Loading...
HomeMy WebLinkAboutLift Station Standard Policy CITY OF PRIOR LAKE SANITARY SEWER LIFT STATION STANDARDIZATION POLICY APRIL 7, 2003 TABLE OF CONTENTS I. GENERAL........................................................................................................................... 1 IT. LIFT STATION TypES....................................................................................................... 1 ill. ELECTRICAL OPTIONS .......... .......................................................................................... 1 IV . START-UP AND TESTING............................................... ....... .......................................... 2 V. CONSTRUCTION AND CONSTRUCTION DOCUMENTATION.................................. 3 VI. LIFT STATION WARRANTy.......... ........................... ....................................................... 4 VIT. TYPE ONE LIFT STATION................................................. ............................................... 4 Vill. TYPE TWO LIFT STATION........... ...... ........... ........................................................... ...... 14 IX. TYPE THREE LIFT STATION.........................................................................................23 Sheet No.1.................................................................................................................................... .34 Sheet No.2................................................................................................ .................................... .35 Sheet No.3... .............. .............................................. ......... ....... ..... .............................................. ...36 Sheet No.4.................................................................................................................................. ...3 7 Sheet No.5....................................................................................... ............................................ ..3 8 Sheet No.6.................................................................................................................................... .39 F: \ WPWIMl244-08IPrior Lake LS Standard. doc .._"-".__..,"_._-~--"~--- "...~...- -..-...-----...-'--~'>.....,,~~._----.~-___...____...,..__,____~___,....___,.,._______'__m".___ PRIOR LAKE SANITARY SEWER LIFT STATION STANDARDIZATION POLICY April 7, 2003 1. GENERAL To provide for the standardization of all sanitary lift stations in the City, the City of Prior Lake, Minnesota, has adopted the following general standards for the rehabilitation of existing sanitary lift stations and the design and construction of future sanitary lift stations within the City of Prior Lake. The standardization of lift stations within the City will simplify operation and maintenance of the -stations and will reduce the spare parts inventory that will be necessary to keep on hand. In order to provide uniformity and standardization, the City of Prior Lake will obtain the following items for inclusion in the construction of new, and rehabilitation of existing, lift stations: · Pumps · Pump Discharge Elbows · Mini CAS (Control and Status) Monitoring Unit · Pump Controller · SCADA Equipment II. LIFT STATION TYPES The City has defined three different levels of sophistication that may be required for any one lift station installation. The City of Prior Lake shall determine the level of sophistication required for existing and proposed lift stations within the City of Prior Lake, Minnesota. Lift stations with pumps and discharge piping that cannot pass a 3-inch solid will be provided with grinder pumps. III. ELECTRICAL OPTIONS The pump station electrical requirements, available utility voltages, and standby power requirements must be identified prior to completing the lift station electrical design. Page 1 F:\WPWIM1244-08\Prior Lake LS Standard. doc The City will contact the serving electric utility to determine which service voltages are available. Three-phase power is preferred to avoid the use of phase-converters, capacitors, or variable frequency drives used as phase converters. If there are utility charges to provide three-phase service, the City will obtain an estimate of the charges from the serving utility, and prepare a cost comparison between a three- phase installation and a single-phase installation. Preferred three-phase service voltages: · 277 /480V AC, three-phase, four-wire, grounded-wye · 120/240V AC, three-phase, four-wire, delta with grounded center tap · 120/208V AC, three-phase, four-wire, grounded-wye Single-phase voltage: · 120/240V AC, single-phase, three-wire, grounded center tap For stations that require a connection for portable standby power, confirm the City's ability to provide standby power in the required capacity at the desired voltage, using the City's existing portable engine-generator sets. Obtain information from the serving electric utility regarding available fault current at each service voltage. The entire lift station electrical system and control panel shall be designed to withstand the available fault current. The final voltage selection shall be determined by City staff, based on a cost-benefit comparison of available operating voltages. IV. START-UP AND TESTING A factory trained service representative shall be present at the time when the station is to be put into service and turned over to the Owner. The service representative shall instruct the Owner in the proper operation and maintenance of the equipment. The service representative shall provide a minimum of eight (8) hours for field testing and training. At the time of start up, the Contractor shall conduct the necessary pumping test to determine the proper operation of the system. The Contractor shall furnish all meters, equipment and water required for these tests and the tests shall be so conducted as to check the operation of the pumping system. Necessary measurements ofthe electrical consumption shall be made to determine whether or not the pump is operating within the conditions recommended by the pump manufacturer. Perform a witnessed operational test of all equipment. Confirm proper operation of all station features and functions. Page 2 F:\WPWINl1244-08\Prior Lake LS Standard. doc Record phase-to-phase and phase-to-ground voltages during no-load conditions and during all pump operating conditions. Record pump motor phase currents during all pump operating conditions. In the event that the tests show the equipment does not comply with the specifications of the pump manufacturer, this shall be sufficient cause to reject the pump. All tests therein required shall be supervised by the Engineer. No "start ups" shall be scheduled for Fridays. V. CONSTRUCTION AND CONSTRUCTION DOCUMENTATION A. Submittals 1. Shop Drawings: Shop drawings shall be submitted for approval by the Engineer. Submit the following as a minimum for review: · Detailed specifications, dimensions, and weights of pumps, hatches, valves, piping, manholes, and other appurtenances. · Size and model number of pump and motor. · Factory-certified pump curves for the specific pump to be delivered. · Detailed electrical data. · Control drawings and data. · Typical installation guide. · Access hatch drawings. · Technical manuals. · Parts lists. · Operation and maintenance manuals and data. · Printed warranty for pumps and appurtenant equipment. · Motor performance chart including curves for torque, current, power factor, input/output kilowatts, and efficiency. Include data on starting and no load characteristics. · Certified factory performance test curves for each pump provided shall be furnished and approved prior to shipment of the unit to the site. Test curves shall cover the full range of operation from shut off to maximum capacity including head capacity curve, horsepower curve, wire to water efficiency, shut offhead, and recommended operating range. Factory testing of all pump equipment shall be made in accordance with the test code of the Hydraulic Institute Standards. Pumping equipment that fails to meet the specified requirements shall be replaced with pumping equipment that does meet the specified requirements. Page 3 F: IWPWINll244-08IPrior Lake LS Standard. doc B. As-Built Documentation 1. As-builts: · Submit a complete set of drawings, documentation and manufacturer's operation and maintenance instructions for the project. Construction record drawings shall be updated to show "as-built" conditions. · Submit complete electrical schematics showing control panel "as- built" conditions. · Submit complete instrumentation and control "as-built" information including ladder logic. · All drawings shall be submitted in reproducible hard copy format and in electronic format (either AutoCAD .DWG or Adobe .PDF format). VI. LIFT ST A nON WARRANTY The Contractor shall warrant Contractor-supplied lift station components and Contractor's work for twelve (12) months from final completion and written acceptance by the City of Prior Lake. VII. TYPE ONE LIFT STATION A. General A Type One Lift Station is a lift station with a lower level of sophistication. This type lift station will utilize floats for pump control and will be provided with local alarms. Remote communication will not be provided for this type lift station. This type of lift station will be provided with one, two, or three pumps at the City's discretion. Attached, please fmd drawings for two different Type One Lift Stations. Sheet Nos. 1 and 2 are for larger non-grinder pump lift stations. Sheet No.3 is for a smaller grinder pump lift station. Sheet No.4 provides details for both non-grinder and grinder lift stations. B. Wet Well and Valve Manhole 1. Materials of Construction: Main structure shall be reinforced concrete pipe and/or reinforced concrete. All wet well hardware and fasteners shall be stainless steel. Page 4 F:\WPWIN\1244-08\Prior Lake LS Standard. doc 2. Buovancy: Without justification using site specific soils and ground water information, the wet well, wet well base slab, and wet well cover shall be designed to overcome the buoyant forces on the lift station assuming a ground water elevation at the surface, no soil interaction with the structures, and a minimum safety factor of 1.10 based on the dead loads of the concrete structure, excluding all equipment, hatches, piping, etc. 3. Structure Reinforcement: The concrete structure, including base slab and wet well shall be designed and constructed to overcome the pressure associated with minimum and maximum ground water elevations and a structural safety factor which meets current industry standards. The top slab shall be designed to handle AASHO H20 vehicle loads when structure is located away from potential vehicle loads. The top slab shall be designed at a minimum for AASHO H20S loads when the placement of the lift station may allow vehicle loads (the City of Prior Lake shall make a case by case determination of minimum needs. It is the City's intent to not construct lift stations or valve manholes within roadways). 