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other ordinance of the jurisdiction. Permits presuming to give authority to violate or cancel the provisions of this code or other ordinances of the jurisdiction shall not be valid." exG. 2- O, PRIp�, �jr U t:f CWVhite -Building\ "Canary 4NNESo�P EngInee1Th Pink Planning BUILDING PERMIT APPLICATION DEPARTMENT CHECKLIST NAME OF APPLICANT . j. 144 e 044 f C frV'-- APPLICATION RECEIVED 11/i /D 7 The Building, Engineering, and Planning Departments have reviewed the building permit application for construction activity which is proposed at: 1A3AT672. d-i4v— /Co 33S /TA-SCA AVS. F;41 . Accepted Accepted With Corrections Denied Reviewed By: -�-�`-- Date: ,Z4a o T Comments: E/ 41L01416-1, A)Z. F¢✓L- Por'ss,cc.� 71*Yz_fr,,vkl 014-r-X.7 I 7D Sys ALL a 77-ferz 77726A s 73 6 6 gitC ,pieo?G=r.7--/ 77964E" 44)/1-73-)2 25'Y ©77r APP/co I/ 6--pt") "The issuance or granting of a permit or approval of plans, specifications and computations shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other ordinance of the jurisdiction. Permits presuming to give authority to violate or cancel the provisions of this code or other ordinances of the jurisdiction shall not be valid." /-!)/4 OI PRio Eft x' 4646 Dakota Street Southeast 1.4 v m Prior Lake,MN 55372 40NN£Sdir January 3, 2008 Mr. Brad Kramer R.J. Mechanical P.O. Box 373 Mora,MN 55051 RE: Plumbing plan review for Water Treatment Facility 16335 Itasca Avenue SE Following are the results of the Plumbing plan review for the Water Treatment Facility building. Our review was based on the Minnesota rules, Chapter 4715 Minnesota State Plumbing Code (MPSC). Including the requirements for the 2007 Minnesota State Building Code (MSBC) which adopted with amendments the 2006 International Building Code (IBC) with handicap regulations of the Minnesota Accessibility Code Chapter 1341. Also requirements of the 2007 Minnesota State Fire Code (MSFC) which adopted with amendments the 2006 International Fire Code (IFC). 1. Mechanical contractor to provide details of penetration fire stopping at rated walls: IBC sections 713 Fire-resistive Joints, 712 Penetrations of plumbing pipes, sprinkler pipes, flues, heating pipes ventilation, exhaust pipes and electrical and communication wires. 2. Potable water backflow prevention; RPZ methods are not allowed at the lawn irrigation service stub, the reclaim tank service stub and the boiler fill lines. Provide details of other approved methods for backflow protection. 1" RPZ for Potassium Permanganate feed system will be allowed. 3. Identify all potable and non potable water lines as required. MSPC 4715.1910. 4. Minnesota Department of Health review letter dated August 1, 2007 corrections shall be addressed and corrected. MDH must have final approval of acceptance before the City of Prior Lake Inspection Department's final inspection of Water Treatment Facility prior to occupancy. www.cityofpriorlake.com Phone 952.447.9800 / Fax 952.447.4263 This review is based on Plumbing plans dated June 25, 2007 that were submitted on November 1, 2007. These above corrections will need to be addressed before this permit can be issued. Questions, please call me at 952-447-9856. Sincerely, Bernie Feidt Plans Examiner/Building Inspector City of Prior Lake 4646 Dakota Street S.E. Prior Lake, Minnesota 55372 952-447-9856 cc. Mr. Seth Peterson, Bolton and Menk, Inc. cc. Thomas Wentz, Bolton and Menk, Inc. (04--"19. AI 4646 Dakota Street Southeast V D n Prior Lake,MN 55372 January 30, 2008 Mr. Seth Peterson Bolton &Menk, Inc. 12224 Nicollet Avenue Burnsville, Minnesota 55337-1649 RE: Backflow prevention for City of Prior Lake Water Treatment Facility 16335 Itasca Avenue SE Dear Seth, After discussing backflow devices at our January 25, 2008 meeting, the City requests that three reduced pressure zone (RPZ) backflow devices be substituted