HomeMy WebLinkAboutBuilding Permit 02-1062 Fire Protection Plan & Code Plans Fire Sprinkler Plan Review Date : January 23 , 2006 Owner: City of Prior Lake Location : 16200 Eagle Creek Ave . Prior Lake MN. 55372 Contractor : Brothers Fire Protection - 9950 East Hwy. 10 Elk River MN 55330 1 . Separate permits are required for the alarm system. 2 . The 1999 of NFPA 13 shall be the standard. 3 . All materials shall be tested and installed per the listing. 4 . All valves controlling water flow shall be monitored and secured including the PIV . 5 . It is the responsibility of the fire sprinkler contractor to flush all main and branch lines . 6 . Provide frost protection for all portions of the wet system. 7 . Field verify all head locations . 8 . Secure all valves against tampering . All valves in public areas shall be locked 9 . Provide a water resistant system plan at the each sprinkler riser to include the following information. a. Total site plan b . All valves c . Riser locations d. Areas served by individual risers e. All main and auxiliary drains f. Location of inspector ' s test 10 . For inspections call (952) 447 -9850 give the project building permit number (054062) 11 . Seal all penetrations in rated walls in an approved manor. . 12 . Provide fire protection to areas under overhead doors .