4. Hatch: A heavy duty aluminum access hatch shall be cast into the top slab of the lift station and valve manhole. The hatch assembly shall include a recessed padlock locking device, flush steel drop handle which does not protrude above the cover and an automatic hold open arm with vinyl grip on release handle and a stainless steel cable holder bracket (a cable holder bracket will not be necessary on the hatch for the separate valve manhole). Hatches will be equipped with a compression spring assist so that cover will require no more than 30 pounds of force to open using lifting handle. Hatches will have a removable "T" handle operated slam lock system with a slam lock plug. A thick coat ofbitumastic coal-tar epoxy shall be applied to the exterior of the hatch frame that will be in contact with the concrete. The hatches shall be sized to allow removal of the pumps and valves. The hatch or hatches shall provide a clear opening for easy removal of pump or pumps and all equipment, valves and piping to be located in the wet well or valve manhole. A minimum of 2 inches of clearance will be provided between the sides of the pumps and the hatch and a minimum of 6 inches clearance will be provided between the front ofthe pump (side of pump away from guide rails) and the hatch, assuming the pumps are brought straight up through the hatch following the guide rails which are set to meet manufacturer's standards. Hatches in non-traffic areas shall withstand AASHO H20 loads at a minimum. Hatches in traffic areas shall withstand AASHO H20S loads, at a minimum. (The City of Prior Lake shall make a case-by-case determination of minimum needs. It is the City's intent to not construct lift stations or valve manholes within roadways.) A "master" lock shall be provided for each hasp on the access hatches keyed to City of Prior Lake specifications. Page 5 F: IWPWIN\1244-08\Prior Lake LS Standard. doc Each hatch shall be provided with removable safety grating or retractable safety netting. The City shall decide which safety system will be used on a case-by-case basis. 5. Wet Well Size and Dimensions: The wet well dimensions and size shall follow the recommendations of the most recent standards of the Hydraulics Institute. Wet well sizing shall maintain pump cycling at or below 10 starts per hour. The lower portion of the wet well shall be sloped to reduce solids residence times within the station to reduce the potential for odors. The high water alarm elevation shall be at least 6 inches below the invert of the deepest influent pipe. The low water alarm shall be above the pump manufacturer's minimum operating water level, and above the top of the submersible pump and motor unit. Pump and wet well settings, including high water and low water alarms and pump off and on settings, shall be separated by at least 1 foot in elevation. Oversize wet well to accommodate increase in flows should flow increases be likely. Avoid odor production using sloped fillets and adjustable pump on/off elevation settings. Single pump installations should be avoided. Provide a separate valve manhole for 3-inch diameter and larger discharge pIpmg. Wet well dimensions shall promote the use of standard pump sizes wherever possible. Consult the City for a list of standard pump sizes. 6. Valve Manhole Size and Dimensions: Provide a minimum of 9 inches of clear space between the valve manhole structure and flanged or otherwise bolted fittings for ease of construction and repair. Provide adequate space for maintenance personnel to enter the valve vault to repair or replace piping, valves, etc. Page 6 F:\WPWIM1244-08\Prior Lake LS Standard. doc See Drawing No. 1 for additional requirements. C. Discharge Piping 1. Sizing: Discharge piping velocities shall be above 2.5 feet per second and below 10 feet per second. Acceptable discharge piping velocities may be lowered based on life cycle costs calculated by the City. 2. Piping and Fitting Materials: Unless otherwise stated, ductile iron pipe and fittings shall conform to the requirements of ANSI! A WW A C151/A21.51 for 150 pound working pressure with flange or mechanical joints. Flange joints shall conform to ANSI!A WW A CI15/A21.15, drilled in accordance with ANSI B 16.1 Class 125. The weight, class, or nominal thickness shall be shown on each pipe. All buried ductile iron pipe within 20 feet of lift station and valve manhole structure shall be a minimum of Class 53. Mechanical joint fittings shall conform to A WW A C 11 0/ ANSI A21.1 0 rated at 250 psi, or A WW A C 153/ ANSI A21.53 rated at 350 psi. Rubber gaskets shall conform to A WWA C Ill. All ductile iron pipe and fittings shall be lined with cement mortar in accordance with ANSI!A WW A C104/A21A unless otherwise noted. 3. Special Fittings: Flanged coupling adapters shall be Dresser Style 227, Smith Blair 912, or equal. 4. Check Valves: Swing check valves shall be of the outside lever and weight type and meet the material requirements of A WW A C508. Check valves shall have a 316 stainless steel hinge pin. The hinge pin shall operate in bronze or babitte support bearings conforming to ASTM B 16. The seat ring shall be bronze conforming to ASTM B62. Lever arms and disc shall be keyed to the shaft. When there is no flow through the line, the gate shall hang lightly against the seat. The maximum permissible leakage shall be 1 fl. oz. per hour per inch of nominal valve size. Check valves shall be as manufactured by Clow Valve, Golden Anderson, or approved equal. Page 7 F:I WPWIN11244-08\Prior Lake LS Standard. doc 5. Gate Valves: Gate valves four (4) inches and larger shall be resilient seated gate valves conforming to A WW A C509. Allowances shall be made for material thickness associated with ductile iron valves. D. Pumps and Guide Rails 1. Pump Type: Install City-furnished Flygt submersible, non-clog sewage pumps and discharge elbows capable of passing a three-inch diameter solid sphere. If properly sized pumps and piping cannot pass a three-inch diameter solid sphere, install City-furnished Flygt submersible grinder pumps and discharge elbows. 2. Non-Grinder Pump Warranty: The pump manufacturer shall warrant the total non-grinder submersible pumping package for eighteen (18) months from the date of shipment, or for twelve (12) months from the date of written acceptance by the City of Prior Lake, based on whichever date is later. This total pumping package warranty will be a 100% not pro-rated warranty. The total pumping package includes all pump components, including bearings, power cables, etc. The major wear parts such as mechanical seals, impeller, pump housing, wear rings, and ball bearings, are pro-rated on a linear basis over a full five (5) years following the time period stipulated previously in this paragraph. 3. Grinder Pump Warrantv: The pump manufacturer shall warrant the total grinder submersible pumping package for twelve (12) months from the date of shipment, or for twelve (12) months from the date of written acceptance by the City of Prior Lake, based on whichever date is later. This total pumping package warranty will be a 100% not pro-rated warranty. The total pumping package includes all pump components, including bearings, power cables, etc. 4. Pumps and Motors: Pumps shall be centrifugal, non-clog, solids handling, submersible explosion proof wastewater type pumps capable of handling raw unscreened wastewater. The entire pumping unit shall be explosion proof. The pump casing shall have a centerline discharge equipped with an automatic pipe coupling arrangement for ease of installation and piping alignment. The pumps shall automatically connect to the discharge piping when lowered into position. Sealing of the pump to the discharge piping (discharge elbow) shall incorporate a watertight metal-to-metal contact between machined surfaces. The pumps shall be equipped with stainless steel chains long enough and strong enough to raise the pump for removal and inspection. The pumps shall be easily removable by one operator with a portable hoist for inspection or service, requiring no bolts, nuts, or other fasteners to be removed for this purpose, and no need for personnel to Page 8 F:\WPWIMl244-08\Prior Lake LS Standard. doc enter the wet well. No portion of the pump shall bear directly on the sump floor. The pump volute, motor, and seal housing shall be high quality grey cast iron, ASTM A-48, Class 35B. All external mating surfaces shall be machined and Buna N Rubber o-ring sealed. All fasteners exposed to the water shall be 304 stainless steel. The pump impellers shall be double shrouded (non-grinder pumps) or single shrouded (grinder pumps) non-clog type. The impeller shall be dynamically balanced. The impeller shall be A 48 Class 35 B Cast Iron. A wear ring system shall be installed to provide efficient sealing between the volute and impeller. Replaceable metal wear rings shall have a Brinell Hardness of200 or more. The pump shafts shall be AISI Type 431 stainless steel. Pump shaft and motor shaft shall be the same unit. Couplings will not be allowed. The pump bearings shall have a B 1 0 bearing life of a minimum of 50,000 hours. The pump shall be provided with an oil chamber for the shaft sealing system. The drain and inspection plug, with positive anti-leak seal, shall be easily accessible from the outside. The pump shall have an electrode probe mounted in the seal chamber. The probe shall be connected via submersible cable to the motor control center to alarm a seal failure when liquid is sensed, including a light in the control panel to notify the operator of a problem. The pump shall have two mechanical seals mounted in tandem. Each seal shall be held in contact with its own spring. The upper tandem set of seals shall operate in an oil chamber located just below the stator housing. This set shall contain tungsten-carbide rings (for non-grinder pumps) or carbon- ceramic rings (for grinder pumps). This set of seals shall function as an independent secondary barrier between the pumped liquid and the stator housing. The lower of the tandem set of seals shall function as the primary barrier between the pumped liquid and the stator housing. This set of seals shall contain one stationary and one positively driven rotating, corrosion resistant tungsten-carbide ring (for both non-grinder pumps and grinder pumps). The motor stator, rotor and bearings shall be mounted in a sealed submersible housing. The stator windings shall have Class H or better insulation. Motors shall be equipped with thermal overload protection Page 9 F: I WPWIN\1244-08\Prior Lake LS Standard. doc capable of resetting automatically after cool-down. The motors shall also be equipped with a seal leak detection and warning system that will be connected to the motor control center to alarm a seal failure when liquid is sensed, including a light in the control panel to notify the operator of a problem. The pump and motor shall be designed so that they may operate partially or totally submerged in the water. The pump and motor shall be rated for continuous duty. Motors shall be sized so they are not loaded above full-load rating at any point on the impeller operating curve. Operation in the motor "service factor" range is not acceptable. Minimum motor efficiency shall be designated by the City. Motors shall be suitable for City-determined voltages, phases and hertz of operating power at a City-specified maximum rpm. Protect all pumping equipment metal surfaces in contact with pumpage, other than stainless steel or brass, with a factory-applied spray coating of acrylic dispersion zinc phosphate primer with a polyester resin paint finish. The power cable shall be sized according to NEC and lCEA standards and shall be of sufficient length to reach the control panel without any need for splices. The use of junction boxes will require special consideration and written authorization from the City of Prior Lake. The outer jacket of the cable shall be oil resistant chloroprene rubber. The motor and cable shall be capable of continuous submergence underwater without the loss of watertight integrity to a depth of 65 feet. 5. Guide Rails: Lift stations shall be equipped with dual stainless steel guide rails to guide the pump into proper alignment with the discharge elbow. The guide rails shall extend from the discharge elbow to the upper guide holder on the access door. Guide rails shall be of full length single piece construction from the factory. Field welded guide rails shall not be acceptable. Guide rail supports shall be stainless steel. The guide rail diameter and guide rail bracing spacing shall be as recommended by the pump manufacturer. Intermediate guide rail braces shall be stainless steel. Page 10 F: I WPWlMl244-08IPrior Lake LS Standard. doc All piping and bracing inside the wet well structure shall be stainless steel with the exception of the discharge elbows and the ductile iron discharge pIpmg. E. Pump Control 1. Level control shall be accomplished using float switches and a pump controller/alternator. Provide five float switches with the following functions: · High Level Alarm · Start Lag Pump · Start Lead Pump · Stop Both Pumps · Low Level AlarmlRedundant Stop 2. Float switches shall be non-mercury type. Provide intrinsically-safe barrier relays on each float switch circuit. 3. Install City-furnished U.S. Filter Control Systems Model CB2D pump controller/alternator. The front face ofthe pump controller/alternator shall be extended thru the inner doors of the control panel for operator access. F. Motor Starters / Variable Frequency Drives 1. Starters shall be NEMA-style, NEMA-rated for the application. Starters shall have replaceable contacts and solid-state type adjustable overloads that provide NEMA Class 10 protection for submersible pump motors. 2. Approved starter manufacturers: · Allen-Bradley · Square D Company · Cutler- Hammer/Westinghouse · General Electric 3. Where phase conversion equipment is needed to convert single-phase utility power to three-phase power for pump motors, provide variable frequency drives (VFDs) that are rated for single-phase input voltage by the drive manufacturer. When VFDs are used, the control panel shall be oversized to dissipate heat from the VFDs, and the panel shall be located in an area that is not exposed to direct sunlight. 4. Approved VFD manufacturers: Page 11 F:I WPWIN\1244-08IPrior Lake LS Standard. doc · Allen-Bradley · Cutler- Hammer/Westinghouse · ABB G. Permanent Standby Power - (When required) 1. Engine-generator set shall be a diesel-powered unit with four-cycle industrial diesel engine, double-wall base fuel tank, weatherproof housing, silencer, battery, battery charger, alternator, control panel, silencer, and related equipment. 2. Size the engine-generator set for continuous duty at peak flow conditions. Provide fuel storage for 24 hours, minimum operation at continuous peak station flow. Engine generator shall be sized to allow starting both pumps at a duplex lift station and all three pumps at a triplex lift station. 3. Locate the unit on the project site, and provide adequate sound abatement so that the installation complies with Minnesota Pollution Control Agency (MPCA) noise rules. 4. Provide automatic transfer switch in the pump control panel, so that the unit will automatically start and transfer upon loss of utility power, or upon abnormal supply voltage conditions. Acceptable manufacturers: · Automatic Switch Company (ASCD) · General Electric / Zenith 5. Provide generator with an "Emergency Stop" push button located inside the lockable housing. Do not provide generator switch on the outside of the housing. 6. Acceptable permanent standby power generator manufacturers: · Caterpillar · Cummins/Onan H. Portable Standby Power - (When required) 1. Provide Crouse-Hinds connector to match available connectors on the City's existing portable generator sets. Select connector ampacity to match the station service entrance amperage rating. 2. For stations where an existing connector exists, salvage and install the existing connector on the new pump control panel if the connector is ofthe required type. Page 12 F:\WPWIN\1244-08\Prior Lake LS Standard. doc 3. Provide main and standby circuit breakers with circuit breaker manufacturer's "walking-beam interlock" to allow only one breaker to be closed at a time. I. Control Panel 1. Control panel enclosure shall be NEMA Type 3R, constructed of Type 304 or Type 316 stainless steel. The enclosure shall be low-profile, two-door design, with stainless steel hinges, stainless steel three-point latch, and stainless steel vault handle with padlock provisions. Control panel enclosure shall be free-standing type with stainless steel supporting legs and skirting secured with stainless steel tamperproofhardware. 2. Size the enclosure to accept all electrical equipment without overcrowding, and in accordance with UL 508 requirements. 3. The completed panel shall bear UL labels in accordance with Minnesota Board of Electricity requirements. 4. Control panel shall contain a voltage monitoring relay to protect motors from operating during phase failure, phase reversal or undervoltage conditions. For single-phase stations, the voltage monitoring relay shall protect motors from operating during undervoltage conditions. 5. Provide front-panel components as required by equipment, and as indicated on attached Sheet No.5. See attached Sheet No.5 for general control panel layout requirements. J. Outside Communication 1. Provide a 20" wide by 30" high by 10" deep space in the control panel for the addition of SCADA equipment in the future. Communication equipment will not be added at this time. K. Spare Parts 1. A spare parts package shall be provided for each lift station. The spare parts package shall contain the following items: · One set of each, of upper and lower seals. · Spare fuses and lamps, consisting of a minimum of 10% spare each type used, or quantity six (6) of each type used, whichever is greater. Page 13 F:\WPWIM1244-08\Prior Lake LS Standard. doc VIll. TYPE TWO LIFT STATION A. General A Type Two Lift Station is a lift station with a medium level of sophistication. This type lift station will utilize floats for pump control and will be provided with local alarms and simple remote communication. This type of lift station will be provided with one, two, or three pumps at the City's discretion. Attached, please find drawings for two different Type Two Lift Stations. Sheet Nos. 1 and 2 are for a larger non-grinder pump lift station. Sheet No.3 is for a smaller grinder pump lift station. Sheet No.4 provides details for both non-grinder and grinder lift stations. B. Wet Well and Valve Manhole 1. Materials of Construction: Main structure shall be reinforced concrete pipe and/or reinforced concrete. All wet well hardware and fasteners shall be stainless steel. 