with backflow devices such as an atmospheric vacuum breakers (AVB) or pressure vacuum breakers (PVB). By using devices such as these, the City can reduce the long term maintenance costs of yearly inspections and the mandatory 5 year rebuilding of RPZ's. Also AVB's and PVB's are initially lower in material price than RPZ's. We suggest that the proposed 2" RPZ for the lawn irrigation, 4" RPZ for the reclaim tank wash down lines and 3/4" RPZ for boiler feed be substituted with a 2" AVB for the lawn irrigation, three AVB's for the reclaim wash down and a manual boiler feed with a double-check with intermediate atmospheric vent (DCVIAV) be utilized. The Minnesota State Plumbing Code (MSPC), as stated in 4715.2110 which allows the use of an AVB's and PVB's in these installations. The following are installation requirements for AVB's and PVB's: A.) Atmospheric Vacuum Breaker. (1) Must be installed at least six inches above the spill line (see special requirements in part 4715.2150.) (2) No possibility of back pressure permitted. (3) Only permitted on discharge side of last control valve. (4) No more than 8 hours of continuous line pressure permitted. B.) Pressure Vacuum Breaker. (1) Must be installed at least 12" above spill line. (2) No possibility of back pressure permitted. (3) And continuous line pressure permitted. We understand that a concern of the State of Minnesota Department of Heath, Section of Drinking Water Protection is the substitution of an AVB in lieu of the RPZ providing backflow prevention of the wash down system in the reclaim tank. Because of the cost saving measures mentioned above, the City is suggesting the use of three AVB's to these wash down lines for backflow prevention. We believe that www.cityofpriorlake.com Phone 952.447.9800/Fax 952.447.4263 AVB's in this situation provide adequate backflow prevention because of the amount of redundancy measures built into the design of the tanks. The list of redundancies in this installation is as follows: a.) Backflow device in room #123 is at an elevation of 919.0' with invert elevations of the 2" wash down lines at 908.0', difference in elevation of 11.0' lower than the backflow devices. b.) The pneumatic valve is disengaged/closed until water and sludge levels reach approximately 891.6' elevation. c.) The 3 compartment reclaim tank is not pressurized or air tight and if water levels would reach the overflow elevation of 911.6', it is still 7.4' below backflow devices installed in room#123. In regards to the 1" service line to the Potassium Permanganate feed system, the RPZ installation is required and would remain as proposed. This letter is based on plumbing plans dated June 25, 2007. Please provide supplemental drawings for the above conditions. If you have any questions or ideas that would differ than those suggested above, please call me at 952447-9856. Sincerely, t .Q.� Bernie Feidt Plans Examiner/Building Inspector City of Prior Lake 4646 Dakota Street S.E. Prior Lake, Minnesota 55372 952-447-9856 Email: bfeidt@cityofpriorlake.com CC. Mr. Brian Noma, Minnesota Department of Heath, Section of Drinking Water Protection. Thomas Wentz,Wentz Associates. Steve Albrecht, City of Prior Lake Engineer/Public works Director. Craig Eldred, City of Prior Lake Utilities Supervisor. • • O 4 , U ) ed O� Ol O -d i v N 1.0 5, I` �" n (,) a) CTS C 7 6 N O M bf) cci • '� lam() bI- 1-13 _ x 0 co o N O O O1 RS (n 0 C N .moi ^_ Z +•I Q c)' E U) QS Q A, OO a).' N Ok _C N• 1.1- CO - g 0 ,0 ,- f— ' Q CU O V ti cd Q +, ,...co C/] O N g U O P i • � � IM- (AW M � � Q � a (+A N , N- p CO w LO H W w u) al o ° a cr (.n .c 1) (0 U QA V) >._, J d' o H LAKE •s1 O4 ., r r� a •, w� I 4•LIJ ......, ---- •w."wc,..,.. , a< .u; „iM11MIIM0**Ordta,;, AIOIPIMIIM,,,:.y,,p1100wwr,;..,.m.w SYR v _____ . 4VI ___4__ ______ li ____ ____A_ u ` 4 _ ,, _ . ___,, , - ,, it ' . . . 