HomeMy WebLinkAboutFire Sprinkler Inspection 3/27/2006
GILBERT MECHANICAL CONTRACTORS, INC.
REPORT OF INSPECTION
4451 W. 76th St. - Minneapolis, MN 55435
Office phone 952-835-3810 Fax 952-835-4765
Inspection # 2370
Inspection Date: 3/27/06
Billing Info171U1iion:
Name: North Lake Office Center
Address: 684 Excelsior Blvd
City, State, Zip: Excelsior, MN 55331
Job Information:
North Lake Office Center 3
14180 Commerce Ave NE
Prior Lake, MN 55372
~--- - -- -- - ~ - -~--- -- ----~- -~ -
No'
1. GENERAl.
a. Is the building occupied?
b. Is occupancy same as previons inspection?
c. Are all the systems in service?
d. Are all fire protection systems same as last inspection?
e. Is hazard completely sprinklered?
f. Are all new additions and building changes properly protected?
g. Is all stock or storage properly below sprinkler piping?
h. Was property free of fire since last inspection? (Explain any fire on Page 2)
I. In areas protected by wet system, does the building appear to be properly heated in all areas, including blind attics
and perimeter areas and are all exterior openings protected against entrance of cold air?
2. CONTROl, VALVES (See Section 16)
a. Are all sprinkler system main control valves open?
b. Are all other valves in proper position?
c. Are all control valves in good condition and sealed or supervised?
3. WATER SUPPLIES (See Section 17)
a. Was a water flow test made and results satisfactory?
4. TANKS, PUMPS FIRE DEPARTMENT CONNECTIONS
a. Are fIre pumps, gravity tanks, reservoirs and pressure tanks in good condition and properly maintained?
b. Are fIre department connections in satisfactory condition, couplings free, caps in place and check valves tight?
5. WET SY.',TEMS r,c;ee .<i;ection HI
Yes
x
X
x
X
X
X
x
X
X
X
Yes
X
X
X
N/A
No'
N/A
No'
a. Are cold weather valves open or closed as necessary? X
b. Have antifreeze systems been tested and left in satisfactory condition? x
c. Are alarm valves, water flow indicators and retards in satisfactory condition? X
a. Is dry valve in service and in good condition? X
b. Is air pressure and priming water level normal? X
c. Is air compressor in good condition? X
d. Were low points drained during fall and winter inspection? X
e. Are Quick Opening Devices in service? X
f. Has piping been checked for stoppage within past 10 years? x
g. Has piping been checked for proper pitch within past 5 years? X
h. Have dry check valves been trip tested satisfactorily as required? X
I. Are dry valves adequately protected from freezing? X
j. Valve house and heater condition satisfactory? x
a. Were valve systems tested as required? X
b. Were all heat responsive systems tested and results satisfactory? X
c. Were supervisory features tested and results satisfactory? X
a. Water motor and gong test satisfactory? X
b. Electric alarm test satisfactory? X
c. Supervisory alarm service test satisfactory? X
6. DRY SYSTEMS (See Section 141
7. SPECIAL SYSTEMS (See Section 181
8. ALARMS
9. SPRTNKLERS-PIPING
a. Are all sprinklers in good condition, not obstructed, and free of corrosion or loading?
b. Are all sprinklers less than 50 years old?
c. Are extra sprinklers readily available?
d. Is condition of piping, drain valves, check valves, hangers, pressure gauges, open sprinklers, strainers satisfactory?
e. Are all sprinklers of proper temperature rating?
f. Are portable fire extinguishers in good condition?
g. Is hand hose on sprinkler systems satisfactory?
Yes
No'
Yes
N/A
No'
N/A
No'
Yes
N/A
No'
Yes
N/A
'Explain "No" answers on Page 2
GILBERT MECHANICAL CONTRACTORS, INC.
4451 W. 76th St. - Minneapolis, MN 55435
REPORT OF INSPECTION
Inspection # 2370
Inspector: Dean Kaminski
10. Date Dry System Piping last checked for stoppage:
n. Date Dry System Piping last checked for proper pitch:
U. Date Dry Pipe Valve last trip tested:
13. Wet Systems: 1 Make and Model? 2 1/2"
32 Sec Retard
14. Dry Systems:
15. Special System,
Make and Model?
Type?
Make and Model?
Condition?
Good
16. CONTROL VALVES .
Open Secured Closed Signs
Number Type Yes No Yes No Yes No Yes No Condition
City Connection Control Valve 1 PIV X X X X
1st
Sectional Control Valves
System Control Valves 1 BFV X x x , x , ,
. .
17. WATER FLOW TEST
Water Pressure?
Water Flow Test?
103
CITY PSI
(If none made, Why?)
TANK PSI
FIRE PUMP PSI
Size Pressure Flow Pressure Size Pressure Flow Pressure
Test Pipe Located Test Pipe Before Pressure After Test Pipe Located Test Pipe Before Pressure After
Mech Room 1-1/4" 103 80 96
. ,
18. Heat Responsive Devices: Type of Test?
Valve # A B C D E F Valve # A B C D E F
Valve # A B C D E F Valve # A B C D E F
Valve # A B C D E F Valve # A B C D E F
Valve # A B C D E F Valve # A B C D E F
Auxiliary Equipment? Number? Type? Location? Test Results?
19. Explanation of any "No" answers:
20. Recent changes in building occupancy or fire protection equipment:
Another panel in daycare.
21. Adjustment or corrections made:
22. Desirable improvements:
Recall heads in one space, and paperwork has started to get heads replaced.