2. Buovancv: Without justification using site specific soils and ground water information, the wet well, wet well base slab, and wet well cover shall be designed to overcome the buoyant forces on the lift station assuming a ground water elevation at the surface, no soil interaction with the structures, and a minimum safety factor of 1.10 based on the dead loads of the concrete structure, excluding all equipment, hatches, piping, etc. 3. Structure Reinforcement: The concrete structure, including base slab and wet well shall be designed and constructed to overcome the pressure associated with minimum and maximum ground water elevations and a structural safety factor which meets current industry standards. The top slab shall be designed to handle AASHO H20 vehicle loads when structure is located away from potential vehicle loads. The top slab shall be designed at a minimum for AASHO H20S loads when the placement of the lift station may allow vehicle loads. (The City of Prior Lake shall make a case-by-case determination of minimum needs. It is the City's intent to not construct lift stations or valve manholes within roadways.) 4. Hatch: A heavy duty aluminum access hatch shall be cast into the top slab of the lift station and valve manhole. The hatch assembly shall include a recessed padlock locking device, flush steel drop handle which does not protrude above the cover, and an automatic hold open arm with vinyl grip on release handle and a stainless steel cable holder bracket (a cable holder bracket will not be necessary on the hatch for the separate valve manhole). Hatches will be equipped with a compression spring assist so that cover will require no more than 30 pounds of force to open using lifting handle. Hatches will have a removable "T" handle operated slam lock system with Page 14 F: \ WPWIMl244-08\Prior Lake LS Standard. doc _M___.__"+___~____,.._,....._._..._.._,._V'__""""+ "_""""'_'__"_'__~_~__________"_______'_'.__"''''_~__'''__'_'_'__'_~__'__.__._.____." ___~'_._____..____.._..__,____^..._",._ a slam lock plug. A thick coat ofbitumastic coal-tar epoxy shall be applied to the exterior of the hatch frame that will be in contact with the concrete. The hatches shall be sized to allow removal of the pumps and valves. The hatch or hatches shall provide a clear opening for easy removal of pump or pumps and all equipment, valves and piping to be located in the wet well or valve manhole. A minimum of 2 inches of clearance will be provided between the sides of the pumps and the hatch and a minimum of 6 inches clearance will be provided between the front of the pump (side of pump away from guide rails) and the hatch, assuming the pumps are brought straight up through the hatch following the guide rails which are set to meet manufacturer's standards. Hatches in non-traffic areas shall withstand AASHO H20 loads at a minimum. Hatches in traffic areas shall withstand AASHO H20S loads, at a minimum. (The City of Prior Lake shall make a case-by-case determination of minimum needs. It is the City's intent to not construct lift stations or valve manholes within roadways.) A "master" lock shall be provided for each hasp on the access hatches keyed to City of Prior Lake specifications. Each hatch shall be provided with removable safety grating or retractable safety netting. The City shall decide which safety system will be used on a case-by-case basis. 5. Wet Well Size and Dimensions: The wet well dimensions and size shall follow the recommendations ofthe most recent standards of the Hydraulics Institute. Wet well sizing shall maintain pump cycling at or below 10 starts per hour. The lower portion of the wet well shall be sloped to reduce solids residence times within the station to reduce the potential for odors. The high water alarm elevation shall be at least 6 inches below the invert of the deepest influent pipe. The low water alarm shall be above the pump manufacturer's minimum operating water level, and above the top of the submersible pump and motor unit. Pump and wet well settings, including high water and low water alarms and pump off and on settings, shall be separated by at least I foot in elevation. Page 15 F: \ WP WIMI 244-08\Prior Lake LS Standard. doc Oversize wet well to accommodate increase in flows should flow increases be likely. Avoid odor production using sloped fillets and adjustable pump on/off elevation settings. Single pump installations should be avoided. Provide a separate valve manhole for 3-inch diameter and larger discharge plpmg. Wet well dimensions shall promote the use of standard pump sizes wherever possible. Consult the City for a list of standard pump sizes. 6. Valve Manhole Size and Dimensions: Provide a minimum of 9 inches of clear space between the valve manhole structure and flanged or otherwise bolted fittings for ease of construction and repair. Provide adequate space for maintenance personnel to enter the valve vault to repair or replace piping, valves, etc. See Drawing No. I for additional requirements. C. Discharge Piping 1. Sizing: Discharge piping velocities shall be above 2.5 feet per second and below 10 feet per second. Acceptable discharge piping velocities may be lowered based on life cycle costs calculated by the City. 2. Piping and Fitting Materials: Unless otherwise stated, ductile iron pipe and fittings shall conform to the requirements of ANSI! A WW A C1511A21.51 for 150 pound working pressure with flange or mechanical joints. Flange joints shall conform to ANSI! A WW A C 115/ A21.15, drilled in accordance with ANSI B 16.1 Class 125. The weight, class, or nominal thickness shall be shown on each pipe. All buried ductile iron pipe within 20 feet of lift station and valve manhole structure shall be a minimum of Class 53. Mechanical joint fittings shall conform to A WW A ClIO/ANSI A21.10 rated at 250 psi, or A WW A CI53/ANSI A21.53 rated at 350 psi. Rubber gaskets shall conform to A WW A C Ill. All ductile iron pipe and fittings shall be lined with cement mortar in accordance with ANSI! A WW A C 1 04/ A21A unless otherwise noted. Page 16 F: IWPWINl1244-08\Prior Lake LS Standard. doc -~._'--_._---~,~~--"-~~_.~.,-,...._,---_.~_._--~._,-,_...,.,..._"._~-<._,.._-----.._--_...~- 3. Special Fittings: Flanged coupling adapters shall be Dresser Style 227, Smith Blair 912, or equal. 4. Check Valves: Swing check valves shall be of the outside lever and weight type and meet the material requirements of A WW A C508. Check valves shall have a 316 stainless steel hinge pin. The hinge pin shall operate in bronze or babitte support bearings conforming to ASTM B 16. The seat ring shall be bronze conforming to ASTM B62. Lever arms and disc shall be keyed to the shaft. When there is no flow through the line, the gate shall hang lightly against the seat. The maximum permissible leakage shall be 1 fl oz per hour per inch of nominal valve size. Check valves shall be as manufactured by Clow Valve, Golden Anderson, or approved equal. 5. Gate Valves: Gate valves four (4) inches and larger shall be resilient seated gate valves conforming to A WW A C509. Allowances shall be made for material thickness associated with ductile iron valves. D. Pumps and Guide Rails 1. Pump Tvpe: Install City-furnished Flygt submersible, non-clog sewage pumps and discharge elbows capable of passing a three-inch diameter solid sphere. If properly sized pumps and piping cannot pass a three-inch diameter solid sphere, install City-furnished Flygt submersible grinder pumps and discharge elbows. 2. Non-Grinder Pump Warrantv: The pump manufacturer shall warrant the total non-grinder submersible pumping package for eighteen (18) months from the date of shipment, or for twelve (12) months from the date of written acceptance by the City of Prior Lake, based on which date is later. This total pumping package warranty will be a 100% not pro-rated warranty. The total pumping package includes all pump components, including bearings, power cables, etc. The major wear parts such as mechanical seals, impeller, pump housing, wear rings, and ball bearings, are pro-rated on a linear basis over a full five (5) years following the time period stipulated previously in this paragraph. 