1 ______ A.,...., ...,, ,„,'. _______ _____ , ,, L.,...„ __ cp PP :, ilk z ts-- 4p1p..—Li.' q 4%1 Abibibh„ r_ Z---- A.__-V___ ti _ 41 I A ,, 0,ii MI ESOTA MI)H i ,:, DO7 tunictrummun Prowling, maintaining and improving the health of all Minnesotans August 1,2007 City of Prior Lake c/o Mr. Frank Boyles,Manager Prior Lake City Hall 16200 Eagle Creek Avenue Southeast Prior Lake, Minnesota 55372-1787 Gentlemen/Ladies: Subject: Prior Lake Water Treatme t Facility, Prior Lake, Scott County,Minnesota, Plan No. 071432 We are enclosing a copy of our report overing an examination of plans and specifications on the above-designated project. it is the pr ject owner's responsibility to retain the plans at the project location. The submitter shall give the owner a set of plans and specifications representative of the completed construction within six months of finished construction. If you have any questions in regard to he information contained in this report, please contact me at 651/201-5180. Sincerely, 0/0‘,_, 11-2-10r Lucas A. Martin Public Health Engineer Section of Drinking Water Protection P.O. Box 64975 St. Paul, Minnesota 55164-0975 LAM:cmp Enclosure cc: Bolton & Menk, Inc. Randy Ellingboe, Minnesota Dep• ment of Labor gn &Industry,Plumbing Unit Bassam Banat, MDH District En 'neer, SOP Gcncral lnformarion: 651.201-5000 • Toll-frcc: 888-345-0823 • n. • 1-201.5797 • www,health.stacc.mn.us An equal opportunity employer 1 Ed WHLV:OT ZOOS 20 •rj TeLt^TOETc9: or'or4 XNd HOW: WOdu MINNESOTA DEPARTMENT OF HEALTH Division of Environmental Health REPORT ON PLANS Plans and specifications on treatment plant(new): Prior Lake Water Treatment Facility,Prior Lake,Scott County, Minnesota,Plan No. 071432 OWNERSHIP: City of Prior Lake,c/o Mr.Frank Boyles,Manager,Prior Lake City Hall, 16200 Eagle Creek Avenue Southeast,Prior Lake,Minnesota 55372-1787 SUBMITTER(S): Bolton&Menk,Inc.,c/o Mr. Seth A.Peterson,P.E., 12224 Nicollet Avenue,Burnsville, Minnesota 55337-1649 Plans Dated: Date Received: June 4,2007 Date Reviewed: July 27, 2007 SCOPE: This report covers the design of this project insofar as the safety and sanitary quality of the water for public consumption may be affected,and applies to this project only and not to the entire system or any other part thereof. The examination of plans is based upon the supposition that the data on which the design is based are correct, and that necessary legal authority has been obtained to construct the project. The responsibility for the design of structural features and the efficiency of equipment must be taken by the project designer. Approval is contingent upon satisfactory disposition of any requirements included with this report. Water supply plans are examined with regard to the location, construction and operational features of the design and maintenance of all parts of the system which may affect the safety and sanitary quality of the water. Examination is based on the standards of this department. This project consists of the construction of a new water treatment plant for the city orprior Lake,Minnesota. The treatment process design includes induced draft aeration,iron and manganese gravity filtration,and chlorine disinfection with sodium hypochlorite,sodium permanganate feed,fluoride feed,and phosphate feed. The filtration stage will consist of six filter beds,each 440 square feet,and will allow for a firm filtration capacity of 6,250 gpm. Other major components of this project include a 200,000 gallon concrete detention basin,a 235,000 gallon concrete clearwell,a 1,289,000 gallon concrete reservoir,a 373,500 gallon concrete backwash reclamation basin, 3 high service pumps each with a capacity of 3,125 gpm,a 6,600 gpm backwash pump,and a 1,500 kW diesel generator. REQUIREMENT(S): TREATMENT PLANT (NEW) 1. Smooth-nosed sample taps shall be installed prior to the sodium permanganate injector,at points between the anthracite and sand filter media, and on the finished water line. 2. The open ends of air release drainpipes shall terminate at least 18 inches above the finished floor. 