HomeMy WebLinkAboutBuilding Permit 02-1062 Fire Protection Plan & Code Plans Fire Sprinkler Plan Review
Date : January 23 , 2006
Owner: City of Prior Lake
Location : 16200 Eagle Creek Ave .
Prior Lake MN. 55372
Contractor : Brothers Fire Protection -
9950 East Hwy. 10
Elk River MN 55330
1 . Separate permits are required for the alarm system.
2 . The 1999 of NFPA 13 shall be the standard.
3 . All materials shall be tested and installed per the listing.
4 . All valves controlling water flow shall be monitored and secured including the PIV .
5 . It is the responsibility of the fire sprinkler contractor to flush all main and branch lines .
6 . Provide frost protection for all portions of the wet system.
7 . Field verify all head locations .
8 . Secure all valves against tampering . All valves in public areas shall be locked
9 . Provide a water resistant system plan at the each sprinkler riser to include the following information.
a. Total site plan
b . All valves
c . Riser locations
d. Areas served by individual risers
e. All main and auxiliary drains
f. Location of inspector ' s test
10 . For inspections call (952) 447 -9850 give the project building permit number (054062)
11 . Seal all penetrations in rated walls in an approved manor.
. 12 . Provide fire protection to areas under overhead doors .