3. Grinder Pump Warrantv: The pump manufacturer shall warrant the total grinder submersible pumping package for twelve (12) months from the date of shipment, or for twelve (12) months from the date of written Page 17 F:\WPWIM1244-08\Prior Lake LS Standard. doc acceptance by the City of Prior Lake, based on whichever date is later. This total pumping package warranty will be a 100% not pro-rated warranty. The total pumping package includes all pump components, including bearings, power cables, etc. 4. Pumps and Motors: Pumps shall be centrifugal, non-clog, solids handling, submersible explosion proof wastewater type pumps capable of handling raw unscreened wastewater. The entire pumping unit shall be explosion proof. The pump casing shall have a centerline discharge equipped with an automatic pipe coupling arrangement for ease of installation and piping alignment. The pumps shall automatically connect to the discharge piping when lowered into position. Sealing of the pump to the discharge piping (discharge elbow) shall incorporate a watertight metal-to-metal contact between machined surfaces. The pumps shall be equipped with stainless steel chains long enough and strong enough to raise the pump for removal and inspection. The pumps shall be easily removable by one operator with a portable hoist for inspection or service, requiring no bolts, nuts, or other fasteners to be removed for this purpose, and no need for personnel to enter the wet well. No portion of the pump shall bear directly on the sump floor. The pump volute, motor, and seal housing shall be high quality grey cast iron, ASTM A-48, Class 35B. All external mating surfaces shall be machined and Buna N Rubber o-ring sealed. All fasteners exposed to the water shall be 304 stainless steel. The pump impellers shall be double shrouded (non-grinder pumps) or single shrouded (grinder pumps) non-clog type. The impeller shall be dynamically balanced. The impeller shall be A 48 Class 35 B Cast Iron. A wear ring system shall be installed to provide efficient sealing between the volute and impeller. Replaceable metal wear rings shall have a Brinell Hardness of 200 or more. The pump shafts shall be AISI Type 431 stainless steel. Pump shaft and motor shaft shall be the same unit. Couplings will not be allowed. The pump bearings shall have a B 1 0 bearing life of a minimum of 50,000 hours. The pump shall be provided with an oil chamber for the shaft sealing system. The drain and inspection plug, with positive anti-leak seal, shall be easily accessible from the outside. The pump shall have an electrode probe mounted in the seal chamber. The probe shall be connected via submersible cable to the motor control center Page 18 F:\WPWIN\1244-08\Prior Lake LS Standard. doc to alarm a seal failure when liquid is sensed, including a light in the control panel to notify the operator of a problem. The pump shall have two mechanical seals mounted in tandem. Each seal shall be held in contact with its own spring. The upper tandem set of seals shall operate in an oil chamber located just below the stator housing. This set shall contain tungsten-carbide rings (for non-grinder pumps) or carbon- ceramic rings (for grinder pumps). This set of seals shall function as an independent secondary barrier between the pumped liquid and the stator housing. The lower of the tandem set of seals shall function as the primary barrier between the pumped liquid and the stator housing. This set of seals shall contain one stationary and one positively driven rotating, corrosion resistant tungsten-carbide ring (for both non-grinder pumps and grinder pumps). The motor stator, rotor and bearings shall be mounted in a sealed submersible housing. The stator windings shall have Class H or better insulation. Motors shall be equipped with thermal overload protection capable of resetting automatically after cool-down. The motors shall also be equipped with a seal leak detection and warning system that will be connected to the motor control center to alarm a seal failure when liquid is sensed, including a light in the control panel to notify the operator of a problem. The pump and motor shall be designed so that they may operate partially or totally submerged in the water. The pump and motor shall be rated for continuous duty. Motors shall be sized so they are not loaded above full-load rating at any point on the impeller operating curve. Operation in the motor "service factor" range is not acceptable. Minimum motor efficiency shall be designated by the City. Motors shall be suitable for City-determined voltages, phases and hertz of operating power at a City-specified maximum rpm. Protect all pumping equipment metal surfaces in contact with pumpage, other than stainless steel or brass, with a factory-applied spray coating of acrylic dispersion zinc phosphate primer with a polyester resin paint finish. The power cable shall be sized according to NEC and lCEA standards and shall beof sufficient length to reach the control panel without any need for splices. The use of junction boxes will require special consideration and written authorization from the City of Prior Lake. The outer jacket of the cable shall be oil resistant chloroprene rubber. The motor and cable shall Page 19 F:\WPWIM1244-08\Prior Lake LS Standard. doc be capable of continuous submergence underwater without the loss of watertight integrity to a depth of 65 feet. 5. Guide Rails: Lift stations shall be equipped with dual stainless steel guide rails to guide the pump into proper alignment with the discharge elbow. The guide rails shall extend from the discharge elbow to the upper guide holder on the access door. Guide rails shall be of full length single piece construction from the factory. Field welded guide rails shall not be acceptable. Guide rail supports shall be stainless steel. The guide rail diameter and guide rail bracing spacing shall be as recommended by the pump manufacturer. Intermediate guide rail braces shall be stainless steel. All piping and bracing inside the wet well structure shall be stainless steel with the exception of the discharge elbows and the ductile iron discharge pIpmg. E. Pump Control 1. Level control shall be accomplished using float switches and a pump controller/alternator. Provide five float switches with the following functions: · High Level Alarm · Start Lag Pump · Start Lead Pump · Stop Both Pumps · Low Level AlarmlRedundant Stop 2. Float switches shall be non-mercury type. Provide intrinsically-safe barrier relays on each float switch circuit. 3. Install City-furnished U.S. Filter Control Systems Model CB2D pump controller/alternator. The front face of the pump controller/alternator shall be extended through the inner doors of the control panel for operator access. F. Motor Starters / Variable Frequency Drives 1. Starters shall be NEMA-style, NEMA-rated for the application. Starters shall have replaceable contacts and solid-state type adjustable overloads that provide NEMA Class 10 protection for submersible pump motors. Page 20 F:\WPWIM1244-08\Prior Lake LS Standard. doc 2. Approved starter manufacturers: · Allen-Bradley · Square D Company · Cutler- Hammer/Westinghouse · General Electric 3. Where phase conversion equipment is needed to convert single-phase utility power to three-phase power for pump motors, provide variable frequency drives (VFDs) that are rated for single-phase input voltage by the drive manufacturer. When VFDs are used, the control panel shall be oversized to dissipate heat from the VFDs, and the panel shall be located in an area that is not exposed to direct sunlight. 4. Approved VFD manufacturers: · Allen-Bradley · Cutler-Hammer/Westinghouse · ABB G. Permanent Standby Power - (When required) 1. Engine-generator set shall be a diesel-powered unit with four-cycle industrial diesel engine, double-wall base fuel tank, weatherproof housing, silencer, battery, battery charger, alternator, control panel, silencer, and related equipment. 2. Size the engine-generator set for continuous duty at peak flow conditions. Provide fuel storage for 24 hours, minimum operation at continuous peak station flow. Engine generator shall be sized to allow starting both pumps at a duplex lift station and all three pumps at a triplex lift station. 3. Locate the unit on the project site, and provide adequate sound abatement so that the installation complies with Minnesota Pollution Control Agency (MPCA) noise rules. 4. Provide automatic transfer switch in the pump control panel, so that the unit will automatically start and transfer upon loss of utility power, or upon abnormal supply voltage conditions. Acceptable manufacturers: · Automatic Switch Company (ASCD) · General Electric / Zenith Page 21 F:\WPWIM1244-08\Prior Lake LS Standard. doc 5. Provide generator with "Emergency Stop" push button located inside the lockable housing. Do not provide a shutdown switch on the outside of the housing. 6. Acceptable permanent standby power generator manufacturers: · Caterpillar · Cummins/Onan H. Portable Standby Power - (When required) 1. Provide Crouse-Hinds connector to match available connectors on the City's existing portable generator sets. Select connector ampacity to match the station service entrance amperage rating. 2. For stations where an existing connector exists, salvage and install the existing connector on the new pump control panel if the connector is of the required type. 3. Provide main and standby circuit breakers with circuit breaker manufacturer's "walking-beam interlock" to allow only one breaker to be closed at a time. I. Control Panel 1. Control panel enclosure shall be NEMA Type 3R, constructed of Type 304 or Type 316 stainless steel. The enclosure shall be low-profile, two-door design, with stainless steel hinges, stainless steel three-point latch, and stainless steel vault handle with padlock provisions. Control panel enclosure shall be free-standing type with stainless steel supporting legs and skirting secured with stainless steel tamperproofhardware. 2. Size the enclosure to accept all electrical equipment without overcrowding, and in accordance with UL 508 requirements. 3. The completed panel shall bear UL labels in accordance with Minnesota Board of Electricity requirements. 4. Control panel shall contain a voltage monitoring relay to protect motors from operating during phase failure, phase reversal or undervoltage conditions. For single-phase stations, the voltage monitoring relay shall protect motors from operating during undervoltage conditions. 