3. Solution tank overflows shall be screened,turned downward,and have a free fall discharge where the drain terminates at least 6 inches or two pipe diameters above the finished floor,whichever is greater. --~ Ed Wdzt':�T Z©©Z �© '��Q TOt TOETS9: ON Xad HaW: WOdd Prior Lake Water Treatment Facility Treatment Plant(New) Plan No.071432 Page 2 August I,2007 4. The vent for the sodium hypochlorite feed system shall be turned downward and provided with a corrosion resistant screen. 5. Stock phosphate solution must be kept covered and disinfected by carrying approximately 10 ppm free chlorine residual unless the phosphate is not able to support bacterial growth and is being fed from the covered shipping container. Phosphate solutions having a pH of 2,0 or less also may be exempt from this requirement. 6. The fluoride is fed at a rate shall be such that the fluoride level in the finished water is maintained between 0.9 ppm and 1.5 ppm,with the optimum level being 1.2 ppm. • 7. Chemical feed lines shall be easily accessible throughout their entire length. 8. All chemicals being fed shall meet the requirements of NSF standard 60. 9. The project owner shall make sure that if a vacuum truck is used to remove the contents from a treated water tank,or from a backwash reclaim tank,-that the tank truck and the associated pumping/vacuum equipment shall be used only for potable water installations. In addition,the equipment shall be thoroughly disinfected with a chlorine solution of at least 200,ppm before it is used. PLU!M1BING 1. Double wyes may not be used for drainage fittings in the horizontal position(see Minnesota Rules, part 4715.2420, subpart 3). Proper pipe slope cannot be maintained on both of the offset branches. 2. The installation of reduced pressure zone backflow preventers is permitted only when periodic testing is done by a trained backflow preventer tester acceptable to the administrative authority. Testing intervals shall not exceed one year, and records must be kept. All devices must be tested after initial installation to assure that debris from the piping installation has not interfered with the functioning of the device. The devices shall be overhauled at least once every five years. The installation of new backflow preventers must be at least 12 inches,but not more than 6 feet above the finished floor or ground level. COMPLIANCE: No construction shall take place except in accordance with the approved plans. If it is desired to make deviations from the approved plans, the State Department of Health should be consulted and approval of the changes obtained before construction is started;otherwise,such construction is installed without proper approval, and in addition may create dangers to public health. Authorization for construction in accordance with the approved plans may be withdrawn if construction is not undertaken within a period of two years. The fact that the plans have been approved does not necessarily mean that recommendations or requirements for change will not be made at some later time when changed conditions, additional information, or advanced knowledge make improvements necessary. �d WH8t':OT ©Or 'oda TOLPTOETSS: 'ON XH. HQW: L10dd Prior Lake Water Treatment Facility Treatment Plant(New) Plan No.071432 Page 3 August 1, 2007 Approved: Lucas A.Martin Robert H. Smude,P.E. Public Health Engineer Public Health Engineer Section of Drinking Water Protection Section of Drinking Water Protection P.O.Box 64975 P.O.Box 64975 St.Paul,Minnesota 55164-0975 St.Paul,Minnesota 55164-0975 651/201-5180 651/201-4677 • Sd N Bb:01 220E: 20 "oaa rOLt'i0EtS9: '0N Xdd HG4: WOdd ❑ Jennifer Wittkopt City of Prior Lake PROPOSAL 0 Craig Eldred,City