HomeMy WebLinkAboutFire Sprinkler Insp. 9/30/2005
,
"
OF
INSPECTION
CONTRACT NO.
PGS.
FIRE-GUARD
SPRINKLER SERVICE
INSPECTION
REPORT NO.
MN LICENSE NO:
C00018
2055 White Bear Ave. No.. Suite C
SI. Paul, Minnesota 55109.
PH: 651-748-9499 . FAX: 651-748-9143
CONFIRMED
WITH
REPORT TO:
STREET:
OWNER'S S ON (To be answered by owner or occupant)
A. Explain an occupancy hazard changes since the previous inspection. R~
B. Describe fire protection modifications made since last inspection.
C. Describe any fires since last inspection.
D. When was the system piping last checked for stoppage, corrosion or foreign material?
E. When was the dry-piping system last checked for proper pitch?
F. Are dry valves adequately protected from freezing?
INSPECTOR'S SECTION (All responses reference current inspection)
1. GENERAL
a. Is the building occupied? ......... .................................
b. Are all systems in service? .................
c.ls there a minimum of 18 in. (457 mm) clearance between the top
of the storage and the sprinkler deflector? ........................................
d. In areas protected by wet system, does the building appear to be
properly heated in all areas, including blind attics and perimeter
areas, were accessible? Do all exterior openings appear to be
protected against freezing? ......... ............................ ..........................
e. Does the hand hose on the sprinkler system appear satisfactory? ...
2. CONTROL VALVES (See item 14)
a. Are all sprinkler system control valves all all other valves in the
appropriate open or closed position?................................................
b. Are all control valves in the open position and locked, sealed or
equipped with a tamper switch?.................................
3. WATER SUPPLIES (See item 15)
a. Was a water flow test of main drain made at the sprinkler riser? .......
4. TANKS, PUMPS, FIRE DEPARTMENT CONNECTIONS
a. Are fire pumps, gravity tanks, reservoirs and pressure tanks in
good condition and properly maintained? ...........................
b. Are fire department connections in satisfactory condition,
couplings free, caps in place, and check valves tight? Are
they accessible and visible? .................................
5. WET SYSTEMS (See item 13)
a. Are cold weather valves (O.S.& Y.) in the appropriate open >t.-
or closed position? ....................................... ....................... ...............
b. Have antifreeze systems solutions been tested?..............................
c. Were the antifreeze test results satisfactory? ....................................
6. DRY SYSTEMS (See items 10 to 14 and attached report) ~
a. Is the dry valve in service?
b. Are the air pressure and priming water level in accordance
with the manufacturer's instructions? .................................................
BUREAU
FILE NO.
. -
BLDG. NAME:
ADDRESS:
CITY, STATE, ZIP: "
LICENSE NO.~O 3;).1-/
no
yes n.a. no
c. Has the operation of the air or nitrogen supply been tested?
Is it in service? .....................................................................................
d. Were low points drained during this inspection? .................................
e. Did quick-opening devices operate satisfactorily? ...............................
f. Did the dry valve trip properly during the trip pressure test? ...............
g. Did the heating equipment in the dry-pipe valve room operate
at the time of inspection?.....................................................................
10.
7. SPECIAL SYSTEMS (See item 16)
a. Did the deiuge or pre-action valves operate properly during testing?..
b. Did the heat-responsive devices operate properly during testing? ......
c. Did the supervisory devices operate during testing?...........................
8. ALARMS
a. Did water motor and gong test satisfactorily?.....................................
b. Did electric alarm test satisfactorily? ...................................................
c. Did supervisory alarm service test satisfactorily? ...............................
9. SPRINKLERS
a. Are all sprinklers free from corrosion, loading or obstruction to spray
discharge? ................................ ........... .................... .......... .......... ........
b. Are sprinklers over 50 years old, thus requiring sample testing? ........
c. Is stock of spare sprinklers available? .................................................
d. Does the interior condition of sprinkler system appear to be
satisfactory? .................................. .......... ..................... ........... ............
11.
Date dry-pipe valve trip tested (control valve par~'!.", ope~ _
(see trip test which follows) ......................~.:::JJ.J..,-:.U.7..........
Date dry-pipe valve trip tested (control valve fully open)
(see trip test which follows) .................................................................
12.
Date quick-opening device tested (see ASCOA trip test report) .........
13. Date deluge or preaction valve tested .................................................
14. See Control Valve Maintenance Table.
CONTROL MAINTENANCE TABLE
Control Valves
System Control Valves
Other Control Valves
. Type of Equipment
Manufacturer:
Auxiliary Equipment: No?
17. Explain any "No" answers and comments:
Explain Abnormal Condition
Test Pipe
Located
Size
Test Pipe
Pressure
Before
Flow
Pressure
Pressure
After
Condition:
Model:
S~
eft,
18. Adjustments or corrections made during this inspection:
19. Although these comments are not the result of an engineering review, the following desirable improvements are recommended:
fh~5
WHITE: CLIENT
YELLOW: OFFICE
PINK: INSURANCE AUTHORITY
FIRE-GUARD
SPRINKLER SERVICE, INC.
2055 White Bear Ave. No., Suite C
St. Paul, Minnesota 55109
PH: 651-748-9499 . FAX: 651-748-9143
MN License No. C00018
NO.2
NO.3
SIZE, MAKE, MODEL & YEAR '7" ~f~l
OF MANUFACTURER
CONTROL SPRINKLERS IN J1J~f- d' ~
PRESSURE (LB.) AIR 30
BEFORE TESTS WATER )02>
CONTROL VALVE WIDE OPEN? ]-+-vr(\S
(IF NOT, HOW MANY TURNS?)
OPERATED AT: ~
AIR PRESSURE (LB.) J~ r~l
TIME (MIN., SEC.) -
OPERATION INDICATE: SAT
(SATISFACTORY, PARTLY
SATISFACTORY, OR FAILED)
REASON FOR FAILURE OR )lcY1 C2.-
PARTLY SATISFACTORY
VALVE RESET DRY? 'yE>5
LIST REPAIRS MADE (~~
CONDITION: <4~
INTERIOR OF BODY ,J
WATER FROM TEST PIPE
MOVING PARTS
SEALS
RUBBER FACING
ALARMS OPERATED? ~ S
~
QUICK OPENING DEVICES
MAKE, MODEL, YEAR
OPERATION INDICATE:
SATISFACTORY, FAILED OR SHUT OFF
SIGNATURE AND TITLE OF PERSON MAKING TESTS
fNt
MPANY~~ANDADDRESS
9~YJ~ 0')
DATE OF EXAMINATION
WITNESS (OWNER OR LEASEE OF THE PROPERTY)
WHITE: CLIENT
YELLOW: OFFICE
PINK: INSURANCE AUTHORITY