5. Provide front-panel components as required by equipment, and as indicated on attached Sheet No.5. See attached Sheet No.5 for general control panel layout requirements. Page 22 F:\WPWIMJ 244-08\Prior Lake LS Standard. doc J. Outside Communication 1. Provide an 8-channel Sensaphone automatic telephone dialer and standard telephone service to alert operators of station alann conditions. Alann dialer channels shall be wired as follows: a. Channell - Wetwell High Level Alarm b. Channel 2 - Wetwell Low Level Alarm c. Channel 3 - Power Failure / Phase Failure d. Channel 4 - Pump No. 1 Alarm e. Channel 5 - Pump No.2 Alarm f. Channel 6 - Pump No.3 Alarm (if applicable) g. Channel 7 - (Spare) h. Channel 8 - (Spare) 2. Provide a 20" wide by 30" high by 10" deep space in the control panel for the addition of SCADA equipment in the future. The space taken up by the communication device in Item #1 directly above can be a part ofthis space requirement for future SCADA. K. Spare Parts 1. A spare parts package shall be provided for each lift station. The spare parts package shall contain the following items: · One set of each, upper and lower seals. · Spare fuses and lamps, consisting of a minimum of 10% spare each type used, or quantity six (6) of each type used, whichever is greater. IX. TYPE THREE LIFT STATION A. General A Type Three Lift Station is a lift station with a high level of sophistication. This type lift station will utilize a submersible transducer for pump control, with a float switch back-up system, and will be provided with full SCADA outside communication. This type of lift station will be provided with one, two, or three pumps at the City's discretion. Attached, please find drawings for two different Type Three Lift Stations. Sheet Nos. 1 and 2 are for a larger non-grinder pump lift station. Sheet No.3 is for a smaller grinder pump lift station. Sheet No.4 provides details for both non-grinder and grinder lift stations. Page 23 F:\WPWIN\1244-08\Prior Lake LS Standard. doc B. Wet Well and Valve Manhole 1. Materials of Construction: Main structure shall be reinforced concrete pipe arid/or reinforced concrete. All wet well hardware and fasteners shall be stainless steel. 2. Buoyancy: Without justification using site-specific soils and ground water information, the wet well, wet well base slab, and wet well cover shall be designed to overcome the buoyant forces on the lift station assuming a ground water elevation at the surface, no soil interaction with the structures, and a minimum safety factor of 1.10 based on the dead loads of the concrete structure, excluding all equipment, hatches, piping, etc. 3. Structure Reinforcement: The concrete structure, including base slab and wet well, shall be designed and constructed to overcome the pressure associated with minimum and maximum ground water elevations and a structural safety factor which meets current industry standards. The top slab shall be designed to handle AASHO H20 vehicle loads when structure is located away from potential vehicle loads. The top slab shall be designed at a minimum for AASHO H20S loads when the placement of the lift station may allow vehicle loads. (The City of Prior Lake shall make a case-by-case determination of minimum needs. It is the City's intent to not construct lift stations or valve manholes within roadways.) 4. Hatch: A heavy duty aluminum access hatch shall be cast into the top slab of the lift station and valve manhole. The hatch assembly shall include a recessed padlock locking device, flush steel drop handle which does not protrude above the cover and an automatic hold open arm with vinyl grip on release handle and a stainless steel cable holder bracket (a cable holder bracket will not be necessary on the hatch for the separate valve manhole). Hatches will be equipped with a compression spring assist so that cover will require no more than 30 pounds of force to open using lifting handle. Hatches will have a removable "T" handle operated slam lock system with a slam lock plug. A thick coat ofbitumastic coal-tar epoxy shall be applied to the exterior of the hatch frame that will be in contact with the concrete. The hatches shall be sized to allow removal of the pumps and valves. The hatch or hatches shall provide a clear opening for easy removal of pump or pumps and all equipment, valves and piping to be located in the wet well or valve manhole. A minimum of2 inches of clearance will be provided between the sides of the pumps and the hatch and a minimum of 6 inches clearance will be provided between the front ofthe pump (side of pump away from guide rails) and the hatch, assuming the pumps are brought straight up through the hatch following the guide rails which are Page 24 F: \ WP WIM1 244-08\Prior Lake LS Standard. doc set to meet manufacturer's standards. Hatches in non-traffic areas shall withstand AASHO H20 loads at a minimum. Hatches in traffic areas shall withstand AASHO H20S loads, at a minimum. (The City of Prior Lake shall make a case-by-case determination of minimum needs. It is the City's intent to not construct lift stations or valve manholes within roadways.) A "master" lock shall be provided for each hasp on the access hatches keyed to City of Prior Lake specifications. Each hatch shall be provided with removable safety grating or retractable safety netting. The City shall decide which safety system will be used on a case-by-case basis. 5. Wet Well Size and Dimensions: The wet well dimensions and size shall follow the recommendations of the most recent standards of the Hydraulics Institute. Wet well sizing shall maintain pump cycling below 10 starts and stops per hour. The lower portion of the wet well shall be sloped to reduce solids residence times within the station to reduce the potential for odors. The high water alarm elevation shall be at least 6 inches below the invert of the deepest influent pipe. The low water alarm shall be above the pump manufacturer's minimum operating water level, and above the top of the submersible pump and motor unit. Pump and wet well settings, including high water and low water alarms and pump off and on settings, shall be separated by at least 1 foot in elevation. Oversize wet well to accommodate increase in flows should flow increases be likely. Avoid odor production using sloped fillets and adjustable pump on/off elevation settings. Single pump installations should be avoided. Provide a separate valve manhole for 3-inch diameter and larger discharge pIpmg. Wet well dimensions shall promote the use of standard pump sizes whenever possible. Consult the City for a list of standard pump sizes. Page 25 F:\ WPWINI1 244-08\Prior Lake LS Standard. doc 6. Valve Manhole Size and Dimensions: Provide a minimum of 9 inches of clear space between the valve manhole structure and flanged or otherwise bolted fittings for ease of construction and repair. Provide adequate space for maintenance personnel to enter the valve vault to repair or replace piping, valves, etc. See Drawing No.1 for additional requirements. C. Discharge Piping 1. Sizing: Discharge piping velocities shall be above 2.5 feet per second and below 10 feet per second. Acceptable discharge piping velocities may be lowered based on life cycle costs calculated by the City. 2. Piping and Fitting Materials: Unless otherwise stated, ductile iron pipe and fittings shall conform to the requirements of ANSI! A WW A CI51/A21.51 for 150 pound working pressure with flange or mechanical joints. Flange joints shall conform to ANSI! A WW A C 115/ All.15, drilled in accordance with ANSI B 16.1 Class 125. The weight, class, or nominal thickness shall be shown on each pipe. All buried ductile iron pipe within 20 feet of lift station and valve manhole structure shall be a minimum of Class 53. Mechanical joint fittings shall conform to A WW A C 11 0/ ANSI A21.1 0 rated at 250 psi, or A WW A C 153/ ANSI A21.53 rated at 350 psi. Rubber gaskets shall conform to A WW A C 111. All ductile iron pipe and fittings shall be lined with cement mortar in accordance with ANSI! A WW A C 1 04/ AlIA unless otherwise noted. 3. Special Fittings: Flanged coupling adapters shall be Dresser Style 227, Smith Blair 912, or equal. 4. Check Valves: Swing check valves shall be of the outside lever and weight type and meet the material requirements of A WW A C508. Check valves shall have a 316 stainless steel hinge pin. The hinge pin shall operate in bronze or babitte support bearings conforming to ASTM B16. The seat ring shall be bronze confonning to ASTM B62. Lever arms and disc shall be keyed to the shaft. Page 26 F:\WPWIMl244-08\Prior Lake LS Standard. doc When there is no flow through the line, the gate shall hang lightly against the seat. The maximum permissible leakage shall be 1 fl. oz. per hour per inch of nominal valve size. Check valves shall be as manufactured by Clow Valve, Golden Anderson, or approved equal. 5. Gate Valves: Gate valves four (4) inches and larger shall be resilient seated gate valves conforming to A WW A C509. Allowances shall be made for material thickness associated with ductile iron valves. D. Pumps and Guide Rails 1. Pump Type: Install City-furnished Flygt submersible, non-clog sewage pumps and discharge elbows capable of passing a three-inch diameter solid sphere. If properly sized pumps and piping cannot pass a three-inch diameter solid sphere, install City-furnished Flygt submersible grinder pumps and discharge elbows. 2. Non-Grinder Pump Warranty: The pump manufacturer shall warrant the total non-grinder submersible pumping package for eighteen (18) months from the date of shipment, or for twelve (12) months from the date of written acceptance by the City of Prior Lake, based on which date is later. This total pumping package warranty will be a 100% not pro-rated warranty. The total pumping package includes all pump components, including bearings, power cables, etc. The major wear parts such as mechanical seals, impeller, pump housing, wear rings, and ball bearings, are pro-rated on a linear basis over a full five (5) years following the time period stipulated previously in this paragraph. 