of Prior Lake ❑ Bob Hutchins, City of Prior Lake REQUEST 0 Craig Habighorst,Rice Lake Construction. (2 Copies) ❑ Thomas Leonard,Rice Lake Construction ❑ Seth Peterson,Bolton&Menk,Inc. ❑ Kelly Yahnke,Bolton&Menk,Inc. PROJECT: Water Treatment Facility PROPOSAL REQUEST NO: 1 Prior Lake,Minnesota OWNER: City of Prior Lake,Minnesota DATE:December 20,2007 TO:(CONTRACTOR) Rice Lake Construction ENGINEER'S PROJECT NO: M21.38412 22360 Co.Rd. 12 PO Box 517 Deerwood,MN 56444 CONTRACT DATED: August 6,2007 Please submit an itemized quotation for changes in the contract sum and/or Time incidental to proposed modifications to the Contract Documents described herein. THIS IS NOT A CHANGE ORDER NOR A DIRECTION TO PROCEED WITH THE WORK DESCRIBED HEREIN. Description: Provide two(2),6-inch connections to the manhole located west of the garage as shown on the attached figure. The lines arc a continuation of the 6-inch grey water and 6-inch sanitary sewer line exiting the west side of the garage as shown on sheet 6.02. The invert of the lines leaving the building should be 907.00 and the invert at the manhole for both lines shall be 906.50. Attachments: Figure 1 —Revised sheet 2.03 .WtA3(1. ENGINEER: Seth A.Peterson,P.E. DATE: December 20,2007 ❑ Jennifer Wittkopf,City of Prior Lake PROPOSAL 0 Craig Eldred,City of Prior Lake ❑ Bob Hutchins,City of Prior Lake REQUEST 0 Craig Habighorst,Rice Lake Construction. (2 Copies) ❑ Thomas Leonard,Rice Lake Construction ❑ Seth Peterson,Bolton&Menk,Inc. ❑ Kelly Yahnke,Bolton&Menk,Inc. PROJECT: Water Treatment Facility PROPOSAL REQUEST NO: 1 Prior Lake,Minnesota OWNER: City of Prior Lake,Minnesota DATE:December 20,2007 TO:(CONTRACTOR) Rice Lake Construction ENGINEER'S PROJECT NO: M21.38412 22360 Co.Rd. 12 PO Box 517 Deerwood,MN 56444 CONTRACT DATED: August 6,2007 Please submit an itemized quotation for changes in the Contract sun and/or Time incidental to proposed modifications to the Contract Documents described herein. THIS IS NOT A CHANGE ORDER NOR A DIRECTION TO PROCEED WITH THE WORK DESCRIBED HEREIN. Description: Provide two(2),6-inch connections to the manhole located west of the garage as shown on the attached figure. The lines arc a continuation of the 6-inch grey water and 6-inch sanitary sewer line exiting the west side of the garage as shown on sheet 6.02. The invert of the lines leaving the building should be 907.00 and the invert at the manhole for both lines shall be 906.50. Attachments: Figure 1 —Revised sheet 2.03 artil ,imk(i. ENGINEER: Seth A.Peterson,P.E. DATE: December 20,2007 • BO L_TON 8. M N K , I NC_ Consulting Engineers & Surveyors 12224 Nicollet Avenue • Burnsville, MN 55337-1649 Phone (952) 890-0509 • FAX(952) 890-8065 August 22,2007 Mr.Robert D.Hutchins,Building Official City of Prior Lake 4646 Dakota Street SE Prior Lake,MN 55372 Re: Water Treatment Facility Response to Plan Review Comments BMI Project No.M2138412 Dear Mr.Hutchins: Following are our responses to your comments from your letter dated August 20,2007 for the above referenced project. The numbered responses below correspond to the numbered comments from your August 20th letter. Included with my letter is a response letter from David Medin,project Architect. 1 a.The building elevation has been reclassified as two-story as shown in the attached revised sheet 4.01. 1 b and lc.These items will be revisited after receiving the report from Mountain Star Group,Inc. Id.The generator room has been reclassified as H-3 Occupancy as shown on the attached revised sheet 4.01. 1 e.The allowable area is shown on the attached revised sheet 4.01. 2. This item will be revisited after receiving the report from Mountain Star Group,Inc. 5. A certificate of survey is enclosed. 6. A plumbing fixture count is provided on attached revised sheet 4.01. 12.A post indicator valve is now shown on attached revised sheet 2.03. 