3. Grinder Pump Warrantv: The pump manufacturer shall warrant the total grinder submersible pumping package for twelve (12) months from the date of shipment, or for twelve (12) months from the date of written acceptance by the City of Prior Lake, based on whichever date is later. This total pumping package warranty will be a 100% not pro-rated warranty. The total pumping package includes all pump components, including bearings, power cables, etc. 4. Pumps and Motors: Pumps shall be centrifugal, non-clog, solids handling, submersible explosion proof wastewater type pumps capable of handling raw unscreened wastewater. The entire pumping unit shall be explosion proof. The pump casing shall have a centerline discharge equipped with an automatic pipe coupling arrangement for ease of installation and piping alignment. The pumps shall automatically connect to the discharge piping Page 27 F: IWPWlMl244-08IPrior Lake LS Standard. doc when lowered into position. Sealing of the pumps to the discharge piping (discharge elbow) shall incorporate a watertight metal-to-metal contact between machined surfaces. The pumps shall be equipped with stainless steel chains long enough and strong enough to raise the pump for removal and inspection. The pumps shall be easily removable by one operator with a portable hoist for inspection or service, requiring no bolts, nuts, or other fasteners to be removed for this purpose, and no need for personnel to enter the wet well. No portion of the pump shall bear directly on the sump floor. The pump volute, motor, and seal housing shall be high quality grey cast iron, ASTM A-48, Class 35B. All external mating surfaces shall be machined and Buna N Rubber o-ring sealed. All fasteners exposed to the water shall be 304 stainless steel. The pump impellers shall be double shrouded (non-grinder pumps) or single shrouded (grinder pumps) non-clog type. The impeller shall be dynamically balanced. The impeller shall be A 48 Class 35 B Cast Iron. A wear ring system shall be installed to provide efficient sealing between the volute and impeller. Replaceable metal wear rings shall have a Brinell Hardness of 200 or more. The pump shafts shall be AISI Type 431 stainless steel. Pump shaft and motor shaft shall be the same unit. Couplings will not be allowed. The pump bearings shall have a B 10 bearing life of a minimum of 50,000 hours. The pump shall be provided with an oil chamber for the shaft sealing system. The drain and inspection plug, with positive anti-leak seal, shall be easily accessible from the outside. The pump shall have an electrode probe mounted in the seal chamber. The probe shall be connected via submersible cable to the motor control center to alarm a seal failure when liquid is sensed, including a light in the control panel to notify the operator of a problem. The pump shall have two mechanical seals mounted in tandem. Each seal shall be held in contact with its own spring. The upper tandem set of seals shall operate in an oil chamber located just below the stator housing. This set shall contain tungsten-carbide rings (for non-grinder pumps) or carbon- ceramic rings (for grinder pumps). This set of seals shall function as an independent secondary barrier between the pumped liquid and the stator housing. The lower of the tandem set of seals shall function as the primary barrier between the pumped liquid and the stator housing. This set of seals Page 28 F:\WPWINlJ 244-08\Prior Lake LS Standard. doc shall contain one stationary and one positively driven rotating, corrosion resistant tungsten-carbide ring (for both non-grinder pumps and grinder pumps). The motor stator, rotor and bearings shall be mounted in a sealed submersible housing. The stator windings shall have Class H or better insulation. Motors shall be equipped with thermal overload protection capable of resetting automatically after cool-down. The motors shall also be equipped with a sea11eak detection and warning system that will be connected to the motor control center to alarm a seal failure when liquid is sensed, including a light in the control panel to notify the operator of a problem. The pump and motor shall be designed so that they may operate partially or totally submerged in the water. The pump and motor shall be rated for continuous duty. Motors shall be sized so they are not loaded above full-load rating at any point on the impeller operating curve. Operation in the motor "service factor" range is not acceptable. Minimum motor efficiency shall be designated by the City. Motors shall be suitable for City-determined voltages, phases and hertz of operating power at a City-specified maximum rpm. Protect all pumping equipment metal surfaces in contact with pumpage, other than stainless steel or brass, with a factory-applied spray coating of acrylic dispersion zinc phosphate primer with a polyester resin paint finish. The power cable shall be sized according to NEC and ICEA standards and shall be of sufficient length to reach the control panel without any need for splices. The use of junction boxes will require special consideration and written authorization from the City of Prior Lake. The outer jacket ofthe cable shall be oil resistant ch10roprene rubber. The motor and cable shall be capable of continuous submergence underwater without the loss of watertight integrity to a depth of 65 feet. 5. Guide Rails: Lift stations shall be equipped with dual stainless steel guide rails to guide the pump into proper alignment with the discharge elbow. The guide rails shall extend from the discharge elbow to the upper guide holder on the access door. Guide rails shall be of full length single piece construction from the factory. Field welded guide rails shall not be acceptable. Page 29 F:\WPWINll244-08\Prior Lake LS Standard. doc Guide rail supports shall be stainless steel. The guide rail diameter and guide rail bracing spacing shall be as recommended by the pump manufacturer. Intermediate guide rail braces shall be stainless steel. All piping and bracing inside the wet well structure shall be stainless steel with the exception of the discharge elbows and the ductile iron discharge plpmg. E. Pump Control 1. Level control shall be accomplished using a submersible pressure/level transducer and solid-state pump controller/alternator. In addition, float switches shall be provided as a backup system to the submersible transducer and solid-state controller. The float switch backup circuitry shall be independent of the primary level control circuitry for redundancy. Provide two float switches with the following functions: · High Level Alarm / Start Pumps · Stop Pumps 2. Float switches shall be non-mercury type. Provide intrinsically-safe barrier relays on each float switch circuit. 3. Install the following City-furnished equipment: · U.S. Filter Control Systems Model D153 pump controller. · U.S. Filter Control Systems Model AIOO submersible pressure/level transducer. · U.S. Filter Control Systems intrinsically-safe barriers. · U.S. Filter Control Systems Model D153 pump controller/alternator. The front face of the pump controller/ alternator shall be extended thru the inner doors of the control panel for operator access. F. Motor Starters / Variable Frequency Drives 1. Starters shall be NEMA-style, NEMA-rated for the application. Starters shall have replaceable contacts and solid-state type adjustable overloads that provide NEMA Class 10 protection for submersible pump motors. 2. Approved starter manufacturers: · Allen- Bradley · Square D Company Page 30 F:\WPWlM1244-08\Prior Lake LS Standard. doc · Cutler-Hammer/Westinghouse · General Electric 3. Where phase conversion equipment is needed to convert single-phase utility power to three-phase power for pump motors, provide variable frequency drives (VFDs) that are rated for single-phase input voltage by the drive manufacturer. When VFDs are used, the control panel shall be oversized to dissipate heat from the VFDs, and the panel shall be located in an area that is not exposed to direct sunlight. 4. Approved VFD manufacturers: · Allen-Bradley · Cutler- Hammer/Westinghouse · ABB G. Permanent Standby Power - (When required) 1. Engine-generator set shall be a diesel-powered unit with four-cycle industrial diesel engine, double-wall base fuel tank, weatherproof housing, silencer, battery, battery charger, alternator, control panel, silencer, and related equipment. 2. Size the engine-generator set for continuous duty at peak flow conditions. Provide fuel storage for 24 hours, minimum operation at continuous peak station flow. Engine generator shall be sized to allow starting both pumps at a duplex lift station and all three pumps at a triplex lift station. 3. Locate the unit on the project site, and provide adequate sound abatement so that the installation complies with Minnesota Pollution Control Agency (MPCA) noise rules. 4. Provide automatic transfer switch in the pump control panel, so that the unit will automatically start and transfer upon loss of utility power, or upon abnormal supply voltage conditions. Acceptable manufacturers: . · Automatic Switch Company (ASCO) · General Electric / Zenith 5. Provide generator with an "Emergency Stop" push button located inside the lockable housing. Do not provide a shutdown switch on the outside of the housing. Page 31 F:\WPWIMI244-08\Prior Lake LS Slandard.doc 6. Acceptable permanent standby power generator manufacturers: · Caterpillar · Cummins/Onan H. Portable Standby Power - (When required) 1. Provide Crouse-Hinds connector to match available connectors on the City's existing portable generator sets. Select connector ampacity to match the station service entrance amperage rating. 2. For stations where an existing connector exists, salvage and install the existing connector on the new pump control panel if the connector is of the required type. 3. Provide main and standby circuit breakers with circuit breaker manufacturer's "walking-beam interlock" to allow only one breaker to be closed at a time. 1. Control Panel 1. Control panel enclosure shall be NEMA Type 3R, constructed of Type 304 or Type 316 stainless steel. The enclosure shall be low-profile, two-door design, with stainless steel hinges, stainless steel three-point latch, and stainless steel vault handle with padlock provisions. Control panel enclosure shall be free-standing type with stainless steel supporting legs and skirting secured with stainless steel tamperproofhardware. 