18.The accessible parking stall has been relocated adjacent to the door. Please reference the attached sheet 2.03 and 2.04. 23.Details 5 and 8 on sheet 4.11 have been revised. Revised sheet 4.11 is attached. 25. The stair riser heights have been modified and are less than 7-inches. Please reference revised sheets 4.06 and 4.18. 27. We have enclosed information on the various concrete block fire ratings. As part of the shop drawing review process,the contractor will submit information on the firestopping used at the various locations. GAI'RLK13841sihi�s���►�sedt u220 O•.dStLEEPY EYE,MN • BURNSVILLE,MN • CHASKA,MN MAIV WILLMAR,MN • RAMSEY,MN • AMES,IA www.bolton-menk.com An Equal Opportunity Employer Mr.Bob Hutchins August 22,2007 Page 2 of 2 If you have any questions or require additional information please do not hesitate to give me a call. Sincerely, .BOLTON&MEW.,`R ARCFI1TECTS PLUS .--" 4/40 i"''"' A Seth A. P.E. G lS Project Manor Vice President Enclosures Architects Plus Letter Revised Sheet 2.03 Revised Sheet 2.04 Revised Sheet 4.01 Revised Sheet 4.06 • Revised Sheet 411 Revised Shed 418 Certificate of Sur + Amcan Block Fire Rist Ratings cc: Steve Albrecht,Director of Public Works(w/out enclosures) y�/'y yy�q� yYyy,. �y ,yam,, �e� AYW i os/1fA 1s11 s- Joa-riAJL.�71.L8k� i ite aWc Water Treatment Facility Final Correction List March 31, 2009 ELECTRICAL(State Electrical Inspector): 1. Generator ground fault field test. 2. Also two well houses and a remote pump which are not included with the WTF permit. . FIRE SUPPRESSION/CONTROL: All marked with asterisk* are included in the Hazardous Materials Technical Opinion Report prepared by Hughes Associates,Inc.dated March 3,2008. 1. Sprinkler Flow fmal• Co w"'`o 0"`t• Monitored/Turn around test. 3. Fire Alarm Test a. Add manual alarm-initiating device outside corridor at chemical room and in garage at generator room. *. b. Add horn/strobe outside corridor at chemical room,fluoride room and in garage at generator room. * � c.tamper switches.* • Aa Loefv F'YV d.Fire Alarm permit submittal. (iV% 4. Fire Dampers Operational • ✓ `7 �''� 5. Exit and Emergency Lighting c, � a. Add exit light above door to garage in generator room:** ' 5‘..4*v(Sem 6. Smoke/Heat Detectors {{''.�,v5 a. Add smoke detector in chem.,`r�oom*• _ f • Ss WI 7. HVAC Duct Detectors... WV 8. PIV operation I'• � Co ���,,ll9. Hydrostatic tests A./1, r fLk? —I10. Prove the manual emergency shutoff valves and controls for the remotff—c9L,t, activated emergency shutoff valves for the piping systems in the chemical.and fluoride rooms.,* HVAC: 1. Ventilation Operational a. Prove ventilation runs continually in chemical and fluoride rooms* b. Add ventilation manual shut off outside corridor at chemical room and outside exterior door in fluoride room. Switch shall be a break glass type and labeled"VENTILATION SYSTEM EMERGENCY SHUTOFF". * from z g ri er4ii error; `, 1 ilation systemto Seth Peterson programm programmable time clock kes dated June 4,and interlock for a 2008, omplete air change once an hour. — catiDA Co tpkorAN.3 ' 2. Final Inspection 3. Balancing Report-may be submitted at a later date. PLUMBING: 1. Bacteria Tests for drinking fountains • 2. Additional correction list from an inspecjion dated December 31,2008.Plumbing contractor is in receipt of corrections list.— C --r" LAS-1 HANDICAP: 1. Signage' • STRUCTURE: 1. Labeled Fire Doors at Gen room; 2. Firestopping in fire Gen and fluoride and chem.rooms N r EXITS: Open and Unobstructed PARKING LOT/CURBS: Handicap Signs - Handicap Access• ENGINEERING DEPARTMENT SIGNS OFF-may be submitted at a later date: As-builts received and approved Utilities tested including bacteria testing Final grade/water conveyance -- COMMUNITY DEVELOPMENT/NATURAL RESOURES DEPARTMENT SIGN OFF-may be submitted at a later date. TEMPORARY CERTIFICATE OF OCCUPANCY- " FINAL CERTIFICATE OF OCCUPANCY o •