2. Size the enclosure to accept all electrical equipment without overcrowding, and in accordance with UL 508 requirements. 3. The completed panel shall bear UL labels in accordance with Minnesota Board of Electricity requirements. 4. Provide front-panel components as required by equipment, and as indicated on attached Sheet No.6. See attached Sheet No.6 for general control panel layout requirements. J. Outside Communication 1. Outside communication shall be via an expansion of the City's existing SCADA system. SCADA system expansion shall be constructed by System Control Services, Inc., under separate contract directly with the City. 2. SCADA system contact person: Page 32 F: \ WPWlN\1244-08\Prior Lake LS Standard. doc System Control Services, Inc. Attn: Mr. Ron Smith 366 Prior Avenue North - Suite 206 Saint Paul, MN 55104 Phone: 651-647-9955 3. Provide 24" wide by 30" high by 10" deep unobstructed space within the pump control panel for installation of the SCADA equipment by the SCADA equipment supplier. 4. Provide the following signals wired to terminal strips for monitoring by the SCADA system: a. Wetwelllevel (4-20mA analog signal). b. Wetwell High Level Alarm c. Wetwell Low Level Alarm d. Power Failure / Phase Failure e. Pump No. 1 Alarm f. Pump No.2 Alarm g. Pump No.3 Alarm (if applicable) h. Pump No. 1 Running 1. Pump No.2 Running J. Pump No.3 Running (if applicable) k. Control Panel Low Temperature Alarm 1. Control Panel High Temperature Alarm m. Engine-Generator Running (if applicable) n. Engine-Generator Alarm (if applicable) K. Spare Parts 1. A spare parts package shall be provided for each lift station. The spare parts package shall contain the following items: · One set of each, upper and lower seals. · Spare fuses and lamps, consisting of a minimum of 10% spare each type used, or quantity six (6) of each type used, whichever is greater. Page 33 F:\WPWIM1244-08\Prior Lake LS Standard. doc .-_ -=-- u~_ V.LOSaNNIW'IDIV'HIOnId NOUVZIallV<INV~S -- .....=::--==:.:;....:t~ NOLLY.LS.un - ..Iao,. .. ~ ~d ;!~~~~I ~~~i ~ ~ i; ~i ~!~ i.:i~ ~ I il i~ ~~! ~~~~~ i ;;j .~ ~i all Kalil e i ~~i~:~~~ ~:a V 8 i;te55l!!i~ ~Sl!lll!l ;o~ ;~ ~ III~ S:Si ~. S~l:l ~I!! gai~ili .. cii ~~zt3~ ~ ~i~ ~~~I3I~~1f 5 ~~ ! ~i i~ll!i ~ Ji t~~i ~ ~ Z ..: N Pi . ... .a ,.:.. Gi 2 .. . I 'd Q !~. ~ ~ N8 ~~-l ~W ~ ~~ ~ i~ lS~ 8 ~~a ~'ll ~:"f"'L'.r::"_"""""'~"'_"'II....t:.Io3.J.lIr.I.'1. =~: :::=m IfJ :. ..........." tl:tS; Nn '''JOdON''!n 8SM ~:;~D!JOw," 110110 ~lt ~_.. 3: w 5> . ~ ~il ~ I .. ~e ~ii!~ i !i ~. ~o i ! !~ ~ I i~~!= ~Ih ~ ~~ ~ ~i~ ~ ~ i5i~~g !~;III ~ ~ ~ ~"" t; fil ~ ~~:l! Ill' ~ .. mi~ ~ i~: ~ ~il ~Ii~~ ~~~~z i ~~;! [ C~: ~I !li~li !5~~ i ! ~~~ ~ ~; 2!j ~ Ii Udi~ h~~i ~ 8 i~~ ~ ~ iO,. 8S ~~~J 5~~~ I ", ",~h~ 8 ~ J~ ~ ~~ ~~~~~ui:.le g ~18l @ l!ll @ @ @l@ @ @ @J S ~. ~ . III ..~~ ~ ..n ~C8 a a ~~ . t i~ 1 S [ i i e ~~. d!i! ~ ~:!~ 5 ~ 9 ~ I ~ i' ~. lil~ il ~i! i . ~~!l _ ~ ~ III ! ~..~~ ! :~.. ~1Is L I!!! i~ ~ Iii ~ ~ ;g~ ; i ~ ~~ Il~ lS~;t ~ i ~-! .. Ld ~~ii .. i , ~ ~~ !I ~~ @l @ @ @@@ @ @@@@@ @ C8l i! II.! i. , , i ;I~;e~~ ~g ~; ~ ~~ J ~ ..! I ~ Bd lIli Ii i ~. It..!! ~ 1Isl'i ~11~~ia i~ ~I. ~~ ~!~ -!~~ ~ ~ ~ i ~! II (J) eo i l3 .. C1&. li....i!! II!~ L K ~ 'ir.:! ~ ~~I!!I :1: 11tl' ~ It ~; ! ~ ~ ~ ~ r~~:.d~ g~ N ~ i~~ ~~ ~~ I~ ~~ I ~~~ b;i ~ ~ 0 e ee e e e e e @ ~ @ @J ~ -^J ~ ~~ ~~ ~.3 ~e; uo.e Eo - I ;1 e ~ ~ 51 I !&i n~~~Si! an B I ~g Wd S",9n fOOZIll> 'nno"" '5Mp'tlllH+Ztl"'ll1 JO!Jd\J......".".".,IlM\:w t:i lLJ ::I: Vl z o ~ Iil t:: ::J 15 c z ~ I Z o z c ~ ~ ~ ""'-- - ...,.,~- -=- _._....~;M._ Ila-J~~.....'I_,__ ____..............0Jf\fIdW... ....~'IlnI.....UIID.....1 V ~OSmrNIW ':!I)lV'I HOHId NOLLVZlmlVlINVJ.S NOLL V.LS .l.!In OOI.I-IH-A.t: XV" ""'.......... oott-IH-ttl ~ ZZ." Nn'suocloeuum SSM ~~'1D!JOWe" UDSfO OS&t ~-- ....'1.1~1........-...,..~II..'II:.._fll.I.Ut.:lll::l,'11I:1~1. III U ii! .... z z ~ ~ ~ 815 ~ 1 1~ ~ 0: ~ ~~ ~ .r,J 8' ~ S .... z 1= z i3 1I)f5~.ffi ~ !;;: '!:S1~ z ~ :r: moz 0 z ~~: ~~: o .... oi5~ ~';(~ ~i:l~ :I => z :i ~ @@@@~ @ Ii:' e. (J) w b z ~ ~ z o ~ o z w 0.:1 :1:1 =>0 Q.U o::~ C) ;~ ~ ~ ~! i ~ :E~ ~ ~ 0: :;i:i. U to ~~ ~ ~ ~ 8: s ~ n~~~~~~~~ e eeeeeeee 0: I i ~ '" u' I z 0 I J ~ J Gj I I a. I ....J ~ I w ~ I I I I I a:: w 3= ~ 2 I I 0 I I ....J 5 ~ Z I ~ I a. ~ 5 z ~ a. j W W '" u' "'z i>:Q ~~ Q.=>z ~~~ 0. =>0 a:~u w w 0. a: Wd >Z:ZO:ll toolkl> 'IV1OA81 '6Mp'ElIn-"ZII"'flIl JOfJd\lalo_"".,oMI:w N w w J: (/) z o ~ iii t ::J ffi c z ii: C> I z o z c ~ ~ ~ _ ___ - -~ [Q-LD-tO - V.LOSmlNIW 'IDIV'I 1I0nId NOLL VZIOllVONV J.S NOLLVJ.S .I.!II'l -~ ....... _ ...::.: .::n)lll"'::: r:..u:: .... -.... a-.... .... . :II II...... .. 1IIOl.~""""_.....a_1 oj d ~ -' ! ~ W : ~lf~hi !i I: ~:~~ ~ il j~ ;i~:I~~ f!l S;( i~i !l~ j~i ~ 15 ~ ~ aii~ ~Zd~h ~ ~; I~~ ~ ~~~ ..: cot I"i .. iii . 0' Cl.. > 0 I- W I ..J W 3= I w 3= :> w z 5 .... <( Z ..J <( 0... ..J Cl.. ~ ~ 10 ~ ~ og 8 ~g-;/ ~1E~l;! ~oeli I?!i ~I;l"!g ~:1~e ~ l~ .. 'i--J~ ail; " ~ ~ I ~ I ! e n p I~US~~ '_N llill iUhg -.:!I:.a........r::._....I:I&I..I~....-.".I.,.......,..,J..h.'_ I') ~:::::s: ICY.I .... '---, It Ztt" Nn'SllodlMtW!" SSM ~q:::'''1O!-1OW.n UOSlO ~'" ~-- w w ::t Ul ci tl l'i ~ II! ~ 2 ~ if.! ~ 9~ ~ w~ @@) i 5 II ~tl ~ ~ go e;~ 1!1~ l!I~ i : III a~~ ::l;! ;! i li ~i 1lI!l!l'i ~~" ; 0 d is..... i X~ll' ~ ~illl ~. WII!;:i!i lil hit F ;~S ~ ~ :g ~I ~ ~ ~~~ ~ 1<~ !l ~ is;!~ lilli! ~ !l !l !l ~ ~,,~ ~iIi;! ~ : ~~ ~1S ~c ~ ~ ~ ~ ~ 1lI~~ "'~~ '" 8 bli'l 85 ;8 ~ uI uI uI l'i !aa In.....e: III :I ~UIf NU 11I_ $' en 1/1 en ... ...~l5 z o ~ ~ t:: :J f5 o z ii1 ~ o ~ ~ @ @@J@ @ @ @@@J@@@ ~tl ~ ";-1 zoc i!'i ~ w ~::c ~.. i'i ;Il F ... <: I !:liS II"' I:l ~ ~~ ~ ~u~ ~;:i ,.::! ~~ ~ ; j!!"'fl ~ ~~~ il<i! ail! ~ ur", ~ I~I IS ~ca; 1'''' ....~ 6tt;: % Q Uoc ~! ~ ~~! i~ll ~~ ~~ ~! ; ~ iii ~~ ~ i~ i j!;"~ i!!~ 81!l 3til! g ~ ~ ~f!!l!ful ~~ i :t'H lil~lS bhU.~::l ::l ~ ~dij e @CSJ@@ @ @@ @@@@ oe .. a~ i'i ..~ ~8 ::'" II Ii... \.tiKI- '" \l~iS u1~ j!!"zulolSi3 zlS:!~~ u1u 5 l;jPlS iShiiil~~ i'i~~ J:~"'~~I -'uS. !U . W (S...Ic"I-O ~duliSi~j!! !Z ~ :;;d~d "i"~!SI ~lIllSo ~h~ .~ lil iEl~It~.. d~~~ ls'" flz!~ N 0 "G:~~b" j!!1'!.~ eQ~II/i'i ... ~o"u1"l'ie "'i~l!! ~ol!(il~1I '" : ~ ~ ~l!!u1~..~ ~ iil :!~~ IIi:! bI ~ ~ iIi "' I~:i!~~ ~~~! !~i~r~~ ~ ~i i ;i i ~~~::!"~ill U;s i~iI1~~~~ ~ I:!l!!" ..l!I ~ ~lii::l~ne '-~OlS !:!lii~i~~ N alii a ilil ~ e e e ee ee e ~^\~~ (' \:22 ~ ~:!lg ~ ~~~ A( ..~51 ,~ :2g~ '= ec~ " ~l!l!l ~Be; 8G.e 3= w :> z o i= <( > W ..J W Wd K:6S:Z1 EOOZ~" 'llOOAe1 '6"".ZlIu....Z1IOlC'1 JO!ld\J.,_'"_"MI:W - n ~ - V.LOS:iNNIW'IDIV'lllOHld NOLL VZIOlIVlINV.LS -:::.:=.,~':::r:...-= NOLLYlS.l.!Ir1 ....~=-.:'a:~~ .... 13 ~ '" ::0 III i 8 iE ~ 0:: ~ lil I I;j ~ u ~ if ~ ~ ~ i !~ I~ !~ . . .. <\ f;1' 9S . . l:~ z x. ..,0 ~Si~ ~ ~~~fil l:l .oilill ~ ::JizllI 0:: m~~~ (,)lj~ e .. -' ~ o o a:: j 1 aq u -' ~ o z o ~ a:: ~ z W ll.. I & ~ lD -' ~ o W <.'> ~ o ::c u z <l: ffi ~ gg <I: "'';ICIO!I~liJIr.:._'''l:II!CI~IYh'II!~O:IIIHJIt.:J''''''.'~I:k'l. ~::::gf X'(~ iiiiiiii '''!lll N" ..........," s.~ -'I"S ~tt6tH JDIJOW." UOIIO OgL t s I;i ~ o u lot fil ~. ~ i ><, ID ~d 0- i ~kJ g~i ><3iii" eiS.. .., 0 ~U ;~~~ ~~g ~~~I" i ~ ~ ~u~a~ ~!EilI ~~~j~ ~~~ i)"f)iz~ i5~S fil~ 2 bID.. ~~~~~ ~;; ~ ~~ti..9 onu~rJ l--. I :....:.: ,,~ .." .. '" ~. ~":::~ . . ....... ..:..... .. '. .~~..' ~ ~ ~~ i~ ~~ .... N ;::. s ~ !l:S ~ z ~ ~~~t ~ mi ~g~~~ ~ ~~ "Wz .. i:i~~ 0:: ~~ ~~:r 6 ;~:i~.. ~ ~~ lot g ~I~l , '1' L Q3Yln03Y Sf ~ e ~~... ~~i5..; gi~~ ~ 15~ 8~~m ~u, ~ ~..NQ J~~ -d~ l< ~gl;i Ii ~~'" ~ u'l!! :i ~~g ~ ~u~... I;i ~~~~ ~ ~~gi 8 ~ I;i '" u ~ u e u ~ Cl 0: z :5 ll.. W ~ ll.. W (f) <l: zm ~~ ~~ 3", ~! :z:~ z o i= ~ -' w i~ f ~! J fl!~ o i~ !Z~ l:z: -' ~ o 0::: o ::c u z : I ~ ~ "'" t:i w :I: III ~ ~ c z o ~ Iil t: :J c ~ ~ ~ "" .>:"':.1 (oozk~ .1....., 'liMp'>l!Q->>.II>llOl __MJOleMI:W lL. -' ~ o I- 0::: o ll.. ll.. :J III W ll.. a: t5 ~ ~ g w w a.. a: I- z W > 0::: o lL. -' ~ o 0::: :5 -' o u [51 ~i o ... --_ ---r-...~ EO-to-tO .... V~OS3NNIW '3>1V1l:fOIYd r .- - _1IU1"'~_ '" tu w :x: (/) OOLI-IK-nL 'I:tJ ..... ~ .. DOIt-ltS-OL ......" tttg; N" '1IIodDeuUlft 8SM m:~::~Df.low." uOIfO OSlt T- . ... .... NOIlVZJa~VaNV1S _-.- ,. ...... _ ~-:1:~~~ NOIl'v'lS 1~1l 8s Bs V? =<1> z: ------ 0 i= Bs Bs 1<1> ~ V? ]]]]]]]]]]] I- ~~~ !:!:: hJ~~ fHj N m ~ 0 ~U!n (/) =~! z: !:!2!!t::!!$!!~ ...J ... <( ~ I BBB ~ 0 !~ ]]]]]]]]]]] l.LJ ~~;~!~~ g l!l ~ I- H~H~~ 13 w => <<IalS=~::!::f uf 0 ~ <( I g ~ -' ]]]]]]]]]]] l.LJ Z ~~ ~ z: B~B~ <( R illi a.. 8~ -' !hid~ 0 B~ B ij))~B:e:B~ B~ ~ ~ z: 0 ..:f'oIl"f.ri.t-: <..) B~~B:e:B~8~~ -' <( 8~ ~~ ~!i! !~ II ~! / !! lu ~ ~~ ~'\ 2 i; ~ i ..;i ~ ~ lsi i .. i8~ ~~~ z: ; ~ ~ V? lil~ a si ~ ~~ l- V? N~ I- ~ ------ ~!i! i I ",,_\ ._, ... l.. ... ._... ._.... .._. .... ....-- --:--.._~.... ... -- -- -:::.:;z:~~;"~~I= _...",... I_":::-~ 5~ Bs B[9 Bs 8[9 Q ill ~ L1dJ I I ~~B CSI o ~ B:e: B~B~ B~ B ~~B:e: B:e: B:e: ~ 8:e: B~~B:e:B:e:B:e:~ 51 -' < I- W Cl l- V) < i ~ii ~ ~ '~J ~ !I !I~ ~~ 9 ':I'l< <Ii ~~ VlOS3NNIIIV '3>1V'1 UOIUd NOll 'ofZla~'ofaN'of lS NOll 'of lS 1.:111 ~ OOU-IK-['tL IVl ---'..-~'ll~ OQIt"IK-['tL iiiiiiiif ZZt~ N". ............u'" B.~ r.! .'1"5 OMq6!H IO!<IOW'" "0_10 osu. '" Iii w J: (I) SCD ICD I- ...-..............-..-..-.....--...........---.....-......... ~ I"') ]]]]]]]]]]] ]]]]]]]]]]] ]]]]]]]]]]] ................................------.-.-............"""'" V) z o i= < l- V) w ~U ~ ~~!i~~ ~ ;u5;~ ~ !!"~!!2!2 ~ :5 ~ -' i! C z ~~..~!!! ~ ~ uiu~~ ~ .._5f::~::!= ~ (zla('l .al :C::..__o 1~__""'7n1 """ CSI o i:i V) ;~ :z 0 i= r < !I l- V) I- .e ...... ~~ ::J I"') w Cl.. >- I-